4-1
Maintenance
SYSDRIVE 3G3IV requires very few routine checks. It will function longer if it
is kept clean, cool and dry, while observing the precautions listed in “Loca-
tion”. Check for tightness of electrical connections, discoloration or other
signs of overheating. Use the table below as the inspection guide. Before
servicing, turn off AC main circuit power and be sure that CHARGE lamp is
off.
Periodical Inspection
Component
Check
Corrective Action
External terminals, unit mounting
b lt
t
t
Loosened screws
Tighten
g
bolts, connectors, etc.
Loosened connectors
Tighten
Cooling fins
Build-up of dust and dirt
Blow with a dry compressed air of 4 to
6kg-cm
2
(57 to 85 Ibs. in
2
) pressure.
Printed circuit board
Accumulation of conductive dust or oil
mist.
Clean the board. If dust and oil cannot
be removed, replace the board.
Cooling fan
For abnormal noise and vibration.
Whether the cumulative operation
time exceeds 20,000 hours or not.
Replace the cooling fan.
Power elements
Accumulation of dust and dirt
Blow with a dry compressed air of 4 to
6kg-cm
2
(57 to 85 Ibs. in
2
) pressure.
Smoothing capacitor
Discoloration or odor
Replace the capacitor or inverter unit.
Note Operating conditions as follows:
•
Ambient temperature: 30
°
C (86
°
F)/yearly mean
•
Load factor: 80% or below
•
Operation rate: 12 hours or below/day
Section 4-1
Summary of Contents for SYSDRIVE 3G3IV
Page 3: ...0 1 2 3 2 4 2 5 4 67 1 5 5 0 8 2 2 4 8 3 9 2 6 0 8 5...
Page 4: ...0 33 3 0 3 3 0 33 3 3 0 33 3 0 3 3 0 3 0 3 4 5 1 3 5 4 0 33 0 5 5 0 5 5 3 6 2...
Page 6: ...1 9 2 6 0 A 1 5 2...
Page 9: ...1 9 2 6 0 0 1...
Page 22: ...1 9 2 6 0 2 3 2 4 2 5 4 67 1 5 5 0...
Page 29: ...1 9 2 6 0 A 1 8 2 2 4 8 3...
Page 33: ...1 8 9 2 6 0 9 2 6 0 8 5...
Page 38: ...A 9 2 6 0 0 33 3 0 3 3 0 33 3 3 0 33 3 0 3 3 0 3 0 3 4 5 1 3 5 4 0 33 0 5 5 0 5 5 3...