Scaling Meter

K3TJ

Highly Functional Scaling Meter with
Versatile, Easy-to-read Red or Green
Display

Red or green display color available.

Wide range of scaling settings, including negative
scaling.

Simple average and movement average proces-
sing methods allow 4 s max. to display the process
value, thus reducing display blinking and making it
easier to read the display.

Step display setting adjusts the step of the
displayed rightmost digit to 2, or 5.
It is possible to fix the displayed rightmost digit to 0.

Zero limit setting enables the K3TJ to display zero
for any value less than the set value and is ideal for
water depth display.

Display brightness can be adjusted.

Conforms to the EMC standard EN61010-1
(IEC1010-1).

uC

Ordering Information

DC Voltage Input Model

Voltage measurement range

Display color

Supply voltage

g

g

p y

100 to 240 VAC

24 VDC (internally insulated)

1 to 5 VDC, 0 to 5 VDC, and 0 to
10 VDC (

lti

)

Red

K3TJ-V111R

K3TJ-V116R

,

,

10 VDC (multi-range)

Green

K3TJ-V111G

K3TJ-V116G

DC Current Input Model

Current measurement range

Display color

Supply voltage

g

p y

100 to 240 VAC

24 VDC (internally insulated)

4- to 20-mA DC

Red

K3TJ-A111R

K3TJ-A116R

Green

K3TJ-A111G

K3TJ-A116G

Model Number Legend

K3TJ-

jjjjj

1

2

3

4

5

1, 2. Input Code

V1: DC voltage input

1 to 5 VDC, 0 to 5 VDC, and 0 to 10 VDC (multi-range)

A1: DC current input

4 to 20 mA

3.

Series No.

1:

Present series

4.

Supply Voltage

1:

100 to 240 VAC

6:

24 VDC (internally insulated)

5.

Display Color

R:

Red LED

G:

Green LED (available upon request)

Summary of Contents for K3TJ

Page 1: ...htness can be adjusted Conforms to the EMC standard EN61010 1 IEC1010 1 uC Ordering Information DC Voltage Input Model Voltage measurement range Display color Supply voltage g g p y 100 to 240 VAC 24...

Page 2: ...nce Malfunction 10 to 55 Hz 0 5 mm single amplitude for 10 minutes each in X Y and Z directions Destruction 10 to 55 Hz 0 75 mm single amplitude for 2 hours each in X Y and Z directions Shock resistan...

Page 3: ...panel meets the requirements of IP50 instead Measuring Ranges Measuring range Input impedance Reliability Max permissible continuous load Voltage DC 1 to 5 VDC 1 M 0 1 rdg 1 digit 250 V g 0 to 5 VDC 1...

Page 4: ...iver into the groove on the bottom of the front panel and pull the front panel off The following is seen after the front panel is removed Parameter selector Up Key Down Key 1 34 5 6 7 8 2 ON No Name P...

Page 5: ...o 1000 0 to 10 VDC input DC Current Input Model Input range Display 4 to 20 mA DC input 0 to 1000 1000 0 max min Display Input Adjust the display shift and scaling for the K3TJ while applying an actua...

Page 6: ...the display To change the value to 0 use the Down Key The displayed value will increase automatically if the Up Key is pressed for 1 s or more and will decrease automatically if the Down Key is press...

Page 7: ...er selector pin 3 to ON at which time the display will not change but a scaling adjustment will be possible After 1200 is displayed set parameter selector pin 3 to OFF to complete the scaling adjustme...

Page 8: ...gntimes This methodis effectivewhentheuserrequiresa long display refresh period Inmovement averageprocessing method the samplingdata obtainedfrom samplingn times including thepresent samplingoperation...

Page 9: ...mit setting range off No zero limit factory set Zero Limit Setting Range Display Zero limit setting value Input 7 Step Display Setting Step display setting is used to change the step of the displayed...

Page 10: ...alue stored in the non volatile memory has been corrupted Execute display shift again according to the display shift adjustment procedure e 12 The scaling value stored in the non volatile memory has b...

Page 11: ...ections 24 VDC HOLD GND GND 0 to 10 VDC 0 to 5 VDC 1 to 5 VDC 4 to 20 mA DC INPUT POWER 3 2 1 4 5 6 7 8 9 100 to 240 VAC Note Terminals 3 and 6 are connected internally The power supply terminals are...

Page 12: ...le Never use the K3TJ in locations where corrosive gas particularly sulfuric or ammonia gas exists Avoid use of the K3TJ in locations subject to severe shock or vibra tion excessive dust or excessive...

Page 13: ...n Phone 06 949 6012 Fax 06 949 6021 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No N080 E1 1C In...

Reviews: