Function Details
The following item configure the output operation for occurrence of communications errors.
Setting
Description
Default val-
ue
Setting range Unit Update timing
Port
£
Error Mode
Output Setting
Sets each port to hold the pre-er-
ror output or clear it when an error
occurs.
00 hex
00 hex:
Clear
01 hex:
Hold
---
Immediately
*1.
£
refers to port numbers 1 to 8.
You can configure the function by one of the following two procedures.
• Configure the function from CX-ConfiguratorFDT
• Configure the function through message communications from the Controller to the IO-Link device
Refer to the
NXR-series IO-Link Master Unit for EtherNet/IP User’s Manual (Cat. No. W619)
for details
on how to configure the function through message communications.
Setting Method
The following describes how to configure the function from CX-ConfiguratorFDT. Refer to
Setting IO-
Link Devices with the CX-ConfiguratorFDT
in the
NXR-series IO-Link Master Unit for EtherNet/IP
User’s Manual (Cat. No. W619)
for how to create a network configuration and how to go online.
1
Create a network configuration and then register the Digital I/O Variable Hub.
2
Double-click or right-click the device DTM for the Digital I/O Variable Hub to configure, and
then select
Configuration
.
The Configuration tab page is displayed. In the Configuration tab page,
Menu
is displayed with
Parameter
selected. Refer to
on page A-6 for details on the
Configuration tab page.
3
Expand
Error Mode Output Setting
. From the drop-down list of
Port
£
Error Mode Output
Setting
, select
Clear
or
Hold
.
4
Right-click the device DTM for the Digital I/O Variable Hub where to store parameters and se-
lect
Go online
.
The relevant device goes online. Devices in the Network View are displayed in bold while you
are online.
5
Right-click the device DTM again and select
Store to device
.
The parameter settings are stored in the Digital I/O Variable Hub.
7-1-9
Monitoring Total Power-ON Time
This section describes the monitoring total power-ON time.
7 Functions of IO-Link I/O Hubs
7-15
NXR-series IO-Link I/O Hub User’s Manual (W620)
7-1
Functions of Digital I/O Hubs
7
7-1-9
Monitoring T
otal Power-ON T
ime
Summary of Contents for NXR Series
Page 6: ...Manual Structure 4 NXR series IO Link I O Hub User s Manual W620 ...
Page 26: ...Revision History 24 NXR series IO Link I O Hub User s Manual W620 ...
Page 34: ...1 Features and System Configuration 1 8 NXR series IO Link I O Hub User s Manual W620 ...
Page 90: ...6 Process Data and Service Data 6 12 NXR series IO Link I O Hub User s Manual W620 ...
Page 108: ...7 Functions of IO Link I O Hubs 7 18 NXR series IO Link I O Hub User s Manual W620 ...
Page 131: ...I Index I 1 NXR series IO Link I O Hub User s Manual W620 I ...
Page 133: ......