Amplifier Units can be easily mounted to 35-mm DIN Track.
■
Installation
(1)Hook the connector end of the
Amplifier Unit on the DIN Track
(2)Press in at the bottom until the Unit
locks into place.
CHECK!
Always hook the connector end of
the Amplifier Unit on the DIN
Track first. Mounting strength may
decrease if the output cable end
is hooked on the DIN Track first.
■
Removal
(3)Push the Amplifier Unit
(4)Up and pull out from the connector
end.
■
Connecting
Push the Sensor Head connector into the Amplifier Unit
connector until it locks.
■
Disconnecting
To disconnect the Sensor Head, hold the Sensor Head's
connector ring and the Amplifier Unit connector, and then pull
them straight out.
Check!
・
Do not touch the terminals inside the connector.
・
When connecting another type sensor head, the setting data in the amplifier unit is
cleared.
・
The input/output cable has the following wires.
CHECK!
Wire the cable correctly. Incorrect wiring may damage the Smart Sensor.
*1 Select the analog output style by menu mode.
*2 Please see the user's manual about other specifications and functions.
(UNIT:mm)
Item
Applicable Sensor
Units
Power supply voltage
Power consumption
Measurement cycle
Response time
Analog output *1
Judgement outputs
HIGH/PASS/LOW:
3output
ERORR output
LD-OFF input
Zero reset input
Timming input
Reset input
Bank input
Surrounding air temperature
Ambient humidity
Dialectic strength
Vibration resistance
(destructive)
Shock resistance
(destructive)
Degree of protection
Materials
Weight (packed state)
ZX2-LDA11
ZX2-LDA41
ZX2-LD
□□
Model
10 to 30 VDC (including ripple 10%p-p) Class 2
3,000mW max. (Power supply voltage: 30V, Current consumption: 100mA max.)
(Senser connected)
min.30μs
60μs, 120μs, 240μs, 500μs, 1ms, 2ms, 4ms, 8ms,
12ms, 20ms, 36ms, 66ms,128ms, 250ms, 500ms
For current output:4 to 20 mA/F.S. maxmum load 300
Ω
For voltage output:±5VDC or 1 to 5V output impedance 100
Ω
Operating: 0 to 50°C, Storage: -15 to 70°C (with no icing or condensation)
Operating and storage: 35% to 85% (with no condensation)
1,000 VAC, 50/60 Hz for 1 min
10 to 150 Hz, 0.7-mm double amplitude,
80 min each in X, Y, and Z directions
300 m/s
2
3 times each in six directions
(up/down, left/right, forward/backward)
IP40
PBT (Case), PC (Cover), Polyacetal(Button)
Approx.200g (sensor head:Approx. 135g)
NPN open-collector outputs,
30VDC, 50mA max. Resistive.
Residual voltage:
1V max. at 10mA load current max.
2V max. at 10mA load current over
ON: Short-circuited with 0V
terminal or 1.2V or less
OFF: Open
(leakage current: 0.1mA max.)
PNP open-collector outputs,
30VDC, 50mA max. Resistive.
Residual voltage:
1V max. at 10mA load current max.
2V max. at 10mA load current over
ON: Supply voltage Short-circuited
or within supply voltage -1.2V max.
OFF: Open
(leakage current: 0.1mA max.)
Checking the package contents
1.Specifications
4.Wiring Input/Output Cables
5.Dimensions
6.Part Names and Functions
2.Installing the amplifier unit
3.Connecting the Sensor Head
(1) Power suplly(10 to 30 VDC)
(2) GND(0V)
(3) HIGH judgement output
(4) PASS judgement output
(5) LOW judgement output
(6) Error output
(7) Linear output
(8) Linear GND
(9) LD-OFF input
(10) Zero reset input
(11) Timing input/ Bank0 input
(12) Reset input/ Bank1 input
①
End plate(option)
②
③
④
72 (When the cover opened: 84.6)
6.
2
3.
1
4.
2
38.4
VINYL INSULATED ROUND
CORD 5.2 Dia. 11 CORES
(
COMDUCTOR CROSS SECTIONAL AREA: 0.09mm
2
/
INSULATION OUTSIDE DIAMETER:0.7mm Dia.)
