New S82K

New S82K

19

Wiring

Carefully wire the input/output terminals while paying attention to
their polarities so as to prevent incorrect wiring.

Battery Charging

When connecting a battery to the load, install an overcurrent limit
circuit and overvoltage protection circuit.

Series Operation

S82K 90-W/100-W/240-W model can be operated in series.
It must be noted that the + output of the 7.5-W dual output model
cannot be connected in series to its – output.

90-, 100-, and 240-W Models

3-, 7.5-, 15-, 30-, 50-W Models

INPUT

+V

–V

INPUT

+V

–V

INPUT

+V

–V

INPUT

+V

–V

Parallel Operation

S82K 90-W/100-W/240-W models can be operated in parallel.
Perform parallel operation with power supplies satisfying the same
specifications.

INPUT

+V

–V

INPUT

+V

–V

90-, 100-, and 240-W Models

Load

Note:

When operating the 240-W model in parallel operation, set
the switch to “PARALLEL.” Refer to the derating curve for
the rated current under this operation.

INPUT

+V

–V

INPUT

+V

–V

Load

3-, 7.5-, 15-, 30-, and 50-W Models

Parallel Operation Precautions

The length and thickness of each wire connected to the load
must be the same so that there is no difference in voltage drop
value between the load and the output terminals of each Power
Supply.

Adjust the output voltage of each Power Supply so that there will
be no difference in output voltage between each Power Supply.

If the 240-W Power Supply is used in single operation under the
parallel operation setting, the overcurrent protection will be
actuated at an output of 90% to 95% (in current), and will not
allow a 100% output.

If the 240-W Power Supplies are used in parallel operation under
the single operation setting, one of them will operate at 110%
output, causing severe heat derating and shortening the service
life.

Minimum Output Current

The minimum output current of the S82K-00727 and S82K-00728 is
restricted by the output voltage and control method.

Note:

All the outputs of the S82K-00727 and S82K-00728 are
controlled by the +V output. If the +V output current falls to
10% or less of the rated output, the –V output voltage may
drop.

Operating and Storage Environments

Do not use or store the Unit in the following places, otherwise the
Unit may malfunction or the characteristics of the Unit may deterio-
rate.

Locations subject to direct sunlight.

Locations subject to ambient operating temperatures outside the
range indicated by the derating curve.

Locations subject to ambient operating humidity outside the
range of 25% to 85%.

Locations subject to condensation as the result of severe
changes in temperature.

Locations subject to ambient storage temperatures outside the
range of –25

°

C to 65

°

C.

Locations subject to corrosive or flammable gases.

Locations subject to dust (especially iron dust) or salts.

Locations subject to shock or vibration.

Locations subject to exposure to water, oil, or chemicals.

Summary of Contents for S82K-00305

Page 1: ...ock with cover according to VDE0106 P100 Conforms to the stringent EN50081 1 standard for universal use in any environment subject to EMI conditions except for 240 W models in addition to EN50082 2 conformity for use at any EMS environment DC output ports comply to EN55022 class A thus ensuring use in any environment subject to EMI with recommended external filters 3 to 100 W models Meets EN61000 ...

Page 2: ...75 A S82K 09024 100 W 24 V 4 2 A S82K 10024 Note The output capacity of the S82K 03005 is 25 W 240 W Models Power ratings Output voltage Output current Functional configuration Models 240 W 24 V 10 A Standard S82K 24024 240 W 24 V 10 A With undervoltage alarm indicator output S82K 24024T 240 W 24 V 10 A With PFC S82K P24024 Model Number Legend 3 to 100 W Models 1 Power Ratings 003 3 W 007 7 5 W 01...

Page 3: ...60 Hz 47 to 63 Hz Current see t 3 100 V input 0 15 A max 0 25 A max 0 45 A max 0 9 A max 1 3 A max 2 5 A max 5 5 A max 4 A max note 3 200 V input 0 25 A max 0 6 A max 0 8 A max 1 5 A max 3 5 A max 2 A max Power factor 0 95 min Leakage current 100 V input 0 5 mA max see note 3 200 V input 1 mA max Inrush current 100 V input 15 A max 25 A max see note 3 200 V input 30 A max 50 A max Noise filter Yes...

Page 4: ...tomatic reset 105 to 160 of rated load current automatic reset 101 to 160 of rated load cur rent au tomatic reset see note 5 105 to 160 of rated load current automatic reset Overvoltage protection see note 6 No S82K 24024T model only No Undervoltage alarm indicator DC LOW indicator Yes color red S82K 24024T model only No Undervoltage alarm output DC LOW output No Yes S82K 24024T model only No Para...

Page 5: ...ote 3 240 W Models EMI EN50081 2 Emission Enclosure EN55011 class A see note 4 Emission AC Mains EN55011 class A see note 4 Harmonic Current EN61000 3 2 only for S82K P24024 Common to All Models EMS EN50082 2 Immunity ESD EN61000 4 2 4 kV contact discharge level 2 8 kV air discharge level 3 Immunity Burst EN61000 4 4 2 kV power line level 3 2 kV output line level 4 Immunity Surge EN61000 4 5 betwe...

Page 6: ...mbient temperature C A Standard Vertical Installation B Horizontal Installation Note The derating curve above can be ensured for the above two kinds of installations Top 3 7 5 15 30 50 90 100 W Models 240 W Model Parallel Unit Operation Note 100 V input 85 to 132 VAC Load Ambient temperature C S82K P24024 100 VAC input see note Load Ambient temperature C Single Unit Operation Top Not permitted for...

Page 7: ...long time otherwise the internal circuitry of the S82K may be deteriorated or damaged 50 0 100 Output voltage V Output current Rated voltage 3 7 5 15 90 100 240 W Models 30 50 W Models Rated voltage When Using Output Models The V output detects the total output power V output and V out put to trigger the short circuit protection against overcurrent This protection varies depending on the V output ...

Page 8: ...oltage the green indicator will be lit Green DC ON Red DC LOW see note 1 If the voltage at the output terminal is 75 to 90 the red indicator will be lit Green DC ON Red DC LOW If the voltage at the output terminal is 0 V both the green and red indicators will not be lit Note 1 The more the voltage at the output terminal drops the darker both the green and red indicators will be 2 The relay contact...

Page 9: ... to short circuit terminals 7 and 8 to select 100 to 120 VAC and remove the short bar to select 200 to 240 VAC S82K 24024j 240 W V V Fuse 5 A Noise filter Inrush current protection circuit Drive control circuit DC OUTPUT Overvoltage protection circuitry see note 1 Photocoupler INPUT AC L AC N Overload alarm circuit Rectifying and smoothing circuit Overvoltage alarm circuit Detector GR Rectifier DC...

Page 10: ...New S82K New S82K 13 S82K P24024 240 W V V Fuse 8 A Noise filter Inrush current protection circuit Drive control circuit DC OUTPUT INPUT AC L AC N ...

Page 11: ... min L 20 mm min between each adjacent Power Supply Mounting Brackets Supplied with the Switching Power Supply Used when not mounting the Power Supply directly on the DIN track Two 4 5 0 1 dia 35 0 15 25 0 15 37 5 0 1 27 0 1 S82K 015jj 15 W Mounting Holes Note If more than one Power Supply is installed in a row keep a distance of 20 mm min L 20 mm min between each adjacent Power Supply Two M4 or 4...

Page 12: ... distance of 20 mm min L 20 mm min between each adjacent Power Supply S82K 09024 90 W S82K 10024 100 W 60 135 L Four M4 or 4 5 dia mounting holes 58 1 75 4 sliding 7 max M3 5 with square washer Short bar M3 5 terminal screw 60 0 2 145 135 0 2 Four 4 5 dia 91 35 2 7 5 5 Mounting Holes Note If more than one Power Supply is installed in a row keep a distance of 20 mm min L 20 mm min between each adja...

Page 13: ...n L 20 mm min between each adjacent Power Supply Four M4 or 4 5 dia mounting holes 130 112 8 Four 4 5 dia 100 115 0 2 4 sliding 8 max 9 8 8 3 35 7 8 27 5 270 115 0 2 4 2 130 280 270 0 2 L Accessories Mounting Track Order Separately PFP 100N PFP 50N 4 5 15 25 25 25 25 10 10 1 000 500 see note 7 3 0 15 35 0 3 27 0 15 1 4 5 15 25 25 25 25 15 10 10 1 000 35 0 3 27 24 16 29 2 1 1 5 PFP 100N2 ...

Page 14: ...al 4 Input Voltage Selector Terminals Selects a 100 V or 200 V input voltage 5 Output Indicator DC ON Lights while a Direct Current DC output is ON 6 Output Voltage Adjuster V ADJ It is possible to increase or decrease the output voltage 7 Undervoltage Alarm Indicator DC LOW Other than S82K 24024 and S82K P24024 models 8 Undervoltage Alarm Output DC LOW S82K 09024 10024 24024T models only 9 Parall...

Page 15: ...t least 10 mm spacing between them as shown in the following il lustration Forced air cooling is recommended 10 mm min Short bar To mount the Power Supply on a DIN track hook portion A of the Power Supply to the track and press the Power Supply toward direc tion B A B To dismount the Power Supply pull down portion C with a flat blade screwdriver and pull out the Power Supply C 30 mm min Track stop...

Page 16: ... each Power Supply If the 240 W Power Supply is used in single operation under the parallel operation setting the overcurrent protection will be actuated at an output of 90 to 95 in current and will not allow a 100 output If the 240 W Power Supplies are used in parallel operation under the single operation setting one of them will operate at 110 output causing severe heat derating and shortening t...

Page 17: ...romi Chuo ku Osaka 540 6028 Japan Phone 81 6 6949 6035 Fax 81 6 6949 6069 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No M048 E1 4 In the interest of product improvement specifications are subject to change without notice Printed in Japan 0799 2M a ...

Reviews: