B-24
Solid-state Twin Timer
H3DS-F
Specifications
■
General
Note:
Can be mounted to 35-mm DIN Track with a plate thickness of 1 to 2.5 mm.
■
Time Ranges
Note:
When the time setting dial is set to “0” for any time scale, the output will operate instantaneously.
■
Ratings
Note:
DC ripple rate: 20% max.
Item
H3DS-F
Operating mode
Flicker-OFF/Flicker-ON start
Output type
Relay: SPDT
External connections
Screw terminal, Screw-Less Clamp
Terminal block
Screw terminal type:
Clamps two 2.5-mm
2
max. bar terminals without sleeves.
Screw-Less Clamp type: Clamps two 1.5-mm
2
max. bar terminals without sleeves.
Terminal screw tightening torque
0.98 N·m max.
Mounting method
DIN track mounting (see note)
Attachment
Nameplate label
Approved standards
UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P 100
Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 1 A/DC-13; 30 V 0.1 A)
Time scale display
Time range
0.1 s
0.1 to 1.2 s
1 s
1 to 12 s
0.1 m
0.1 to 1.2 min
1 m
1 to 12 min
0.1 h
0.1 to 1.2 h
1 h
1 to 12 h
Rated supply voltage (See note.)
24 to 230 VAC (50/60 Hz)/24 to 48 VDC
Operating voltage range
85% to 110% of rated supply voltage
Power reset
Minimum power-off time: 0.1 s
Reset voltage
2.4 VAC/DC max.
Power consumption
AC: 33 VA max./2.2 W max. (typical: 31 VA/2.0 W) at 230 VAC
11 VA max./1.9 W max. (typical: 9.7 VA/1.7 W) at 100 to 120 VAC
DC: 0.7 W max. (typical: 0.6 W) at 24 VDC
1.4 W max. (typical: 1.2 W) at 48 VDC
Voltage input
Max. permissible capacitance between inputs lines (terminals B1 and A2): 2,000 pF
Load connectable in parallel with inputs (terminals B1 and A1).
H-level: 20.4 to 253 VAC/20.4 to 52.8 VDC
L-level: 0 to 2.4 VAC/DC
Control output
Contact output:
5 A at 250 VAC with resistive load (cos
φ
= 1)
5 A at 30 VDC with resistive load (cos
φ
= 1)
Ambient temperature
Operating: –10
°
C to 55
°
C (with no icing)
Storage:
–25
°
C to 65
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%