STANDARD LENGTH:2m
16.6
6.1
20.
7
36.
8
9.6
34.2
47.
6
10.9
15.4
16.9
30
18
11.7
(1)Input Cable
The input cable connects the Sensor Head.
(4)Laser indicator
The Laser indicator lights while the Sensor Head is
emitting a laser beam.
(12)Corsor button
The Control Keys select
measurement conditions
and make other settings.
(13)Smart tuning button
When the measurement parameter is
set to the best condition, a smart button
is used.
(15)HIGH threshold indicator
The HIGH indicator lights while the sub
display show High threshold.
(16)LOW threshold indicator
The LOW indicator lights while the sub
display show the low threshold.
(17)MENU indicator
The MENU indicator lights while the
amplifier unit is in the menu mode.
(14)MENU/ SET button
The MENU/ SET button selects
the operating mode and set
measurement conditions.
(7)HIGH indicator
The HIGH indicator
lights when the
judgement result
is HIGH.
(8)PASS indicator
The PASS indicator lights
when the judgement result
is PASS.
(9)LOW indicator
The LOW indicator lights
when the judgement
result is LOW.
(10)Main display
The main display shows
measured values
and function names.
(11)Sub-display
The sub-display shows
additional information and
function settings for
measurements.
(5)Zero Reset indicator
The Zero Reset indicator lights when the zero reset
function is enabled.
(6)ENABLE indicator
The ENABLE indicator lights when the Sensor is ready for
measurement. It goes off when measurement is not possible
(e.g. when the received light amount is excessive or insufficient,
when the measuring range is exceeded, or when the Sensor
Head is not connected when the power is turned ON).
Operating Section(*)
Display Section(*)
(*) Operating and Display Section
(2)Connector (two connectors, one on each side)
The connectors connect Calculation Units.
(3)Output Cable
The output cable connects the sensor to the power
supply and external devices, such as sync sensors
or programmable controllers.
©
OMRON Corporation 2010 All Rights Reserved.
INSTRUCTION SHEET
Model
ZX2-LDA
□□
Smart Sensor
Laser Displacement Sensor CMOS type
Amplifier units For Model ZX2-LD
□□
Thank you for selecting OMRON product. This sheet primarily describes
precautions required in installing and operating the product. Before operating
the product, read the sheet thoroughly to acquire sufficient knowledge of
the product. For your convenience, keep the sheet at your disposal.
Refer to the user’s manual for details.
PRECAUTIONS ON SAFETY
●
Keys to Warning Symbols
●
Warning Symbols
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury or in
property damage.
Do not use it exceeding the rated voltage. There is a
possibility of failure and fire.
Do not connect amplifier units to AC power supply. Risk
of explosion.
Indicates prohibition when there is a risk of minor injury
from electrical shock or other source if the product is
disassembled.
CAUTION
CAUTION
Please observe the following precautions for safe use of the products.
(1)Installation Environment
・
Do not use the product in environments where it can be exposed to inflammable/explosive gas.
・
To secure the safety of operation and maintenance, do not install the product close to high-voltage
devices and power devices.
(2)Power Supply and Wiring
・
The supply voltage must be within the rated range (DC10 to 30V including ripple 10%(peak to peak)).
・
Reverse connection of power supply is not allowed. Connection to AC power supplies also not allowed.
・
Open-collector outputs should not be short-circuited.
・
High-Voltage lines and power lines must be wired separately from this product. Wiring them together
or placing them in the same duct may cause induction, resulting in malfunction or damage.
・
Always turn off the power of the unit before connecting or disconnecting cables.
(3)Other Rules
・
Do not attempt to disassemble, deform by pressure, incinerate, repair, or modify this product.
・
When disposing of the product, treat as industrial waste.
・
If you notice an abnormal condition such as a strange odor, extreme heating of the unit, or smoke,
immediately stop using the product, turn off the power, and consult your dealer.
Please observe the following precautions to prevent failure to operate, malfunctions, or undesirable
effects on product performance.
(1)Do not install the product in locations subjected to the following conditions:
・
Surrounding air temperature outside the rating
・
Rapid temperature fluctuations
・
Relative humidity outside the range of 35 to 85%
・
Presence of corrosive or flammable gases
・
Presence of dust, salt, or iron particles
・
Direct vibration or shock
・
Reflection of intense light (such as other laser beams, electric arc-welding machines, or ultra-violet light)
・
Direct sunlight or near heaters
・
Water, oil, or chemical fumes or spray, or mist atmospheres
・
Strong magnetic or electric field
(2)Power Supply and Wiring
・
When using a commercially available switching regulator, make sure that the FG terminal is grounded.
・
If surge currents are present in the power lines, connect surge absorbers that suit the operating
environment.
・
When using two ore more amplifier units, make sure that the linear GND line of the amplifier units are
connected to each other.
・
When using two ore more amplifier units, turn the power on the amplifier units at the same time.
・
Before turning ON the power after the product is connected, make sure that the power supply voltage is
correct, there are no incorrect connections (e.g. load short-circuit) and the load current is appropriate.
Incorrect wiring may result in break down of the product.
・
The cables must be 10m or shorter in total length, for amplifier units. To extend the cable from the
sensor head, an optional extension cable (ZX2-XC
□
R) must be used. For extension of the cable of
amplifier units, shielded cables of the same type must be used.
・
The sensor is certificated by the UL standard on the assumption of the following installation conditions.
・
It is based on the assumption of usage in “Class 2 circuit” . Please use it with “Class 2 power
supply” in the United States or Canada. The current rating of overcurrent protection is 0.8A max.
・
It is certificated as open type. The sensor shall be installed within an enclosure.
・
Rating of the cable is 30V. Please use it as internal cable wiring only in the end products equipment.
(3)Warming Up
・
After turning on the power supply, allow the Controller to stand for at least 10 minutes before use. The
circuits are unstable immediately after the power supply is turned on and attempting measurement may
result in inconsistent measurement values.
(4)Maintenance and inspection
・
Always turn off the power of the unit before connecting or disconnecting cables.
・
Do not use thinner, alcohol, benzene, acetone, or kerosene to clean the amplifier units.
PRECAUTIONS FOR SAFE USE
PRECAUTIONS FOR CORRECT USE
・
Amplifier units Sensor head ×1
・
Manual (this paper) ×1
Brown
Blue
White
Green
Gray
Yellow
Black
Shield
Pink
Orange
Purple
Red
Brown
Blue
White
Green
Gray
HIGH
judgement output
PASS judgement output
DC10 to 30V
DC10 to 30V
LOW judgement output
Yellow Error output
GND(0V)
Pink
Purple
Orange
Red
Black
Current / voltage
output
Switch
Current output
4 to 20mA
Voltage output
±5V
1 to 5V
Shield
LD-OFF input
Zero reset input
Linear output
Current output:300
Ω
or lower
Voltage output:10k
Ω
or higher
100
Ω
Timing input /
Bank0 input
Reset input /
Bank1 input
Linear GND
Internal circuit
Load Load Load Load
Load
DC
10 to 30V
Current / voltage
output
Switch
Current output
4 to 20mA
Voltage output
±5V
1 to 5V
Current output:300
Ω
or lower
Voltage output:10k
Ω
or higher
100
Ω
Brown
Blue
White
Green
Gray
HIGH
judgement output
PASS judgement output
DC10 to 30V
LOW judgement output
Yellow Error output
GND(0V)
Pink
Purple
Orange
Red
Black
Shield
LD-OFF input
Zero reset input
Linear output
Timing input /
Bank0 input
Reset input /
Bank1 input
Linear GND
Internal circuit
Load Load Load Load
Load
・
I/O Circuit Diagrams
NPN Amplifier Unit
PNP Amplifier Unit
The following notice applies only to products that carry the CE mark:
Notice:
This is a class A product. In residential areas it may cause radio
interference, in which case the user may be required to take adequate
measures to reduce interference.
Manufacturer:
Omron Corporation,
Shiokoji Horikawa, Shimogyo-ku,
Kyoto 600-8530 JAPAN
Ayabe Factory
3-2 Narutani, Nakayama-cho,
Ayabe-shi, Kyoto 623-0105 JAPAN
TRACEABILITY INFORMATION:
Representative in EU:
Omron Europe B.V.
Wegalaan 67-69
2132 JD Hoofddorp,
The Netherlands