New S82K
New S82K
7
Item
PFC
No
Yes
(-P models)
Single output
Dual
outputs
Single output
3 W
7.5 W
7.5 W
15 W
30 W
50 W
90 W
100 W
240 W
240 W
Output
(see
note 2)
Voltage
adjustment range
±
10% (V.ADJ)
Not
possible
(see
note 3)
±
10% (V.ADJ); –10% to 15% for S82K-03012/-03024/-05024
Ripple (see note 1)
2% (p-p) max.
Input variation
influence
0.5 % max. (at 85 to 264 VAC input, 100% load)
0.5 % max. (at 85
to 132 VAC/170 to
264 VAC input,
100% load)
0.5 %
max. (at
85 to
132 VAC
/170 to
253 VAC
input,
100%
load)
0.5 % max.
(at 85 to
253 VAC
input, 100 %
load)
Load variation
influence
1.5% max.
(0 to 100% load)
+V:
1.5%
max.
-V: 3 %
max.
(0 to
100%
load)
1.5% max.
(0 to 100% load)
1.5% max.
(10 to 100% load)
Temperature
variation influence
(see note 1)
0.05%/
°
C max.
Rise time
100 ms max. (up to 90% of output voltage at rated input and
output)
200 ms max.
300 ms
max.
1,000 ms
max.
Hold time
(see note 1)
20 ms min.
Addi-
tional
func-
tion
Overload
protection
105% to 160% of
rated load
current,
automatic reset
(see note 4)
105% to
250% of
rated
load cur-
rent, au-
tomatic
reset
105% to 160% of rated load
current, automatic reset
101% to
160% of
rated
load cur-
rent, au-
tomatic
reset
(see
note 5)
105% to 160% of rated load
current, automatic reset
Overvoltage
protection (see
note 6)
No
S82K-
24024T
model
only
No
Undervoltage
alarm indicator
(DC LOW
indicator)
Yes (color: red)
S82K-
24024T
model
only
No
Undervoltage
alarm output (DC
LOW output)
No
Yes
S82K-
24024T
model
only
No
Parallel operation
Impossible
Possible (2 units max.)
Note:
1. Defined with a 100% load and the rated input voltage (100 or 200 VAC).
2. The output specification is defined at the power supply output terminals.
3. The settings for the output voltage must be within the following range:
+V:
±
1% of the rated value
–V:
±
5% of the rated value
4. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will
operate at a current of 95% to 160% of the rated load current.
5. When the ambient temperature exceeds 25
°
C, the protection function will operate at a current of 92% to 111% of the rated load
current.
6. Circuit-breaker type. To reset, turn the input power supply OFF, then after 1 min has elapsed, turn the input power supply ON again.