Compact Non-Contact Door Switch

INSTRUCTION MANUAL

Thank you for purchasing D40A Compact Non-contact 
Door Switch. Please read and understand this manual 
before using the products. Keep this manual ready to 
use whenever needed. Only qualified person trained 
in professional electrical technique should handle 
D40A. Please consult your OMRON representative if 
you have any questions or comments. Make sure that 
information written in this document are delivered to 
the final user of the product.

Type D40A

English

2139497-6C

Machine may start operating and may result serious 
injury or death.
Do not put the actuator close to the switch when the 
door is opened.
Also make sure to install D40A to minimize defeat 
possibilities. For required measures, refer to ISO14119 
and other relevant standards and regulations.

Safety Precautions

Meanings of Signal Words
The following signal words are used in this manual.

Indicates mandatory actions.

Meaning of Alert Symbols
The following alert symbols are used in this manual.

Alert Statements

WARNING

WARNING

Indicates a potentially hazardous 
situation which, if not avoided, will 
result in minor or moderate injury, or 
may result in serious injury or death. 
Additionally there may be significant 
property damage.

(1) Disconnect G9SX-NS

…

 from power supply when wiring D40A. 

Devices connected to G9SX-NS

…

 may operate unexpectedly.

(2) Do not operate the D40A with flammable or explosive gas. 
(3) Incorrect wiring may lead to loss of safety function. Wire 

conductors correctly and verify the operation of D40A  before 
using the system in which D40A is incorporated. 

(4) Auxiliary monitoring output is NOT safety output. Do not use 

auxiliary monitoring output as any safety output. Such incorrect 
use causes loss of safety function of D40A and its relevant system.

(5) After installation of D40A, qualified personnel should confirm the 

i n s t a l l a t i o n ,   a n d   s h o u l d   c o n d u c t   t e s t   o p e r a t i o n s   a n d  
maintenance.The qualified personnel should be qualified and 
authorized to secure the safety on each phases of design, 
installation, running, maintenance and disposal of system.

(6) A person in charge, who is familiar to the machine in which D40A 

is to be installed, should conduct and verify the installation.

(7) Be sure to inspect D40A daily and every 6 months. Otherwise, 

serious injury may possibly occur due to the system malfunction.

(8) Do not dismantle, repair, or modify D40A.  Doing so may lead to 

loss of its safety functions.

(9) Use only appropriate components or devices complying with relevant 

safety standards corresponding to the required level of safety 
category. Conformity to requirements of safety category is determined 
as an entire system. It is recommended to consult a certification body 
regarding assessment of conformity to the required safety level.

Precautions for Safe Use

(1) D40A must be used with designated actuator (D40A-1C or -A1) 

and designated controller type G9SX-NS

…

. Before using the D40A 

with any other OMRON Safety Controller, check applicability in the 
Instruction Manual for the other Controller.

(2) Handle with care

Do not drop D40A to the ground or expose to excessive vibration 
or mechanical shocks. D40A may be damaged and may not 
function properly.

(3) Conditions of storage and usage

Do not store or use the D40A under the following conditions. 
D40A may be damaged and may not function properly.
1) In direct sunlight
2) At ambient temperatures out of the range of –10 to 55°C
3) At relative humidity out of the range of 25% to 85% or under 

such temperature change that causes condensation.

4) In corrosive or combustible gases
5) With vibration or mechanical shocks out of the rated values.
6) Under splashing of oil or chemicals
7) In the atmosphere containing dust, saline or metal powder.
8) Where steel scrap or metal powder may fall directly to D40A.

(4) Use cables with length less than 100m totally to connect multiple 

D40A switches. 

The supply voltage to D40A may decrease by the 

voltage drop depending on the cable or the wiring configuration. 
Check the power-supply vloltage is in the rated range.

(8) Do not use the D40A in the water or continuous water exposure 

environment. Water may lead into the D40A.

(9) Do not use the switch or actuator as a stopper. Protect the switch 

and the actuator by setting up the stopper. Separate the  switch 
and the actuator to a distance of 1mm or more.

(10) Install D40A actuator and switch in an appropriate distance so 

that it does not create a gap accessible to the hazard.

Precautions for Correct Use

D1 D2 D3 D4

G9SX-NS202
G9SX-NSA222

Total wiring length 100m max.

(5) Disconnect G9SX-NS

…

 from power supply when replacing D40A. 

Devices connected to G9SX-NS

…

 may operate unexpectedly.

(6) Adhesion of solvent such as alcohol, thinner, trichloroethane or 

gasoline on the product should be avoided. Such solvents make 
the marking on D40A illegible and cause deterioration of parts.

(7) Do not use D40A in the magnetic field of 1.5mT or more. D40A 

may not function properly. 

Dimensions

6

Indicator

Two. 4.2 dia.

7.2 dia.

7.2 dia.

Cable diameter : 4
Cross section 
of conductor: 
0.2mm

2

 (AWG24)

7.2 dia.

 7.2 dia.

Two. 4.2 dia.

Actuator

Switch

(1.5)

(2)

48

38

20

25

13

Sensing surface

17

12

13

6

48

38

Target mark

Target mark

(150)

(46)

M12

Sensing surface

15 dia.

Sensing surface

z

 D40A-1C015-F

Connection Example

5

D1 D2 D3 D4

G9SX-NS202
G9SX-NSA222

Black

Brown

White

Blue

Black

Brown

White

Blue

Black

Brown

White

Blue

z

 Single switch connection

z

 Multiple switch connection

Maximum 30 switches can be connected in series.

Note 1. Maximum auxiliary output current is 10mA.

D1 D2 D3 D4

Black

Brown

White

Blue

Y

ellow

G9SX-NS202
G9SX-NSA222

D40A-1C

…

aux. output load

*Note 1

A2

See “  1   Detection ranges”

Ratings and Specifications

4

z

  Ratings

z

  Specifications and Performance

Item

Rated power consumption

Auxiliary output

D40A-1C

…

0.6W Max.  (See Note1)

Load: 24VDC  10mA
(PNP open-collector output)

Assured 
operating 
and 
release 
distance

Ambient temperature

Ambient humidity

Degree of protection

Material

Mounting method

Terminal tightening torque

5mm min.   

(See Note2)

-10 to +55

°

C

(No freezing or condensation)

25 to 85%RH

Switching frequency

+]ZLWK*6;16Ƒ

Insulation resistance

(Between all conductive parts and switch case)

(Between all conductive parts and switch case)

50Mohm Min.

(by 500VDC megger)

Dielectric strength

1000VAC for 1min

Vibration resistance

Frequency: 10 to 55 to 10Hz,
Amplitude: 0.75mm half amplitude

Mechanical shock resistance

300m/s

2

 Min.

IP67

Molded PBT

M4 screws

1N•m

Relaiability data
(ISO 13849-1)

MTTFd = 100 year, DC = 60%

*This data does not include the 

values of a safety controller.

Item

Rated impulse 
withstand voltage

1kV

D40A-1C

…

OFF

p

ON

ON

p

OFF

Differential travel

Temperature influence

15mm max. 

(See Note2)

Note1. Power consumption of loads is not included.
Note2. Operating distance means the distance of sensing surfases 

between switch and actuator.

See “  1   Detection ranges”

Repeat
accuracy (max.)

±

10% of operating distance at 23

°

C

Pollution degree

3

Electromagnetic compatibility As per IEC/EN 60947-5-3

Performance Level / Safety Category

7KH '$ WRJHWKHU ZLWK *6;16Ƒ FDQ FRQVWUXFW WKH FRQGLWLRQ

conforming to PL=d and Category 3 required by EN ISO 13849-1 
European standard.
Refer to the following link for the Safety-related characteristic data:
http://www.fa.omron.co.jp/safety_6en/
This does NOT mean that D40A and G9SX-NS

…

 can always be used 

for required category under all the similar conditions and situations.
UL does not provide UL certification for any functional safety rating 
or aspects of the D40A device.
Conformity to the categories must be assessed as a whole system. 
When using D40A and G9SX-NS

…

 for safety categories, make sure 

the conformity of the whole system. 

Inspection & Maintenance

 Daily inspection:

1.Check every guard door to see that machine stops
   when guard door is opened.

• 6-month inspection:

1. Isolate all power.
2. Check the switch and actuator for proper alignment.
3. Check terminals for proper connections.
4. Check wiring for signs of damage.
5. Before resuming normal machine operation, 
    check every guard door to see that machine stops
    when the guard door is opened.

Troubleshooting

D40A

Light off

NS Light off

Red

Light on

NS Light off

Yellow

Light on

NS Light off

or NS Blink

Failures involving the wiring of power supply input

Check that the brown and the blue cable are correctly connected
with G9SX-NS

…

’s D3 terminal and terminal D4 respectively. 

Installation on magnetic substance

Installation in the vicinity of magnetic source

Failures of the parts of the circuits of D40A

Failures involving the wiring of D40A input

Failures involving the wiring of D40A outputs

Failures of the parts of the circuits of D40A

G9SX-NS

…

 Note 1. When actuator is approximated to the switch.

Expected causes of the faults

Checking points and measures to take

LED indicator  Note1

Failures of the parts of the circuits of D40A

Replace with a new D40A

Install the switch and actuator on a non-magnetic material. 

Install D40A separate from a strong magnetic source.

Replace with a new D40A

Check that the white cable is correctly connected with G9SX-NS

…

’s D1 terminal. 

Check that the black cable is correctly connected with G9SX-NS

…

’s D2 terminal. 

Replace with a new D40A

z

 Wiring

Signal Name

Cable color

brown

blue

+

-

white

black

yellow

Non-contact door 
switch power input

Non-contact door switch
signal input

Non-contact door switch output

Auxiliary monitoring output 
(PNP open corrector output)

Description of operation

Power supply for D40A.
Connect to D3 terninal and D4 terminal on G9SX-NS

…

.

Input designated signal from G9SX-NS

…

.

To set non-contact door switch output in ON state, non-contact door
switch input must be in ON state.

Output status depends on actuator status and non-contact door switch
input state.

Output when sensor detect actuator.

Pim number

1

3

2

4

5

(15) Wiring

1.Use the following to wire to G9SX-NS 
   -Solid wire: 0.2 to 2.5mm

2

  AWG24 to AWG12

   -Stranded wire: 0.2 to 2.5mm

2

 AWG22 to AWG12

2.When auxiliary output is not used, cut off the wiring and 

protect by taping so that it does not contact other terminals.

3.When you use an additional cable of 20m or longer, 

use a multiconductor cable to group the white, black, 
brown, and blue lines together.

(16) Handle cables with care:

1) For bending cables, it is recommended to bend them 

with a radius of bend no less than six times the cable 
outer diameter.

2) Do not apply a tensile strength of 50N or greater to the 

cables.

(17) This is a class A product. In residential areas it may cause 

radio interference, in which case the user may be required 
to take adequate measures to reduce interference.

(18) If there is any machine that has a large surge current(e.g., 

a motor) near D40A, connect a surge absorber to D40A 
between the blue and the other lines (white, black, brown, 
and yellow), respectively.

Suggested surge absorber's specification is as follows:

3HDNSXOVHSRZHU:ȝVRUPRUH

(Per IEC61000-4-5(surge immunity)) 
-Breakdown voltage: 27-33V

Note1. The operating distance is the distance between the switch and 

actuator sensing surfaces.

Note2. The graph indicates shifting to X or Z direction from following 

condition that the switch and actuator target marks are on the same 
axis and the sensing surfaces are exactly parallel condition.
Dashed lines indate reference value for maximum and minimun 
oprating distance at abient tempe23°C. The solid line indicates 
reference values of the maximum and minimum operating distances.

Switch and actuator operation

2

z

  Switch and Actuator Mounting Directions

z

  Switch and Actuator Operating Directions

Switch

Actuator

Switch

Actuator

Detection Ranges (Engineering data)

1

(11)   Where two or more switches mounted adjacent, they should be 

no closer than 25mm. 

(12)  Check that the machine is stopped whenever the interlocked 

guard door is open.

25mm Min.

(13)  Do not mount the switch and actuator on magnetic materials, 

otherwise it may affect the operating distance.

        Refer to the chart below for the estimated influence.

(14)  Tighten each screw with specified torque by using M4 screw 

and washer for the installation of the switch and actuator. After 
installation and commissioning, the actuator and switch fixing 
screws should be coated with tamper proof varnish or similar 
compound.Using anaerobic locking compounds can have a 
detrimental effect on the plastic switch case if the compounds 
contact with the switch case.

Switch

Actuator

Distance from 
magnetic materials

Operating distance

Approximately 90% of the original value

No influence

0 to 5mm

5mm Min.

9.5

EU Declaration of Conformity

Standards

OMRON declares that D40A is in conformity with the 
requirements of the following EU Directives:
 

Machinery Directive 2006/42/EC

 

EMC Directive 2014/30/EU

D40A is designed and manufactured in accordance with 
the following standards:
 EN 

ISO13849-1:2015 

Cat. 3 PL d

 (with G9SX-NS

…

)

,

 

IEC/EN61508 SIL3 

 (with G9SX-NS

…

)

,

 IEC/EN60947-5-3 

PDDB 

(with G9SX-NS

…

)

,

 

IEC/EN61000-6-4,  ISO14119 (Low level coded),

 

UL508,   CAN/CSA C22.2 No.14

Original instructions

z

  LED Display

LED color Status

Sensor does NOT detect actuator

Sensor detect actuator

RED

YELLOW

Suitability for Use 

Omron Companies shall not be responsible for conformity with any standards,
codes or regulations which apply to the combination of the Product in the
Buyer’s application or use of the Product. At Buyer’s request, Omron will
provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not
sufficient for a complete determination of the suitability of the Product in
combination with the end product, machine, system, or other application or
use. Buyer shall be solely responsible for determining appropriateness of the
particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases.

NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT 
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO 
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS 
PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN 
THE OVERALL EQUIPMENT OR SYSTEM.

OMRON Corporation 

 (Manufacturer)

 Contact:  www.ia.omron.com

Regional Headquarters

Shiokoji Horikawa, Shimogyo-ku, Kyoto, 600-8530 JAPAN

OMRON EUROPE B.V. (Importer in EU)

Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388

OMRON ELECTRONICS LLC

2895 Greenspoint Parkway, Suite 200 
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD.

No. 438A Alexandra Road # 05-05/08 (Lobby 2), 
Alexandra Technopark, 
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711

OMRON (CHINA) CO., LTD.

Room 2211, Bank of China Tower, 
200 Yin Cheng Zhong Road, 
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200

ON

OFF

Unstable 

range

15mm (point B)

 5mm (point A)

Y-direction movement

X

Y

16

14

12

10

8

6

4

2

0

6

4

2

0

2

4

6

Distance from the target mark on the switch X (mm)

Oper

ating distance 

Y (mm)

Sensing 
surface

Target marks

Engineering Data
(OFF to ON)

Maximum 
operating distance
(ON to OFF)

18

B

A

15

10

5

0

5

10

15

Distance from the target mark on the switch Z (mm)

Oper

ating distance 

Y (mm)

18

16

14

12

10

8

6

4

2

0

Z

Y

Sensing 
surface

Target marks

Engineering Data
(OFF to ON)

Maximum 
operating distance
(ON to OFF)

B

A

Internal Circuit

brown / 1

white / 2

black / 4

yellow / 5

blue / 3

Internal connection

3

5

3

2

4

1

Engineering Data
(ON to OFF)

Minimum 
operating distance
(OFF to ON)

OFF range

ON range

ON range

OFF range

Engineering Data
(ON to OFF)

Minimum 
operating distance
(OFF to ON)