55
Additional Information
Difference between the TON instruction for the NX1P and the TIM instruction for the
traditional PLC
The TON instruction changes timer output
Q
to TRUE when the set time
PT
elapses after
timer input
In
changes to TRUE.
The timer is reset when
In
changes to FALSE. Elapsed time
ET
changes to 0 and
Q
changes to FALSE.
(2) Input the set time
Specify a TIME data variable for the input parameter
PT
when inputting the set time.
For example, input “T#10.12s” to set to 10.12 seconds.
Classification
Data
type
Data
size
Alignment
Range of values
Notation
Durations
TIME
64
bits
8 bytes
T#-9223372036854.775808ms
(T#-106751d_23h_47m_16s_
854.775808ms) to
T#+9223372036854.775807ms
(T#+106751d_23h_47m_16s_
854.775807ms)
T#12d3h3s
T#3s56ms
TIME#6d_10m
TIME#16d_5h_3m_4s
T#12d3.5h
T#10.12s
T#61m5s (Equivalent to T#1h1m5s)
TIME#25h_3m