78
Hysteresis
•
The hysteresis can be set in the option menu to prevent “chattering” of the out-
put if the measured value fluctuates in the vicinity of the setting values.
•
The hysteresis can be set within a range of 1 and 9999 digits for four consecu-
tive digits beginning with the leftmost digit regardless of the decimal point.
•
The value set to 0 is regarded as 1.
•
The decimal point position set in the scaling menu becomes valid.
Setting range
Unit
Default
1 to 9999
---
1
If the comparative output is a level output, however, the hysteresis will be en-
abled when the measured value starts to become smaller than the HH, H, LL,
and L setting values.
Measured value
H setting value
L setting value
H comparative output
L comparative output
Hysteresis
Hysteresis
This setting is only available for the K3NR with the Comparative Output Unit.
Follow the steps described below to set the hysteresis to 30.
Set Value LED Display Model
Basic Model
1, 2, 3...
1. Press the Mode Key for more than one second while the
opt
option menu is
displayed. The
aUg
average processing setting will appear.
Set Value LED Display Model
Basic Model
hys
FUNCTION
SETTING
REFERENCE
MODELS
SETTING
EXAMPLE
Setting Mode
Section 4-2