2-2
Molded-case Circuit Breaker (MCCB)
Be sure to connect MCCBs between power supply and SYSDRIVE 3G3IV
input terminals L1 (R), L2 (S), L3 (T). Recommended MCCBs are listed in the
table below.
When a ground fault interrupter is used, select the one with no influence for
high frequency, and setting current should be 200mA or over and operating
time, 0.1 s or over to prevent malfunction.
Molded-case Circuit Breakers and Magnetic Contactors
SYSDRIVE
Molded-case circuit
breaker or fuse
Model 3G3IV
Capacity
Rated output
current
Rated current
200 to 230V
A2004-
1.4
3.2
6 A
A2007-
2.1
4.8
10 A
A2015-
2.7
6.4
20 A
A2022-
4.1
9.6
20 A
A2037-
6.9
16
30 A
A2055-
10.3
24
50 A
A2075-
13.7
32
60 A
B2110-
20.6
48
100 A
B2150-
27.4
64
100 A
B2185-
34
80
150 A
B2220-
41
96
150 A
B2300-
54
130
225 A
B2370-
68
160
225 A
B2450-
78
183
300 A
B2550-
95
224
400 A
B2750-
130
300
600 A
400 to 460 V
A4004-
1.4
1.6
5 A
A4007-
2.2
2.6
5 A
A4015-
3.4
4.0
10 A
A4022-
4.1
4.8
10 A
A4037-
6.9
8
20 A
A4055-
10.3
12
20 A
A4075-
13.7
16
30 A
B4110-
20.6
24
50 A
B4150-
27.4
32
60 A
B4185-
34
40
80 A
B4220-
41
48
100 A
B4300-
54
64
100 A
B4370-
68
80
150 A
B4450-
82
96
150 A
B4550-
110
128
225 A
B4750-
140
165
300 A
B411K-
200
224
400 A
Section 2-2
Summary of Contents for SYSDRIVE 3G3IV
Page 3: ...0 1 2 3 2 4 2 5 4 67 1 5 5 0 8 2 2 4 8 3 9 2 6 0 8 5...
Page 4: ...0 33 3 0 3 3 0 33 3 3 0 33 3 0 3 3 0 3 0 3 4 5 1 3 5 4 0 33 0 5 5 0 5 5 3 6 2...
Page 6: ...1 9 2 6 0 A 1 5 2...
Page 9: ...1 9 2 6 0 0 1...
Page 22: ...1 9 2 6 0 2 3 2 4 2 5 4 67 1 5 5 0...
Page 29: ...1 9 2 6 0 A 1 8 2 2 4 8 3...
Page 33: ...1 8 9 2 6 0 9 2 6 0 8 5...
Page 38: ...A 9 2 6 0 0 33 3 0 3 3 0 33 3 3 0 33 3 0 3 3 0 3 0 3 4 5 1 3 5 4 0 33 0 5 5 0 5 5 3...