M-BUS Series 

 

Instruction Manual 

 

wMBHL

 is microcontroller-based pulse counter with 2 pulse inputs and wireless m-bus interface. 

It is used for connection of tax  meters with pulse outputs for wireless  readout. It  can be mounted on the 
wall, not for DIN-rail and comes in IP 54 enclosure. wMBHL does not support tariffs, but user can set initial 
value for each pulse input and multiplier (pulse weight). Device works on battery and has estimated life of 
10  years,  while  transmitting  every  minute.  Minimum  pulse length  to  be  measured  is  50ms  (10Hz  pulses), 
which for water meters is more than enough. 

 

1. Main technical parameters 

- pulse inputs 

 

 

 

– 2 

- supply voltage 

 

 

 

– 3.6 Vdc 

- wireless m-bus mode 

 

  

– T1, OMS compatible 

- pulse frequency, max  

 

 

- 10 Hz 

- input NO resistance 

 

 

- 470 kOhm 

- indication 

 

 

 

- one yellow LED 

- storage temperature 

  

 

- -50

÷

+90 

°

- air humidity, working  

 

 

- 40

÷

90 % 

- dimensions (H/W/D max)  

  

 

– 74/74/40mm 

- communication parameters   

 

– 4800 bps, Even 

- weight    

 

 

 

– < 30 g 

- battery   

 

 

 

– 3.6Vdc, 10+1 years life  

 

 

2. How wMBHL works 

wМBHL  comes  into  storage  mode.  This  means  that  the  counter  is  not  enabled  to  transmit  and 

count pulses. This is made in order  to preserve battery. Device can be  turned ON via our software, using 
optical  head,  or  by  a  pushbutton  on  the  PCB  board.  Once  enabled  pulse  counter  CAN  NOT  be  returned  in 
storage mode. Then wMBHL starts to work in normal mode. This means that all pulses on the two inputs are 
counted and stored in internal memory. Each minute device sends an wireless m-bus telegram in mode T1, 
in which total value for both inputs is transmitted. Total value is calculated by taking in hand pulse weight 
(multiplier) and initial value, set for each input. By default initial value is 0 and multiplier is 1 (1l/pulse). 

Transmitting time can be changed from 30 seconds to 3 minutes, by step of 10 seconds. User can 

also save AES-128 key (Mode 5) and enable or disable AES encryption of the telegram. 

 The battery life is guaranteed for 10 years of work, transmitting every minute. 

 

Turning wMBHL on 

 

Turning  on  wMBHL  is  done  via  wMBHL  setting  software  and  is  irreversible.  User  can  also  use  a 

pushbutton  on  the  board  to  do  that.  Push  button  must  be  pressed  and  hold  down  for  6  seconds,  then 
wMBHL will go into normal work mode. 

 

3. Mounting and electrical connections 

 

wМBHL can be mounted on a wall or other horizontal or vertical surface. Every connection should 

be made with 0.25mm

2

1.5mm

2

 isolated cables, according to the following table:  

No. on the picture 

Description 

IN 1+ 

Positive terminal pulse input 1 - if open collector used 

IN 1- 

Negative terminal pulse input 1  

 

 

IN 2+ 

Positive terminal pulse input 2 - if open collector used 

IN 2- 

Negative terminal pulse input 2 

 
Max. length of each pulse input cable is 15m for twisted pair 0.5mm

2

 

 
4. Inputs and pulse counting 

 

wМBHL  has  two  independent  inputs  for  pulse  counting.  Pulse  weight  for  each  input  can  be 

programmed  independently.  The  pulses  are  collected  in  separate  arrays  for  every  input.  Pulse  counts 
specially of MBHL can be changed through the Gineers software. The idea is to have same on counter and 
water-meter. Pulse counters are stored in non-volatile memory at every power interruption. The data is also 
save in non-volatile memory once a month. 
 

Maximum pulse frequency can be 20Hz. The input pulses can come from: 

 

- non-potential contact (reed contact) 

 

- transistor opto-coupler output 

 

- open collector, if it can work on 3.3Vdc  

 
 

In the last two cases the polarity must be observed. The minimum resistance of the open contact 

should  be  greater  than  1  MOhm,  while  the  maximum  resistance  (including  connecting  cable  resistance) 
should be less than 1 kOhm. Connecting cable length should be no greater than 15m. It is recommended to 
use twisted pair cable type. 
 

Counters rollover to zero when value of 99999999 is reached. 

 

6. Warranty 

 

The  warranty  of  the  device  is  limited  to  3  years  from  the  date  of  sale.  If  the  device  shows  any 

defect  or  malfunctions  during  that  period,  the  manufacturer  is  obligated  to  repair  the  device  in  its  own 
service for manufacturer’s expense, or, if the repair is impossible, to replace the device with the new one. 
The  transportation  costs  to  the  manufacturer’s  service  are  due  to  the  client.  The  warranty  voids  if  this 
manual’s instructions are not met, warranty seals are  removed or the device was opened by unauthorized 
by the manufacturer personnel.  
 
Serial/ ID number:....................     

       

 

            Date of sale: …........................... 

 

Signature: .................................. 

 

7. Package contains 

 

wMBHL - 1 pc. 

 

Instruction manual - 1 pc.  

 

 
8. Manufacturer 

Gineers Ltd., bulding 7, “Iskarsko chausse” 7 blvd.,  
TCE, 1528 Sofia, Bulgaria  
Tel/fax (+359-2) 9758105,   
URL: http://www.gineers.com,  
e-mail: [email protected] 
 

 
 
 
 