background image

B-26

Solid-state Twin Timer 

H3DS-F

Connections 

Block Diagram

I/O Function

Terminal Arrangement

Note: 1.

If voltage is applied to terminal B1, or if terminals A1 and B1 are shorted, the operating mode is switched to flicker-ON start mode. If these
terminals are disconnected, the mode switches to flicker-OFF start mode.

2.

DC supply voltage does not require the designation of polarity.

AC (DC) 
input

ON 
indicator 
(Orange)

OFF 
indicator 
(Green)

ON/OFF start 
selector

Indicator 
circuit

One-chip microcomputer

ROM

RAM

Clock

Time scale 
selector

Output 
circuit

Power 
supply 
circuit

Inputs

Flicker-ON start operation begins when inputs are turned ON.

Outputs

Control output

Outputs are turned ON/OFF according to the time set by the ON-and OFF-time setting dial.

A1

15

15

18

18

16

16

A2

18

16

A2

15

L

18

16

B1

A1

15

B1

H3DS-FLC

H3DS-FL

(See note 2.)

Summary of Contents for H3DS Series

Page 1: ...y timer identification and management Terminal clamp left open when delivered screw terminal type Finger protection terminal block to meet VDE0106 P100 Enables easy sequence checks through instantaneous outputs for a zero set value at any time range Incorporates environment friendly cadmium free contacts Conforms to EN61812 1 and IEC60664 1 4 kV 2 for Low Voltage and EMC Directives Broad Line up o...

Page 2: ...B 10 Solid state Timer H3DS ...

Page 3: ...y B Flicker OFF start B2 Flicker ON start C Signal ON OFF delay D SIgnal OFF delay E Interval G Signal ON OFF delay J One shot 1 2 3 H3DS L 1 M Multi function type S Standard type A Single function type 2 L Smart lock mechanism 3 None Screw terminal type C Screw Less Clamp type Supply voltage Control output Input type Operating mode see note Model Screwterminal type Screw Less Clamp type 24 to 230...

Page 4: ...d state Multi functional Timer H3DS M S A Accessories Order Separately Lock Key Y92S 38 Mounting Track 50 cm l x 7 3 mm t PFP 50N 1 m l x 7 3 mm t PFP 100N 1 m l x 16 mm t PFP 100N2 End Plate PFP M Spacer PEP S ...

Page 5: ...out sleeves Screw Less Clamp type Clamps two 1 5 mm2 max bar terminals without sleeves Terminal screw tightening torque 0 98 N m max Mounting method DIN track mounting see note Attachment Nameplate label Approved standards UL508 CSA C22 2 No 14 Conforms to EN61812 1 IEC60664 1 4 kV 2 VDE0106 P100 Output category according to IEC60947 5 1 AC 13 250 V 5 A AC 14 250 V 1 A AC 15 250 V 1 A DC 13 30 V 0...

Page 6: ...alfunction 100 m s2 3 times each in 6 directions Destruction 1 000 m s2 3 times each in 6 directions Impulse withstand voltage 3 kV between power terminals 4 5 kV between current carrying metal parts and exposed non current carrying metal parts Noise immunity Square wave noise generated by noise simulator pulse width 100 ns 1 µs 1 ns rise 1 5 kV Static immunity Malfunction 4 kV Destruction 8 kV Li...

Page 7: ... Operating mode selector H3DS SL AL AC DC input Zero setting detection circuit Time scale unit selectors Power supply circuit Oscillation circuit Counting circuit Power ON indicator Output indicator Indicator circuit Output circuit Operating mode selector Item H3DS ML H3DS SL AL Input Start Starts operation No input is available Output Control output Outputs are turned ON according to designated o...

Page 8: ...to PNP output sensor No contact Input Connection to NPN output sensor Contact Input Sensor Sensor Operates with PNP transistor ON Operates with NPN transistor ON Operates with relay ON Timer Timer Timer 24 VDC 24 VDC B1 Start B1 Start Voltage Input Signal Levels No contact input 1 Transistor ON Residual voltage 1 V max Voltage between terminals B1 and A2 must be more than the rated H level voltage...

Page 9: ... In order of appearance Note Letters that appear more than once indicate exactly the same operating mode Selection of Time Scale The time scale is selected by turning the time scale selector The time scales will appear in the following order in the time scale display window on the left of the selector 1 s 0 1 s 1 h 0 1 h 10 h 1 h 1 m 0 1 m Note The time scale 1h appears twice Both instances indica...

Page 10: ...nt the power is turned on Start input is invalid while the Timer is in opera tion Start Output Basic operation t t Power A1 and A2 Power indicator t t t a t a Basic operation Power Output For power on operation impose voltage to the Start input The Timer starts operating at the moment the power is turned on Start input is invalid while the Timer is in opera tion Start t t t t t t t Start B1 and A2...

Page 11: ...operating at the moment the power is turned on Start input is valid and re triggerable while the Timer is in operation Start t Power indicator Start B1 and A2 see note Output relay NC 15 and 16 Output relay NO output indicator 15 and 18 Power A1 and A2 Power indicator t t t t a t a t a Basic operation Power Output Start input is valid and re triggerable while the Timer is in operation Start t t t ...

