48
H7CX-R
@
-N
Key Protect Level
When the key-protect switch is set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-7). The key protect level is set in the function setting mode. The key protect indicator is lit when the key-protect switch
is ON.
* Changing mode to DIP switch monitor mode or function setting mode.
Self-diagnostic Function
The following displays will appear if an error occurs.
*1. This includes times when the life of the EEPROM has expired.
*2. Occurs when the measurement value reaches 999,999.
*3. Display flashes (1-second cycles).
*4. The normal display and
e3
will appear alternately.
When the Hold Key is pressed,
e3
will not be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the counter will continue
without clearing the output ON count.)
Level
Meaning
Details
Changing mode*
Switching display
during operation
Hold Key
Up Key
KP-1
(default setting)
Invalid
Valid
Valid
Valid
KP-2
Invalid
Valid
Invalid
Valid
KP-3
Invalid
Valid
Valid
Invalid
KP-4
Invalid
Valid
Invalid
Invalid
KP-5
Invalid
Invalid
Invalid
Invalid
KP-6
Invalid
Invalid
Valid
Valid
KP-7
Invalid
Invalid
Invalid
Valid
Main display
Sub-display
Error
Output status
Correction method
Set value after
reset
ffffff
*3
No change
Measurement value overflow*2
No change
Measurement value
≤
999999
No change
e1
Not lit
CPU
OFF
Either press the hold key or reset the
power supply.
No change
e2
Not lit
Memory error (RAM)
OFF
Turn ON the power again.
No change
e2
sum
Memory error (EEP)*1
OFF
Hold Key
Factory setting
e3
*4
No change
Output Counter Overflow
No change
Hold Key
No change
Key protect indicator
*Factory-set to OFF
ON
(Enable)
OFF
(Disable)
*