H7BR
H7BR
15
■
SIDE VIEW
All DIP switches are set to OFF at the factory.
ON
OFF
Not used
–
–
Output level H L
L H
Not used
–
–
AUX power
24 VDC
12 VDC
Model
Switch no.
1
2
3
4
Operation of each transistor
Invalid
External power
output when count up
supply
Single preset
OFF
—
Output OFF to ON
—
12 VDC
ON
—
Output ON to OFF
—
24 VDC
Double preset
OFF
Output 1
Output 2
—
12 VDC
OFF to ON
OFF to ON
ON
Output 1
Output 2
—
24 VDC
ON to OFF
ON to OFF
Model
H7BR-B (standard)
H7BR-C (+/– range)
Present count
0
0
Presets
0
0
Batch count
0
Not applicable
Batch count preset
0
Not applicable
Input mode
Up
Reversible C (phase difference)
Output mode
N
K
Output 2 time
Hold
1,000 ms
Output 1 time (2-stage only)
Hold
1,000 ms
CP1 and CP2 counting speeds
30 cps
30 cps
Min. reset time
20 ms
20 ms
Decimal point
Far right (no fractions)
Far right (no fractions)
Scale factor
1,000
1,000
Compensation
Not applicable
0
Key protection level
KP-1
KP-1
although power supply is required for inputs and outputs to
operate. Outputs are not possible with the presets set to zero.
The following data is set at the factory. Be sure to make any
setting changes before operating the counter. Setting and
display changes are possible with or without power supplied,
■
FACTORY SETTINGS