background image

K8AC-H

12

Voltage Fluctuation Compensation

The voltage fluctuation compensation function automatically adjusts 

the burnout alarm value of the K8AC-H according to voltage 

fluctuations in the heater circuit.

The operating value for burnout detection when multiple heaters are 

connected is set very close to the normal value. Thus, a false burnout 

alarm output will occur if there is a voltage drop in the heater circuit.

The voltage fluctuation compensation function prevents this type of 

false output.

Example: Voltage Drop from 100 V to 95 V in the Heater Circuit

Conditions: 

Voltage fluctuation compensation standard value = 100 V

Burnout alarm set value = 10.0 A

If the power supply voltage drops from 100% to 95%, the 

operating value will also reduced from 100% to 95%.

Burnout alarm operating value = 10.0 A 

×

 95% = 9.5 A

Gate Input

The gate input provides a sync signal used to link burnout detection 

to the control output of the temperature controller. 

For SSR control, the voltage output pulse from the temperature 

controller is input.

For ON/OFF control, 24 VDC linked to a relay contact of the 

temperature controller is input. 

For cyclic or phase control, a 4 to 20-mA control signal is input. 

If there is no gate input for a Heater Element Burnout Detector, a 

heater burnout alarm would be falsely output when the voltage output 

pulse from the temperature controller turns OFF, and there would be 

no way to tell whether it was a false output.

Note:

The gate input function can be disabled. If it is disabled, Heater 

Element Burnout Detector operation will not be linked to the 

temperature controller control signal. (The gate input can be 

used as a simple undercurrent relay.)

Power-saving Operation

If there are no key operations performed within a preset time period, 

the display automatically turns OFF.

Output Operation Time Charts
Heater Burnout and Heater Layer Short Circuit 
(Overcurrent) Alarms

SSR Short/Open Circuit Alarm

Using the Power Regulator's Gradient Settings

The power regulator's gradient settings can be used to prevent 

malfunction by setting the operation gate current level. The 

relationship between the gradient settings and output current 

depends on the power regulator manufacturer and model, so be sure 

to check the characteristics of the power regulator being used before 

setting.

Setting Example

Initial setting: 7 mA

When the power regulator's gradient settings are changed, the 

operation gate current level is set so that the output current is within 

the measurement range. (In the following diagram, 14 mA is set.)

Using Halogen or Other Heaters with Varying 
Resistance during Phase and Cyclic Control

When phase control is used with halogen heaters or other pure metal 

heaters, the heater resistance fluctuates according to the control 

level. As a result, high-precision detection of heater burnout is not 

possible. The effect on the heater and setting methods depends on 

the heater being used. Therefore, consult with your OMRON 

representative before using a heater with varying resistance values.

Halogen Heater Resistance Fluctuation Example

In the following example, burnout of one element in a six-element 

heater can be detected at a control level of 20 mA, but detection is not 

possible due to the effect of fluctuating resistance if the control level 

is any lower.

Power Save Mode

Standby Time

Heater burnout set value

Heater current

Alarm hysteresis 

Heater layer short circuits

Overcurrent set value

ALM indicator lights. ALM indicator lights.

Alarm output

SSR open-circuit

SSR indicator lights. SSR indicator lights.

Alarm output

SSR short-circuit

4 mA

0%

100%

7 mA

20 mA

Output current

Measurement range

Gradient 

setting 100%

Control signal

Not detected

Detected

4 mA

14 mA

20 mA

0%

100%

Output current

Measurement range

Gradient 

setting 100%

Gradient 

setting 50%

Control signal

Not detected

Detected

7 mA

20 mA

4 mA

Heater resistance

Detectable range

Three elements

burned out

One element 

burned out

Threshold

Normal 

(six elements in parallel)

Control signal

Summary of Contents for K8AC-H Series

Page 1: ...nitor for element burnouts on heaters controlled with power regulators that used a three alarm method Normal monitoring is not possible for circuits that use a power regulator with a six alarm method...

Page 2: ...re linked with the control output value from the temperature controller Compatible with Gradient Settings of Power Controllers When using gradient settings with a power controller set a gate current l...

