Change the Default Read Timeout
22.
Change the Default Read Timeout
22.1. Open the Global Variable page in SYSMAC Studio. See step 10.1 in the section Global Variables.
22.2. Set the initial value field of the variable ReadTime to the desired timeout in milliseconds.
22.3. Go online to the NJ/NX controller and Synchronize the project. Follow the instructions starting at 11.1 in
the section Download Project to Controller.
34
Technical Note: MicroHAWK ID-40 360
º
Barcode Reading Solution
TECHNICAL
NOTE