7. EtherNet/IP Connection Procedure
34
7.5.2. Checking the Data that are Sent and Received
Confirm that the correct data are sent and received.
Always confirm safety at the destination node before you transfer a user
program, configuration data, setup data, device variables, or values in memory
used for CJ-series Units from the Sysmac Studio.
The devices or machines may perform unexpected operation regardless of the
operating mode of the CPU Unit.
1
Select
Watch Tab Page
from the
View Menu.
2
The Watch Window1 Tab Page is
displayed in the lower section of the
Edit Pane.
3
The following names are entered in
the Watch Window1 Tab Page for
monitoring.
EIP002_D10100_OUT[0]
EIP002_D10100_OUT[1]
EIP002_D10000_IN[0]
EIP002_D10000_IN[1]
4
Enter
1234
in the
Modify
Column of
EIP002_D10100_OUT[0]
.
After entering the value, press the
Enter
Key. The online value of
EIP002_D10100_OUT[0]
changes
to 1234.
Enter
5678
in the
Modify
Column of
EIP002_ D10100_OUT[1]
in the
same way.
The online value changes to 5678.