3-11
Servo Driver Overheating
An alarm will go off if the internal temperature (i.e., heat sink temperature) of the Servo Driver exceeds
90
°
C.
Alarm Indication
U Series: A. 10
H Series: E21
M Series: A. L-8, A. L-9
R Series: OH
Probable cause
Item to check
Countermeasure
The ambient temperature is high.
·
The ambient temperature for the
Servo Driver is higher than 55
°
C.
·
Decrease the ambient tempera-
ture with a cooling fan or cooling
unit.
·
Locate the Servo Driver in a
place where the ambient temper-
ature is low enough.
The regeneration is excessive.
(Applicable to M and R Series
only.)
·
The regeneration is beyond the
processing capability of a single
Servo Driver.
* Check the regeneration from
the voltage waveform obtained
from the terminals of the
regeneration resistor. Refer to
Main Circuit Overvoltage
on
page 3-4.
·
Connect the External Regenera-
tion Resistor.
Insufficient rotation of cooling fan
or clogged filter.
(Application to M Series only.)
·
The fan is not rotating.
* Check the fan visually.
·
Replace the Servo Driver.
·
Replace the fan.
(Application to M Series only.)
·
The filter is clogged with dirt.
·
Clean the filter.
The load is too heavy.
·
The Servo Driver is in continu-
ous operation with its output cur-
rent exceeding the rated current.
(Use the current monitor or indi-
cator.)
·
Reduce the load.
·
Increase the acceleration/decel-
eration time.
·
Increase the motor capacity.
Servo Driver Errors
Chapter 3