Summary of Contents for NSA12-15-TX11B

Page 1: ...Cat No V238 E1 02 NSA Series Industrial PC NSA Series USER S MANUAL Cat No Z264 E1 06A Smart Sensor ZFX C USER S MANUAL...

Page 2: ......

Page 3: ...NSA Series Industrial PC NSA12 15 TX11B NSA12 15 TX11S NSA12 15 TX12B NSA12 15 TX12S User s Manual...

Page 4: ...iv...

Page 5: ...up an NSA series Industrial PC Be sure to read this manual before attempting to use it and keep the manual close at hand for reference during operation OMRON 2008 All rights reserved No part of this...

Page 6: ...vi...

Page 7: ...S DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE OMRON DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE...

Page 8: ...that the uses listed may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this manual Nuclear...

Page 9: ...nfirm actual specifications of purchased products DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes even when tolerances are shown PERFORMANCE...

Page 10: ...age Precautions for Safe Use Indicates actions that should be done or avoided for the safe use of this product Precautions for Correct Use Indicates actions that should be done or avoided to prevent o...

Page 11: ...rohibitions Disassembly Prohibition Indicates prohibitions when there is a possibility of injury such as from electric shock as the result of disassembly Mandatory Action Indicates a mandatory action...

Page 12: ...verage or other liquid is spilled onto the product turn OFF the power immediately and remove all connectors from the power supply input terminal block Do not touch the power supply input terminals wit...

Page 13: ...lowing locations may cause electric shock fire or malfunction Locations that are unstable or subject to vibration Locations subject to static electricity Locations subject to dust or high humidity Loc...

Page 14: ...OFF the power supply either turn OFF the external input power supply or disconnect the power supply input connector The NSA series Industrial PC must be installed within a control panel Use a control...

Page 15: ...to a torque of 0 5 to 0 6 N m 5 to 7 lb in Be sure the screws are properly tightened 9 Turn OFF the power supply before connecting or disconnecting cables 10 Always tighten the connector screws after...

Page 16: ...se of the NSA series Industrial PC together with other waste to be sent to a disposal site Dispose of the NSA series Industrial PC according to local ordinances as they apply 25 Use a PCI Board that c...

Page 17: ...e to radioactivity Warnings and Precautions z LCD Panel Precautions There may be inconsistencies in the brightness of the LCD panel depending on what is displayed and the contrast setting This is not...

Page 18: ...suffix to the catalog number on the front cover of the manual Revision Code V238 E1 02 Cat No Revision code Date Revision content 01 March 2008 Original production 02 May 2008 Page 4 12 Adding informa...

Page 19: ...of these parts are missing or damaged contact the sales representative from whom you purchased the product Main Body Mounting Brackets 8 Instruction Sheet Note The OS is not installed in the NSA serie...

Page 20: ...xx...

Page 21: ...1 Overview and Specifications Section 2 Nomenclature Section 3 Installing the NSA series Industrial PC and Connecting Peripheral Devices Section 4 RAS Functions Section 5 Maintenance Appendix 1 2 3 4...

Page 22: ...tions 1 4 1 2 1 Ratings and Specifications 1 4 1 2 2 General Specifications 1 5 1 2 3 Dimensions and External Appearance 1 8 Section 2 Nomenclature 2 1 Nomenclature 2 2 2 1 1 Front Panel 2 2 2 1 2 Rea...

Page 23: ...oring and Auto recovery 4 2 4 1 3 Logging Function and Log Analysis Function 4 4 4 1 4 Architecture 4 4 4 2 Special RAS Board Functions 4 5 4 2 1 Special RAS Board Functions 4 5 4 2 2 Setting Procedur...

Page 24: ...rite Filter Appendix 21 Appendix 2 1 About the EWF Function Appendix 21 Appendix 2 2 Confirming the Operating State of the EWF Function Appendix 21 Appendix 2 3 Enabling the EWF Function Appendix 22 A...

Page 25: ...Section 1 Overview and Specifications...

Page 26: ...f Construction The front panel is rated the equivalent of IP65 for waterproofing Network Functions Connecting to two networks is quick and easy because each NSA series Industrial PC comes with two 10B...

Page 27: ...the front panel These USB ports can be used even when the NSA series Industrial PC is installed in a control panel Windows XP Embedded Windows XP Embedded is an OS for embedded use Purchase the Memor...

Page 28: ...nnectors See note 7 Interface Memory Card Type I CF Card 1 slot bootable drive See note 10 Expansion slots PCI expansion bus 1 slot External input port 3 pin connector port for the UPS power interrupt...

Page 29: ...4 4 power supply line 2 kV Vibration resistance in operation Conforms to JIS C0041 0 05 mm amplitude at 10 to 55 Hz for 50 min each in the X Y and Z directions Shock resistance in operation Conforms...

Page 30: ...will operate properly at the selected ambient operating temperature Example If an Expansion PCI Board with an ambient operating temperature of 0 to 45 C will be used with the Unit installed at angle g...

Page 31: ...l Specifications 1 7 1 Overview and Specifications Note 2 Use the temperature and humidity ranges in the following diagram Note 3 The Unit may not operate properly in locations subjected to oil splash...

Page 32: ...1 2 Specifications 1 2 3 Dimensions and External Appearance 1 8 1 Overview and Specifications 1 2 3 Dimensions and External Appearance NSA12 TX11B S NSA12 TX12B S NSA15 TX11B S NSA15 TX12B S...

Page 33: ...Section 2 Nomenclature...

Page 34: ...r A USB type A connector USB Port Cover A cover for the USB ports on the front panel Display Area The entire display area is a touch panel input device View with the USB Port Cover Open 2 1 2 Rear Pan...

Page 35: ...g BAT LOW Indicator The red indicator is lit when the RAS Board backup battery is exhausted UPS Power Interrupt Signal Connector This connector is used for the power interrupt signal from the UPS DIAG...

Page 36: ...lamp is lit when sending or receiving via Ethernet 8 NC Not used UPS Power Interrupt Signal Connector NSA series Industrial PC connector S3B PH K S J S T Mfg Co Ltd Pin No Signal 1 ACFAIL 2 NC 3 COM...

Page 37: ...Section 3 Installing the NSA series Industrial PC and Connecting Peripheral Devices...

Page 38: ...perating panel To enable the RAS Board s special Action on Error monitoring function forced shutdown or forced reboot To set the ACFAIL signal input method for the external input port UPS power interr...

Page 39: ...evices Step 7 Adjust the touch panel and display Adjust calibrate the touch panel positioning as needed Touch panel positioning adjustment calibration The pre installed universal pointer device driver...

Page 40: ...f Memory Card Notch Enlarged Memory Card Diagram Insert the Memory Card with the backside facing down The backside is the side with the notches and protrusion Notch Protrusion Side View 1 Loosen the s...

Page 41: ...our index finger in front of the memory card to keep it from popping out and falling on the floor Note The NSA series Industrial PC does not include a Memory Card Order the Memory Cards specified by O...

Page 42: ...d Follow the steps below to install a PCI Board Step 1 Remove the back cover Step 2 Install the PCI Board Step 3 Reattach the back cover Removing the Back Cover Note Be sure to turn OFF the NSA series...

Page 43: ...3 3 Installing a PCI Board and Setting the DIP Switch 3 3 1 Installing a PCI Board 3 7 3 Installing the NSA series Industrial PC and Connecting Peripheral Devices 2 Remove the back cover...

Page 44: ...the NSA series Industrial PC and Connecting Peripheral Devices Installing a PCI Board 1 Remove the single screw shown in the figure below to detach the metal plate cover for the PCI slot Screw Metal...

Page 45: ...3 1 Installing a PCI Board 3 9 3 Installing the NSA series Industrial PC and Connecting Peripheral Devices 3 Secure the PCI Board with the screw that was removed from the metal plate cover in step 2...

Page 46: ...fore you remove the back cover and install or remove a PCI Board Refer to PCI Board Dimensions on page 3 9 for mountable board sizes Check the PCI Board that will be used to make sure it operates prop...

Page 47: ...rupt signal connector ON Used for UPS connection OFF Use as general input port default setting 6 Specifies the ACFAIL signal input method for the external input port UPS power interrupt signal connect...

Page 48: ...umidity Locations subject to exposure to chemicals and other harsh substances Locations subject to intense exposure to oil Locations subject to corrosive or flammable gases Locations subject to shock...

Page 49: ...dustrial PC is normally mounted in a panel Follow the steps below to mount the Unit 1 Cut the mounting hole out from the panel Panel thickness 1 6 to 4 0 mm 2 Insert the NSA series Industrial PC into...

Page 50: ...dust resistance Make sure the panel is not dirty or warped and that it is strong enough to hold the product Do not let metal particles enter the product when preparing the panel 3 4 3 Connecting the...

Page 51: ...supply Connecting Parts Note Connect to the power supply terminal block using a twisted pair cable with stranded copper wire between AWG16 and AWG12 with a rated temperature of 75 C Tighten the termin...

Page 52: ...C and Connecting Peripheral Devices Note Do not install the NSA series Industrial PC in the same panel as a noise generating device like a motor or inverter Make sure the NSA series Industrial PC is p...

Page 53: ...Operating System The NSA series Industrial PC shuts down the operating system when it receives a shutdown request from a software application or when the user executes a shutdown operation When the sh...

Page 54: ...external input voltage is interrupted it must remain OFF for at least 10 s before it is turned back ON OFF ON interval 10 s min If the external input voltage is interrupted during any operation includ...

Page 55: ...henever it deviates markedly from its coordinate Connect a USB keyboard and mouse to the NSA series Industrial PC before calibrating the touch panel Make sure the keyboard and mouse are properly conne...

Page 56: ...played prompting you to save the calibration data If there were no problems with the calibration points press the OK Button or the Enter Key on the keyboard If there was a problem with a calibration p...

Page 57: ...djustments for the LCD backlight brightness a RAS Utility By using the color correction function you can further adjust the brightness of the entire display This section will explain how to adjust the...

Page 58: ...tory press the OK Button to close the dialog box Note Do not change any settings other than those specified in these instructions Doing so may create problems with your display Note Press the Restore...

Page 59: ...Section 4 RAS Functions...

Page 60: ...ndustrial PC provides main the following functions A Monitoring Function is provided to constantly monitor the hardware and software of the industrial PC and provide the user failure notification when...

Page 61: ...verheating due to runaway operation Repeating reboot attempts automatically until the system is successfully activated if the system hangs up at startup and Forcefully terminating the system automatic...

Page 62: ...peration when it detects a failure Additionally it saves power supply ON OFF status OS startup shutdown status and logs of various failures in the memory backed up by a battery This enables the user t...

Page 63: ...S has been given to see if shutdown is completed within the set time Action on error forced shutdown or forced reboot Recover processing will be automatically performed when there is notification of a...

Page 64: ...FAIL signal input method for the external input port UPS power interrupt signal connector See note ON Normally supplies 24 V Open at PWR FAIL OFF Normally open supplies 24 V at PWR FAIL Recommended de...

Page 65: ...o voltage 4 POST error logs BIOS startup log data approximately 40 bytes for the 10 most recent errors read from specified CMOS addresses in the chipset Note The NSA series Industrial PC does not have...

Page 66: ...hen Auto Resume is disabled z Auto Mode The message Press F1 to Resume F2 to Setup will be displayed on the screen for the amount of time specified at the timer Any errors will be ignored and startup...

Page 67: ...current BIOS settings The message In progress please wait will be displayed while the settings are being saved Restore CMOS Press Enter Press the Enter Key to restore the last saved BIOS settings The...

Page 68: ...with a pop up message Status Monitor This function lists the industrial PC s hardware and software status which is read periodically Log Analysis The causes of failures and failure trends can be anal...

Page 69: ...s of the Failure Notification Function Failure Notification is enabled Failure Notification is disabled 3 When Failure Notification is enabled the following pop up window will be displayed if a failur...

Page 70: ...failure detected status must be cleared so that the Failure detected Notification Window is not displayed at startup Click View more detail To clear the failure detected status select Action Clear Fa...

Page 71: ...ing the Status Monitor Detailed information can be displayed on the Industrial PC RAS Board This tab page shows information on the occurrence of failures and the RAS Board s operating status Motherboa...

Page 72: ...alyzed efficiently with the Filter and Find Functions Filter Displays a list of the log data that meet the filter conditions Find Focuses on the log data that meets the search conditions Note For deta...

Page 73: ...Section 5 Maintenance...

Page 74: ...a malfunction should occur or the screen becomes unreadable upon reaching the lifetime of the backlight 5 1 3 Backlights LCD Module The LCD module will have to be replaced if the contrast on the displ...

Page 75: ...e floor or otherwise subjected to excessive shock as this may cause the battery fluid to leak Make sure you have the correct type of battery and that you install it properly Replace the battery yourse...

Page 76: ...yed Logo Not Displayed Press F2 to enter SETUP Press the F2 Key while the message is displayed The Setup Menu will start and the Main Setting Dialog Box will be displayed Note The password must be ent...

Page 77: ...hinner to clean the product 5 2 2 Inspecting Inspect the NSA series Industrial PC once or twice a year Shorten the interval between inspections if the operating environment is extremely warm moist or...

Page 78: ...ver External connecting cable status No problems such as cuts or cracks Visual circuit tester Backlight contrast Sufficient contrast Service life at room temperature 25 C Use 50 000 hours as a guideli...

Page 79: ...pplied to PCI boards Check the PCI board specifications The PCI board does not operate The PCI board is not being used in the proper ambient operating temperature range There are restrictions on the a...

Page 80: ...restart the device Refer to 3 3 Installing a PCI Board and Setting the DIP Switch The date or time of the RAS log does not match the date or time of the OS The date or time in the OS was changed Set t...

Page 81: ...Appendix...

Page 82: ...ly is turned ON Logo Displayed Logo Not Displayed Press F2 to enter SETUP 1 Press the F2 Key while the message box is displayed to launch the setup menu 2 The Main Setting Screen will be displayed Not...

Page 83: ...the previous field F1 Displays the General Help Window for BIOS setup F9 Loads the default configuration value F10 Saves the settings to CMOS and exits the BIOS setup utility ESC Moves to the Exit Me...

Page 84: ...chipset Appendix 1 7 Security Sets the user and supervisor passwords as well as the backup and virus check options Appendix 1 8 Power Sets the operation that will be executed after a power failure Ap...

Page 85: ...Date MM DD YYYY Sets the system date IDE Channel 0 Master Slave Moves to submenu 1 IDE Channel 1 Master Slave None Secondary IDE is not available IDE Channel 2 3 Master Moves to submenu 2 System Memo...

Page 86: ...on is selected 16 Sectors Sets the number of sectors sent per block LBA Mode Control Not available if the Auto option is selected Enabled Enables the LBA mode 32 Bit I O Disabled Enabled Enables or di...

Page 87: ...ock LBA Mode Control Not available if the Auto option is selected Disabled Enables the LBA mode 32 Bit I O Disabled Enabled Enables or disables 32 bit data transfers between the CPU and IDE Transfer M...

Page 88: ...large disk access mode Serial ATA Disabled Enabled Enables or disables the serial ATA bus SATA RAID Enable Serial ATA Available only when enabled is selected Disabled Enabled Enables or disables RAID...

Page 89: ...r startup Note The settings in the table are initial values 3 I O Device Configuration Settings PhoenixBIOS Setup Utility Advanced F1 Help Select Item Change Values F9 Setup Defaults Esc Exit Select M...

Page 90: ...elects the I O address allocated to the COM port Interrupt IRQ 4 IRQ 3 Selects the IRQ allocated to the COM port COM Port 3 Disabled Enabled Enables or disables COM port 3 Base I O address 3F8 2FB 3E8...

Page 91: ...ay only 1 8 V V 2 5 Display only 2 5 V V 3 3 Display only 3 3 V V 5 Display only 5 V Vccp Display only 1 05 V VHVCC Display only 3 3 V CPU Temp Display only CPU temperature Ambient Temp Display only S...

Page 92: ...ting Description Post Error Logging Disabled Enabled Enables or disables POST error logging when an error occurs Clear All Error N A Deletes all POST error logs View Post Error Log View Log Hide Log D...

Page 93: ...e only when Retry is selected 1 2 3 4 14 15 Sets the number of retries from 1 to 15 Timer Mode Available only when Retry or Auto is selected 1 3 5 10 15 Sets the amount of time before the next retry a...

Page 94: ...yboard auto repeat rate 30 sec 26 7 sec 21 8 sec 18 5 sec 13 3 sec 10 sec 6 sec 2 sec Selects the number of times per second to repeat a keystroke when you hold a key down Keyboard auto repeat delay 1...

Page 95: ...dix 1 BIOS Setup Appendix 1 7 Intel Menu Appendix 15 Appendix Appendix Appendix 1 7 Intel Menu Function Setting Description MCH Control Moves to submenu 8 Video Control Moves to submenu 9 8 MCH Contro...

Page 96: ...of memory that will be used for graphics IGD Boot Type VBIOS Default CRT LCD CRT LCD EFP CRT EFP Selects the type of monitor output provided at startup Selecting VBIOS default will provide either a CR...

Page 97: ...assword status User Password Display only Clear Set Displays the user password status Set Supervisor Password Up to seven alphanumeric characters Sets the supervisor password Set User Password Up to s...

Page 98: ...iption After Power Failure Stay OFF Last State Power ON Selects the operation executed after a power failure Stay OFF Always stay OFF Last State Return to the most recent state Power ON Always stay ON...

Page 99: ...nu Boot Menu Startup Device Settings Function Setting Description Priority of the Boot Device Removable Device Hard Drive CD ROM Drive Network Boot Specifies the priority in the search for a startup d...

Page 100: ...ges N A Discards changes and exits Load Setup Defaults N A Returns to default settings Discard Changes N A Discards changes Save Changes N A Saves changes Backup CMOS Press Enter Saves the current CMO...

Page 101: ...started or the power is turned OFF The EWF function is disabled when the NSA series Industrial PC is shipped from the factory To use the EWF function you must enable it see Appendix 2 3 When the EWF f...

Page 102: ...be directly written but will be emulated on the main memory Command ewfmgr c enable Execution example Appendix 2 4 Updating Data on the Memory Card When the EWF Function Is Enabled Display the command...

Page 103: ...WF function is enabled since the data written to the Memory Card is emulated on the main memory the system memory space will be reduced and operation may become unstable when a large amount of data is...

Page 104: ...itions asp EWF Overview http msdn microsoft com library default asp url library en us xpehelp html xeconewfoverview asp EWF Architecture http msdn microsoft com library default asp url library en us x...

Page 105: ...set when the product is shipped from the factory Set a password as required If a password has been set however a keyboard will be required when logging on To use a USB connected floppy disk drive keyb...

Page 106: ...installed in the NSA series Industrial PC and an NE1S Series CPU Unit is connected using the USB port The use of either COM1 or COM 2 must be prohibited 1 Start the NSA series Industrial PC and open...

Page 107: ...ther COM1 or COM2 from the Device manager Note COM3 and COM4 are used by the NSA series Industrial PC system internally Do not select these ports 4 Click the General Tab in the displayed Communication...

Page 108: ...for motherboard and RAS board For 12 in display NS12 KBA04 Anti reflection Sheet For 15 in display NS15 KBA04 Sheet to protect the display from reflection Apply to the display 2 GB NSA CEX02 E 4 GB N...

Page 109: ...mber of times that the Memory Card can be written Setting a paging file will shorten the life of the Memory Card Create a paging file on the Memory Card only when the physical memory capacity is insuf...

Page 110: ...ustom size Option and input values to specify the Initial Size and Maximum Size Fields In the Initial size Field input the amount of memory that you want to use for the paging file In the Maximum size...

Page 111: ...ps are for deleting a paging file that was previously set up Make sure that the drive selected is C i e the Memory Card Then select the No paging file Option 4 Click the Set Button and then click the...

Page 112: ...g file size that you selected appears the paging file setup has been done properly If it does not appear return to step 2 above and make the settings again Note The operating system must be restarted...

Page 113: ......

Page 114: ...Cat No V238 E1 02 Printed in Japan 0508...