Page 12: ... enclosed label here as a nameplate The label is attached to the Timer s DIN Track hook section at the time of shipment Time setting dial set time Lock for time setting dial Lock for time scale selector Lock for operating mode selector Wire connection holes Release holes Wire connection holes Wire connection holes Release holes Wire connection holes Power ON indicator green Lit while the power is ...

Page 13: ...ate Multi functional Timer H3DS M S A B 21 Timers Dimensions Note All units are in millimeters unless otherwise indicated 17 5 73 45 80 44 68 H3DS ML SL AL Surface color Light gray 5Y7 1 OMRON H3DS MLC SLC ALC ...

Page 14: ...B 22 Solid state Multi functional Timer H3DS M S A ...

Page 15: ...ings Model Number Structure Model Number Legend Ordering Information List of Models Accessories Order Separately 1 2 3 H3DS F L 1 F Twin timers 2 L Smart lock mechanism 3 None Screw terminal type C Screw Less Clamp type Operating mode Supply voltage Model Screw terminal type Screw Less Clamp type Flicker OFF Flicker ON start 24 to 230 VAC 50 60 Hz 24 to 48 VDC H3DS FL H3DS FLC Lock Key Y92S 38 Mou...

Page 16: ...AC 13 250 V 5A AC 15 250 V 1 A DC 13 30 V 0 1 A Time scale display Time range 0 1 s 0 1 to 1 2 s 1 s 1 to 12 s 0 1 m 0 1 to 1 2 min 1 m 1 to 12 min 0 1 h 0 1 to 1 2 h 1 h 1 to 12 h Rated supply voltage See note 24 to 230 VAC 50 60 Hz 24 to 48 VDC Operating voltage range 85 to 110 of rated supply voltage Power reset Minimum power off time 0 1 s Reset voltage 2 4 VAC DC max Power consumption AC 33 V...

Page 17: ...Noise immunity Square wave noise generated by noise simulator pulse width 100 ns 1 µs 1 ns rise 1 5 kV Static immunity Malfunction 4 kV Destruction 8 kV Vibration resistance Malfunction 0 5 mm single amplitude at 10 to 55 Hz Destruction 0 75 mm single amplitude at 10 to 55 Hz Shock resistance Malfunction 200 m s2 3 times each in 6 directions Destruction 300 m s2 3 times each in 6 directions Life e...

Page 18: ...e 2 DC supply voltage does not require the designation of polarity AC DC input ON indicator Orange OFF indicator Green ON OFF start selector Indicator circuit One chip microcomputer ROM RAM Clock Time scale selector Output circuit Power supply circuit Inputs Flicker ON start operation begins when inputs are turned ON Outputs Control output Outputs are turned ON OFF according to the time set by the...

Page 19: ...ime Locking Unlocking of Selectors and Time Setting Dial The ON OFF time setting dials and time scale selectors can be locked using the Y92S 38 Lock Key a special pen type tool that is sold separately To lock the dials or selectors insert the Lock Key in the keyhole to the lower right of the dial or selector and turn it clock wise until the dial or selector is completely covered with the red cover...

Page 20: ...range When the output is OFF Green ON time setting dial Lock for ON time setting dial Lock for ON time scale selector OFF time setting dial Lock for OFF time setting dial Lock for OFF time scale selector Attach the enclosed label here as a nameplate The label is attached to the Timer s DIN Track hook section at the time of shipment Wire connection holes Wire connection holes Release holes OFF time...

Page 21: ...Solid state Twin Timer H3DS F B 29 Timers Dimensions 17 5 17 5 73 73 45 45 80 80 44 44 68 68 H3DS FL H3DS FLC Surface color Light gray 5Y7 1 OMRON Surface color Light gray 5Y7 1 OMRON ...

Page 22: ...B 30 Solid state Twin Timer H3DS F ...

Page 23: ...t of Models Accessories Order Separately 1 2 3 H3DS G L 1 G Star delta timer 2 L Smart lock mechanism 3 None Screw terminal type C Screw Less Clamp type Operating mode Supply voltage Model Screw terminal type Screw Less Clamp type Star delta operation 24 to 230 VAC 50 60 Hz 24 to 48 VDC H3DS GL H3DS GLC Lock Key Y92S 38 Mounting Track 50 cm l x 7 3 mm t PFP 50N 1 m l x 7 3 mm t PFP 100N 1 m l x 16...

Page 24: ...08 CSA C22 2 No 14 Conforms to EN61812 1 IEC60664 1 4 kV 2 VDE0106 P100 Output category according to IEC60947 5 1 AC 13 250 V 5A AC 15 250 V 1 A DC 13 30 V 0 1 A Time scale Star operation time ranges x 1 1 to 12 s x 10 10 to 120 s Star delta transfer time Programmable at 0 05 s 0 1 s 0 5 s or 1 s Rated supply voltage see note 24 to 230 VAC 50 60 Hz 24 to 48 VDC Operating voltage range 85 to 110 of...

