H5L
2
■
Characteristics
Note:
The overall error, which includes repeat accuracy, setting error, and variations due to changes in voltage and temperature, is
±
0.01% or
±
0.05 s max. The accuracy of
±
0.01% also indicates the error in the time interval of the set time.
Engineering Data
Accuracy of operating time
±
0.01%
±
0.05 s max. (see note 1)
Setting error
Influence of voltage
Influence of temperature
Time accuracy
±
15 s per month (at 25
°
C)
Insulation resistance
100 M
Ω
min.
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying
metal parts and between control power supply circuit and contact control output circuits)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance
Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance
Destruction: 300 m/s
2
(approx. 30G)
Malfunction: 100 m/s
2
(approx. 10G)
Ambient temperature
Operating: –10
°
C to 55
°
C
Ambient humidity
Operating:
35% to 85%
Life expectancy
100,000 operations min. (15 A at 250 VAC, resistive load)
Approved standards
UL (File No. E52800), CSA (File No. LR22310)
Weight
Approx. 350 g
Ambient Operating Temperature and Carry Current
Upper limit of ambient temper
ature (
°
C)
Carry current AC/DC (A)
Note that the upper limit of the ambient operating temperature
lowers when a large carry current is being applies as shown below.