background image

K7L-UP-FLK

4

Communications Performance

*

Baud rate, data length, stop bit length and vertical parity can be separately set.

Communications protocol

CompoWay/F

Modbus (RTU mode)

Transmission path connections

Multi-point (32 nodes max. including Master)

Communications method

RS-485 (two-wire method, half-duplex)

Synchronization method

Start-stop synchronization

Baud rate 

*

4800/9600/19200/38400 bps

Transmission code

ASCII

Binary

Data length 

*

7/8 bits

8 bits

Stop bit length 

*

1/2 bits

Set automatically (no setting) depending on the 
vertical parity setting.
Without vertical parity: 2 bit
With vertical parity: 1 bit

Error detection

Vertical parity (none, even odd)
BCC (Block Check Character)

Vertical parity (none, even odd)
CRC-16 (Cyclical Redundancy Check)

Wait time

00 to 99 ms (Default: 20 ms)

This catalog is intended only as a guide to selecting a product. For details on precautions when using the product, 
be sure to read the [K7L-UP-FLK Liquid Leakage Position Sensor Operation Manual] (Cat. No. Z287). 
The manual can be downloaded from the following website. 
OMRON Industrial website:  

http://www.ia.omron.com/

Summary of Contents for K7L-UP-FLK

Page 1: ...easy to install UL approval List of Models Note 1 The Controller cannot be ordered separately 2 Included with the K7L UP FLK but can be ordered separately Basic configuration Area Separators can be us...

Page 2: ...DC Mechanical 20 million outputs Electrical 80 000 outputs 24 VDC at 5 mA reference value 100 m max default 4 to 20 mA output Allowable load resistance Resolution Error Steady state At error detection...

Page 3: ...in X Y and Z directions Shock resistance 130 m s2 3 times each for 3 axes in six directions Weight Sensor only Approx 185 g Memory protection EEPROM non volatile memory Installation environment Insta...

Page 4: ...8 bits Stop bit length 1 2 bits Set automatically no setting depending on the vertical parity setting Without vertical parity 2 bit With vertical parity 1 bit Error detection Vertical parity none even...

Page 5: ...combination with a button Up Cursor Button Moves the selected item up Moves the selected item up Moves the number or character forward Down Cursor Button Moves the selected item down Moves the selecte...

Page 6: ...disconnection output contacts NC Free terminal 4 Leakage disconnection output contacts 12 External reset 5 RS 485 B 13 External reset 6 RS 485 A NC Free terminal 7 Linear outputs 15 Detect wire Red C...

Page 7: ...e internally isolated Internal Block Diagram 12 13 COM 6 V 4 7 k 7 8 L 500 Max 2 1 Relay 3 4 Relay Power supply circuit X X Linear outputs circuit Drive circuit Reset circuit External reset 4 to 20 mA...

Page 8: ...is function changes the length of the Sensing Cable to any value When there is a discrepancy between the actual length and the measured length this value can be revised to any value for compensation O...

Page 9: ...ession may not be sufficient Dimensions Unit mm Product name Model A Connecting Cable F03 21UP CC B Sensing Cable F03 16UP C M 1 C Area Separator 2 F03 20UP AS D Junction Cable 3 F03 21UP JC E Termina...

Page 10: ...kel Insulation coating Fluororesin Connector materials Metallic parts Brass with nickel plating Resin parts Polyolefine resin Insulation resistance 10 M min Ambient temperature 10 to 55 C Ambient humi...

Page 11: ...pearance Dimensions Junction Cable F03 21UP JC 67 4 7 15 dia 2 050 M12 15 dia 63 Adhesive tape 25 2 15 1 3 5 0 5 1 Material SUS304 Area Separator Leak positions in meters can be divided into up to 20...

Page 12: ...the product in parallel with or bundled with power lines Using separate conduits or ducts and shielded cables can also be effective 14 Do not allow pieces of metal wire clippings or fine metallic sha...

Page 13: ...13 MEMO...

Page 14: ...MEMO 14...

Page 15: ...ons or uses not described in this document Nuclear energy control systems combustion systems railroad systems aviation systems medical equipment amusement machines vehicles safety equipment and instal...

Page 16: ...Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Tokyo JAPAN OMRON ASIA PACIFIC PTE LTD No 438A A...