9. Appendix 1 Detailed Settings of the Tag Data Links
44
9.3. Associating the Tag Data Links
Tag data link parameters are required to perform tag data links with a destination device.
Follow the procedures below to associate the tag data links.
(1)Use the Sysmac Studio to define the global variables to publish on the network.
Store the created global variables in a CSV file to use in the Network Configurator.
(2)Read the CSV file (tag list) created in step 1 to the Network Configurator.
(3)Make a single tag set that includes the tag lists.
(4)Link the tag set with the destination device information and create tag data link
parameters.
The numbers shown in the tables below correspond to the steps above.
■
Output area (Controller
→
PLC)
Controller setting
(Set with Sysmac Studio.)
Data link table setting
(Set with Network Configurator.)
Destination device
information
(1)
Tag set:
EIP002_OUT
20byte
(4)
←
D10100-[20Byte]
Global variable
(3)
Tag list
EIP002_D1010
0_OUT
WORD
[10]
→
(2)
EIP002_D10
100_OUT
(20byte)
*Refer to
9.2
for
details.
■
Input area (Controller
←
PLC)
Controller setting
(Set with Sysmac Studio.)
Data link table setting
(Set with Network Configurator.)
Destination device
information
(1)
Tag set:
EIP002_IN
20byte
(4)
←
D10000-[20Byte]
Global variable
(3)
Tag list
EIP002_D1000
0_IN
WORD
[10]
→
(2)
EIP002_D10
000_IN
(20byte)
*Refer to
9.2
for
details.