Page 3: ...tput specifi cations Com munica tions output Current input range 0 200 to 2 200 A 2 00 to 22 00 A 20 0 to 200 0 A 100 to 240 VAC ON OFF control SSR control Two current inputs for either single phase o...

Page 4: ...ut impedance 4 k min Cyclic and phase con trol 4 to 20 mA DC Burnout detection is possible for an input of 7 mA or greater Input impedance 50 max Outputs Relay contact outputs K8AC H C FLK One SPDT re...

Page 5: ...als and output terminals Dielectric strength 2 000 V for 1 min Between terminals and case Between power supply terminals CT primary terminals and gate input terminals communications terminals Between...

Page 6: ...VAC 0 3 A 30 VDC 1 A Maximum contact voltage 125 VAC 60 VDC Maximum contact current 1 A Maximum switching capaci ty 37 5 VA 30 W Minimum applicable load failure rate P value refer ence value 5 VDC 10...

Page 7: ...ct to the operating power supply All models 3 to 4 5 to 6 Outputs Outputs SSR open or short circuit detection results Outputs heater burnout or layer short circuit detection results K8AC H2 N transist...

Page 8: ...CTs for three phase heaters For three phase heaters always set the burnout alarm set values for both CT1 and CT2 5 6 3 4 Transistor Output K8AC H2 N FLK CT2 CT1 3 7 8 9 10 11 12 13 14 1 2 RS 485 X 4 5...

Page 9: ...ransistor Output K8AC H2 N FLK Heater Power supply Power Regulator Temperature Controller 4 to 20 mA current output Operation Description If the heater current detected at either CT1 or CT2 falls belo...

Page 10: ...o after one heater burns out with the current prior to the burnout i e the normal current taken as 1 3 In actual operation there may be effects from factors such as load heater imbalances so conduct a...

Page 11: ...s output accordingly SSR Short Circuit Detection If current is measured when there is no gate input an SSR short circuit error is detected and an alarm is output SSR Open Circuit Detection If current...

Page 12: ...Short Open Circuit Alarm Using the Power Regulator s Gradient Settings The power regulator s gradient settings can be used to prevent malfunction by setting the operation gate current level The relati...

Page 13: ...or over OFF for less than 4 mA SSR SSR error Lights when an SSR error occurs open or short circuit OFF when SSR is normal ALM Alarm Lights for heater burnout or overcurrent OFF at all other times Up k...

Page 14: ...pe P should be selected Type P is also selected for cyclic control Select the appropriate relay or transistor output specifications depending on the application K8AC H Parameter Settings Procedure Onl...

Page 15: ...freshed each time an alarm is output and it is saved in non volatile memory The value is saved when power is interrupted The number of outputs is not counted for the test function After counting to 99...

Page 16: ...r at least 1s Press the L key for at least 1 s Press the S key for at least 1 s Press the L key for at least 1s When the key is released Press the S key for at least 1 s Press the L and M keys Press t...

Page 17: ...layer short circuit detection function SSR open circuit detection function SSR short circuit detection function Output ON delay time Soft startup time Startup lock time Gate input function Alarm hyst...

Page 18: ...99 9 s 0 0 OFF SSR Short Circuit Detection Turns the SSR short circuit detection function ON and OFF ssht ON OFF OFF SSR Open Circuit Detection Turns the SSR open circuit detection function ON and OFF...

Page 19: ...te current level Sets the gate current level for SSR operation This setting is valid only when cyclic or phase control is selected as the heater control method sglv 4 0 to 20 mA 7 0 mA Cycle time 3 Se...

Page 20: ...ntact Approx 3 dia 18 22 Approx 6 dia Plug Contact Lead Plug 100 15 30 30 5 Two M3 Depth 4 max 12 dia 40 40 5 15 Current Transformer K8AC CT200 Pre wired Leads Current Transformer K8AC CT200L 1 8 76 4...

Page 21: ...o can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose...

Page 22: ...larm of the K8AC H P FLK when phase control is used Set the burnout alarm value of the K8AC H P FLK based on the current measurement value with the heater output at 100 This is because the burnout det...

Page 23: ...RODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR A...

Page 24: ...em as a whole has been designed to address the risks and that the OMRON products are properly rated and installed for the intended use within the overall equipment or system Authorized Distributor In...

Reviews: