Single-phase Voltage Relay

 

K8AB-VS

Cat. No. N143-E1-01

Connections

Wiring Diagram

Overcurrent Operation Diagram 
(Output: Normally Closed)

Note:

The power ON lock prevents unnecessary alarms from being 
generated during the instable period when the power is first 
turned on. There is no relay output during timer operation.

Undercurrent Operation Diagram 
(Output: Normally Open)

Note:

The power ON lock prevents unnecessary alarms from being 
generated during the instable period when the power is first 
turned on. There is no relay output during timer operation.

Nomenclature

Front

Indicators

Setting Knobs

T1

T

Input

Hysteresis 
(5% to 50% of operating value)

Lit

Flashing

Operating value

Control power

Relay

Alarm indicator

T: Operating time (0.1 to 30 s)

T1: Startup lock time (1 or 5 s)

Control power

Relay

Operating value

Alarm indicator

Input

Lit

Flashing

T1

T1: Power ON lock (1 or 5 s)

T

T: Operating time (0.1 to 30 s)

Hysteresis 
(5% to 50% of operating value)

Model

Measuring range

Connection

K8AB-VS1

6 to 60 mV AC/DC

V1-COM

10 to 100 mV AC/DC

V2-COM

30 to 300 mV AC/DC

V3-COM

K8AB-VS2

1 to 10 V AC/DC

V1-COM

3 to 30 V AC/DC

V2-COM

15 to 150 V AC/DC

V3-COM

K8AB-VS3

20 to 200 V AC/DC

V1-COM

30 to 300 V AC/DC

V2-COM

60 to 600 V AC/DC

V3-COM

Output

COM

A1

A2

V1

V2

V3

14

12

11

Single-phase power

Operating 
power

Alarm

Input

Load

Power indicator

Relay status indicator

Voltage knob (SV) 

Hysteresis knob (HYS.)

Operating time knob (T)

Alarm indicator

Item

Meaning

Power indicator (PWR: 
Green)

Lit when power is being supplied.

Relay status indicator (RY: 
Yellow)

Lit when relay is operating. 

Alarm indicator (ALM: Red) Lit when there is an overvoltage or 

undervoltage. 
The indicator flashes to indicate the 
error status after the input has 
exceeded the threshold value while the 
operating time is being clocked.

Item

Usage

Current knob (SV)

Used to set the current to 10% to 100% 
of maximum rated input current.

Hysteresis knob (HYS.)

Used to set the rest value to 5% to 50% 
of the operating value.

Operating time knob (T)

Used to set the operating time to 0.1 to 
30 s.

Summary of Contents for K8AB-VS Series

Page 1: ...tus easily monitoring using LED indicator Input frequency of 40 to 500 Hz supported Easy wiring with ferrules 2 2 5 mm2 solid or 2 1 5 mm2 standard ferrules CE mark compliance certified by third party...

Page 2: ...VS3 100 115 VAC 200 230 VAC K8AB VS3 200 230 VAC Operating power Non isolated power supply 24 VDC 1 W Isolated power supply 24 VAC 4 VA 100 to 115 VAC 4 VA 200 to 230 VAC 5 VA Operate SV Operating val...

Page 3: ...d uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5Y8 1 ivo...

Page 4: ...sis 5 to 50 of operating value Model Measuring range Connection K8AB VS1 6 to 60 mV AC DC V1 COM 10 to 100 mV AC DC V2 COM 30 to 300 mV AC DC V3 COM K8AB VS2 1 to 10 V AC DC V1 COM 3 to 30 V AC DC V2...

Page 5: ...Switch SW3 SW4 SW1 Function Default SW1 Power ON lock time OFF 1 s OFF ON 5 s SW2 Resetting method OFF Manual reset OFF ON Automatic reset SW3 Relay drive method OFF Normally open normally OFF OFF ON...

Page 6: ...ing values appropriate for the controlled object Failure to do so can cause unintended operation and may result in accident or corruption of the product 3 Do not use thinner or similar solvent for cle...

Page 7: ...ndividual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT TH...

Reviews: