S8V-CP

3

Tripping Functions

Current tripping

If the output current of each output exceeds the current tripping, the output is tripped by a semiconductor switch (MOS FET) in accordance with 
the current tripping characteristic.

Over voltage tripping

With the S8V-CP0424S, if the input voltage exceeds 28.8 V, all outputs are tripped by a semiconductor switch (MOS FET).
If the input voltage becomes 28.8 V or less, all outputs automatically return to the previous state.

Reset Signal Input (RST)

Turning ON all outputs during in the Current tripping (enable to reset) state is called reset. All output terminals can be reset by an external input. 
As shown in the following figure, input a high level signal of 0.5 s or more and reset.

Input voltage: 30 VDC max.
Input impedance: 22 k

Ω

Note: 1.

When Reset signal input terminal is used, a miss operation of reset may occur by a noise coming from the cable. Do not make an instable 

potential of Reset signal input terminal.

Alarm Signal Output (ALM1/ALM2)

If any of the output is tripped, the MOS FET relay is turned OFF. The signal output comprises of MOS FET relays and therefore, does not have 
polarity.

Input voltage: 30 VDC max., Input current: 50 mA max.
Residual voltage when ON: 2 V max.
Leakage current when OFF: 0.1 mA max.

Note: 1.

Alarm signal output is not equipped with an internal current limiting circuit, so be sure that the current flowing to the alarm signal output 

terminals does not exceed 50 mA.

2.

Be sure to check that the Alarm signal outputs are working normally after wiring.

Output Status

The status of each output can be identified by the indicator or alarm signal output.
The status of each output is saved when the power is turned OFF. When the power is turned ON again, the status transits to that saved after 
initialization.
All outputs are set to Output ON state by default.

*1.

Each output transits automatically to Current tripping (disable to reset) state according to the Current tripping characteristics.

*2.

The status remains on Current tripping (disable to reset) state during 500 ms to 20 s in order to protect the internal parts from heat. 

After that, the status automatically transits to Current tripping (enable to reset) state.

*3.

S8V-CP0424S only

*4.

If an internal fuse blows, or an internal memory error occurs, the output will be disconnected.

*5.

Always remove the cause of the output first and then reset the alarm when abnormal tripping operates.

Indicator

Alarm Signal 

Output

Output

Status Name

Status Transition 

by Push Button

Status Transition 

by Reset Signal Input

Color

Status

---

OFF

OFF

OFF

Initialization

---

---

Green

ON

ON

ON

Output ON

Manually output OFF

---

Yellow

ON

ON

ON

Over current 

*

1

Manually output OFF

---

Red

ON

OFF

OFF

Manually output OFF

Output ON

---

Red

Blinking

OFF

OFF

Current tripping (Disable to reset) 

*

2

---

---

Yellow

Blinking

OFF

OFF

Current tripping (Enable to reset)

Manually output OFF

Output ON 

(transition due to positive 

pulse longer than 0.5 s) 

*

5

Red

Blinking fast

OFF

OFF

Over voltage tripping 

*

3

Internal error detection 

*

4

---

---

Reset (Connect)

0.5 s min.
High level

External input

Low level: 0 to 5 VDC

High level: 20 to 30 VDC

S8V-CP

RST

22k

Ω

-VI2

-VI1

Summary of Contents for S8V-CP Series

Page 1: ...on load Lineup of a UL Class 2 output compatible model Model Number Structure Model Number Legend Not all combinations are possible Refer to List of Models in Ordering Information below 1 Number of Ou...

Page 2: ...typ at 10 A x 7 CH When all outputs are tripped 0 7 W typ 0 8 W typ 1 1 W typ Start up time 4 Initialization time 250 ms typ Start up delay time 50 ms to 5 s Functions 5 Current tripping function 6 R...

Page 3: ...eck that the Alarm signal outputs are working normally after wiring Output Status The status of each output can be identified by the indicator or alarm signal output The status of each output is saved...

Page 4: ...O4 VO3 VO2 VO1 VI2 VI1 VI2 VI1 S8V CP0424 CONTROL CIRCUIT INPUT SIGNAL INPUT OUTPUT SIGNAL OUTPUT MOS FET RELAY MOS FET ALM2 ALM1 RST VO4 VO3 VO2 VO1 VI2 VI1 VI2 VI1 S8V CP0424S FUSE 15A OUTPUT INPUT...

Page 5: ...VI1 or VI2 2 Follow the figures below for wiring Reset signal input terminal POWER SUPPLY LOAD RESETSIGNAL POWER LINE LOAD LINE SIGNAL LINE INDICATOR COMMON TERMINALBLOCK S8V CP RST VDC VDC ALM1 ALM2...

Page 6: ...inals Connects to the positive side of the power unit output 4 VI2 5 SIGNAL INPUT VI1 Negative input terminal Connects to the negative side of the power unit output This terminal is only used as a gro...

Page 7: ...tripping current is decreased to less than 3 2 A in accordance with the current and voltage tripping characteristic 2 Current tripping takes place between 250 ms to 5 s S8V CP0424 S8V CP0424S S8V CP0...

Page 8: ...1 1 10 4 max when sliding 3 5 Rail stopper S8V CP0424 1 1 94 8 1 90 8 9 44 8 1 11 9 5 1 10 4 max when sliding 90 1 34 3 18 7 24 5 5 5 7 5 2 3 5 Rail stopper S8V CP0424S 1 6 4 6 7 max when sliding 122...

Page 9: ...lt from aluminum abrasion Mounting Rail Material Aluminum PFP 100N PFP 50N 4 5 15 25 25 10 10 1 000 500 25 25 15 5 35 0 3 7 3 0 15 27 0 15 1 indicates the dimensions of the PFP 50N Mounting Rail Mater...

Page 10: ...nally occur Do not apply voltages that exceed the input voltage allowable range Unexpected output may occasionally occur Be careful sufficiently not to accidentally press the push button with indicato...

Page 11: ...at blade screwdriver into the release hole Do not wire anything to the release holes Do not tilt or twist a flat blade screwdriver while it is inserted into a release hole on the terminal block The te...

Page 12: ...Internal parts may possibly deteriorate or be damaged Tripping performance depends on the ambient operating temperature Use the Product within the derating curve see Derating Curves on page 7 Interna...

Page 13: ...way as when connecting stranded wires Connecting Stranded Wires Use the following procedure to connect the wires to the terminal block 1 Hold a flat blade screwdriver at an angle and insert it into t...

Page 14: ...uminum electrolytic capacitors is large and the service life is reduced by half for each 10 C rise in temperature Arrhenius law When the capacity reduction life of the electrolytic capacitor is reache...

Page 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 16: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...

Reviews: