8

Parameter Selection

When a parameter selector pin is set to OFF, the corresponding set value that has been changed will be stored in the non-volatile memory. Any
data that has been previously set will be kept in the non-volatile memory regardless of whether the K3TJ is turned on or off. The following table
lists the parameters assigned to parameter selector pins 1 to 8.

13

4

5

6

7

8

2

ON

OFF

ON

Pin no.

Setting

1

Input range

2

Display shift

3

Scaling

4

Decimal point

5

Averaging

6

Zero limit

7

Step display

8

Display brightness

Parameter Setting

The K3TJ is factory-set to display 0 when the minimum input range value is input and display 1,000 when the maximum input range value is
input.
DC Voltage Input Model

Input range

Display

0- to 5-VDC input

0

to

1000

1- to 5-VDC input

0

to

1000

0- to 10-VDC input

DC Current Input Model

Input range

Display

4 to 20 mA DC input

0

to

1000

1000

0

max.

min.

Display

Input

Adjust the display shift and scaling for the K3TJ
while applying an actual input.

1. Input Range Setting

Select the 0- to 5-V, 1- to 5-V, or 0- to 10-V input range on the DC Voltage Input Model and 4- to 20-mA input range on the DC Current Input
Model.

Example: When selecting the 1- to 5-V input range on the DC Voltage Input Model

Use the Up or Down Keys so that

1- 5

will be displayed.

Up Key or
Down Key

0- 10

1

3
4
5
6
7
8

2

1

3
4
5
6
7
8

2

OFF

ON

OFF

ON

1- 5

Set parameter selector pin 1 to ON, at which time the
factory-set input range

0- 10

will be displayed.

When

1- 5

is displayed, set parameter selector pin 1 to

OFF to complete the input range setting.

The input range has been changed to
the 1 to 5 V range.

DC Voltage Input Model

Display

Input range

0- 5

0 to 5 VDC

1- 5

1 to 5 VDC

0-10

0 to 10 VDC (factory-set)

DC Current Input Model

Display

Input range

4-20

4 to 20 mA DC

Summary of Contents for K3TJ

Page 1: ...htness can be adjusted Conforms to the EMC standard EN61010 1 IEC1010 1 uC Ordering Information DC Voltage Input Model Voltage measurement range Display color Supply voltage g g p y 100 to 240 VAC 24...

Page 2: ...nce Malfunction 10 to 55 Hz 0 5 mm single amplitude for 10 minutes each in X Y and Z directions Destruction 10 to 55 Hz 0 75 mm single amplitude for 2 hours each in X Y and Z directions Shock resistan...

Page 3: ...panel meets the requirements of IP50 instead Measuring Ranges Measuring range Input impedance Reliability Max permissible continuous load Voltage DC 1 to 5 VDC 1 M 0 1 rdg 1 digit 250 V g 0 to 5 VDC 1...

Page 4: ...iver into the groove on the bottom of the front panel and pull the front panel off The following is seen after the front panel is removed Parameter selector Up Key Down Key 1 34 5 6 7 8 2 ON No Name P...

Page 5: ...o 1000 0 to 10 VDC input DC Current Input Model Input range Display 4 to 20 mA DC input 0 to 1000 1000 0 max min Display Input Adjust the display shift and scaling for the K3TJ while applying an actua...

Page 6: ...the display To change the value to 0 use the Down Key The displayed value will increase automatically if the Up Key is pressed for 1 s or more and will decrease automatically if the Down Key is press...

Page 7: ...er selector pin 3 to ON at which time the display will not change but a scaling adjustment will be possible After 1200 is displayed set parameter selector pin 3 to OFF to complete the scaling adjustme...

Page 8: ...gntimes This methodis effectivewhentheuserrequiresa long display refresh period Inmovement averageprocessing method the samplingdata obtainedfrom samplingn times including thepresent samplingoperation...

Page 9: ...mit setting range off No zero limit factory set Zero Limit Setting Range Display Zero limit setting value Input 7 Step Display Setting Step display setting is used to change the step of the displayed...

Page 10: ...alue stored in the non volatile memory has been corrupted Execute display shift again according to the display shift adjustment procedure e 12 The scaling value stored in the non volatile memory has b...

Page 11: ...ections 24 VDC HOLD GND GND 0 to 10 VDC 0 to 5 VDC 1 to 5 VDC 4 to 20 mA DC INPUT POWER 3 2 1 4 5 6 7 8 9 100 to 240 VAC Note Terminals 3 and 6 are connected internally The power supply terminals are...

Page 12: ...le Never use the K3TJ in locations where corrosive gas particularly sulfuric or ammonia gas exists Avoid use of the K3TJ in locations subject to severe shock or vibra tion excessive dust or excessive...

Page 13: ...n Phone 06 949 6012 Fax 06 949 6021 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No N080 E1 1C In...