Item
Inspection
Criteria
Tool
Environment
Check the ambient temperature and the tem-
perature inside the panel
-10 to 55
°
C
Thermometer
Check the ambient humidity and the humidity
inside the panel
25% to 85% (with no
condensation)
Hygrometer
Check for accumulation of dust
No accumulation of
dust
Inspect visually
Installation condi-
tion
Check that the IO-Link I/O Hub is securely
fixed
No looseness
Phillips screw-
driver
Check that the waterproof covers of the cables
are tightened to an appropriate torque on the
connectors of the IO-Link I/O Hub
The covers are tight-
ened to the specified
torque
Torque handle
Check for damaged connecting cables
No visible damage
Inspect visually