KSUG 

CONTROL AND 

MONITORING UNIT 

Valid from week of manufacture 2014.50 

 and software version 1.0. 

Description 

The KSUG is a control and monitoring unit 

designed to control various types of fire/smoke 

dampers and fans in a flexible way. The 

KSUG can be connected to the KSUA, or as a 

completely stand-alone unit. There are damper 

connections and two smoke detector 

connections. These units can be grouped in 1 

or 2 fire zones. Each damper and detector can 

be monitored individually. A ventilation 

system can be connected to the KSUG for 

locking. The KSUG has an input for an 

external fire alarm and for night mode. The 

KSUG can be switched for three actuator 

types. RF technologies MANF VD24, VM24 

and Belimo BSIA24 with BR24-F-ST. 

General 

 

Slave unit for KSUA. 

 

RF technologies MANF VD24 or MANF 

VM24 actuator. 

 

Belimo BR24-F-ST actuator with BSIA24. 

 

Can be used as a stand-alone unit. 

 

Two dampers. 

 

Two detector inputs. 

 

Built-in locking of fans. 

 

48-hour clock for damper exercises 

 

External input for central fire alarm system. 

 

Night mode input. 

 

Damper position indication. 

 

Integrated transformer. 

 

Many selectable options. 

 

Jackable terminals. 

Maximum configuration 

The KSUG can handle two dampers and two 

detector groups. 5 smoke detectors on each 

input. These smoke detector groups and fire 

dampers can then be grouped into a maximum 

of two fire zones. One output for fan control.  

 

Installation 

Designed for wall installation. 

Power supply 

230 VAC 50 Hz  30VA. Protected with 2 A at 

least. 

Protection class 

IP66. 

Ambient temperature 

Max +30

°

C, min 0

°

C. 

Weight 

1.5 kg 

Outputs 

 

Sum alarm. Voltage-free changeover 

contact 5A max 250V. Terminal numbers 

10,11,12. 

 

Triggered smoke detector, shared by all fire 

zones. Voltage-free changeover contact 5A 

max 250V. Terminal numbers 7,8,9. 

 

FAN 1. Voltage-free changeover contact 

max 5A / 250V. Terminal numbers 

13,14,15. 

 

Damper 1. 

 

Damper 2. 

Summary of Contents for KSUG

Page 1: ...with BR24 F ST General Slave unit for KSUA RF technologies MANF VD24 or MANF VM24 actuator Belimo BR24 F ST actuator with BSIA24 Can be used as a stand alone unit Two dampers Two detector inputs Built...

Page 2: ...ycle Definitions Ventilation dampers Dampers that are closed by a spring Evacuation dampers Dampers that are opened by a spring Day mode Ventilation dampers open and evacuation dampers closed Night mo...

Page 3: ...umper F H Stand alone mode Network mode Choice of damper actuator Jumper F and G selects the actuator type to be used If jumper F is ON Belimo BSIA24 and BR24 F ST If jumper G is on RFT MANF VM24 type...

Page 4: ...mper is closed Various jumper settings can be used to prevent fan locking Jumper On Off 2 Do not stop in night mode Stop in night mode 16 Do not stop for test Stop for test F No fan delay 30 s delay S...

Page 5: ...ons be switched Is that the case terminal 4 and 5 in the KSUG must be switched Be aware of Jumper 8 F and G for selection of actuator type in stand alone or network mode Shown without power 13 14 is c...

Page 6: ...t jumper F must be ON and 8 OFF in stand alone mode In network mode jumper F must be ON and G OFF Smoke detector inputs The two smoke detector inputs are designed for a loop resistance of 2200 ohm ter...

Page 7: ...within the time specified for the particular actuator The actuator contacts are correctly closed with the dampers in the off position The dampers go to normal position within the time specified for th...

Page 8: ...MP1 and jumper 4 ON That the dampers open and that the green LED is normal Carry out a manual function test and check that the dampers operate within 2 seconds if the MANF VD24 is used The red LED lig...

Page 9: ...must be sent to a collection point that recycles electrical and electronic equipment By making sure this product is correctly processed you will help to prevent the negative impact on the environment...