Page 25: ...Square wave noise generated by noise simulator pulse width 100 ns 1 µs 1 ns rise 1 5 kV Static immunity Malfunction 4 kV Destruction 8 kV Vibration resistance Malfunction 0 5 mm single amplitude at 10 to 55 Hz Destruction 0 75 mm single amplitude at 10 to 55 Hz Shock resistance Malfunction 200 m s2 3 times each in 6 directions Destruction 300 m s2 3 times each in 6 directions Life expectancy Mecha...

Page 26: ...Delta operation indicator Star operation Delta operation Star opera tion time oscillation circuit Star opera tion time counting circuit Star delta transfer time oscilla tion circuit Star delta transfer time counting circuit Star delta transfer time selection Inputs Outputs Control output Star output is turned OFF when the dial set value is reached and delta output is ON after the preset transfer t...

Page 27: ...operation time scale is x10 Refer to the example below Time Setting The star operation time of the Timer is set with the time setting dial Locking Unlocking of Selectors and Time Setting Dial The time setting dial and time scale selector can be locked using the Y92S 38 Lock Key a special pen type tool that is sold separately To lock the dial or selectors insert the Lock Key in the keyhole to the l...

Page 28: ...time setting dial Time setting dial for setting star operation time Lock for star delta transfer time and star operation time scale Attach the enclosed label here as a nameplate The label is attached to the Timer s DIN Track hook section at the time of shipment Star operation indicator green Front View Front View Star delta transfer time and star operation time scale display window and selector ...

Page 29: ...Solid state Star delta Timer H3DS G B 37 Timers Dimensions 17 5 73 45 80 44 68 H3DS GL Surface color Light gray 5Y7 1 OMRON 17 5 73 45 44 68 80 H3DS GLC Surface color Light gray 5Y7 1 OMRON ...

Page 30: ...B 38 Solid state Star delta Timer H3DS G ...

Page 31: ...Order Separately 1 2 3 H3DS X L 1 X Two wired timer 2 L Smart lock mechanism 3 None Screw terminal type C Screw Less Clamp type Supply voltage Input type Operating mode Model Screw terminal type Screw Less Clamp type 24 to 230 VAC VDC 50 60 Hz No input available ON delay H3DS XL H3DS XLC Lock Key Y92S 38 Mounting Track 50 cm l x 7 3 mm t PFP 50N 1 m l x 7 3 mm t PFP 100N 1 m l x 16 mm t PFP 100N2 ...

Page 32: ...1 5 mm2 max bar terminals without sleeves Terminal screw tightening torque 0 98 N m max Mounting method DIN track mounting see note Attachment Nameplate label Approved standards UL508 CSA C22 2 No 14 Conforms to EN61812 1 IEC60664 1 4 kV 2 VDE0106 P100 Time scale display Time range 0 1 s 0 1 to 1 2 s 1 s 1 to 12 s 0 1 m 0 1 to 1 2 min 1 m 1 to 12 min 0 1 h 0 1 to 1 2 h 1 h 1 to 12 h 10 h 10 to 120...

Page 33: ...e amplitude at 10 to 55 Hz Destruction 0 75 mm single amplitude at 10 to 55 Hz Shock resistance Malfunction 200 m s2 3 times each in 6 directions Destruction 300 m s2 3 times each in 6 directions EMC EMI EN61812 1 Emission Enclosure EN55011 Group 1 class B Emission AC Mains EN55011 Group 1 class B Harmonic Current EN61000 3 2 Voltage Fluctuation and Flickering EN61000 3 3 EMS EN61812 1 Immunity ES...

Page 34: ...ng the time scale selector The time scales will appear in the following order in the time scale display window on the left of the selector 1 s 0 1 s 1 h 0 1 h 10 h 1 h 1 m 0 1 m Note The time scale 1h appears twice Both instances indicate ex actly the same time scale Locking Unlocking of Selectors and Time Setting Dial The time setting dial and time scale selector can be locked using the Y92S 38 L...

Page 35: ...ew Time setting dial set time Lock for time setting dial Wire connection holes Release holes Wire connection holes Lock for time scale selector Power ON indicator green Lit while the power is ON Attach the enclosed label here as a nameplate The label is attached to the Timer s DIN Track hook section at the time of shipment Time scale display window and selector select one from 1 s 0 1 s 1 h 0 1 h ...

Page 36: ...B 44 Solid state Two wired Timer H3DS X Dimensions 17 5 73 45 80 44 68 H3DS XL H3DS XLC Surface color Light gray 5Y7 1 OMRON ...

Page 37: ...2 AWG24 to AWG16 Applicable Wire Type Solid wires stranded wires flexible wires or wires with ferules can be used See note 1 1 8 Diameter D mm 3 0 see note 2 Conductor diameter d mm or length of sides a and b mm 1 6 Note 1 If the overall diameter of the wire is less than 1 8 mm do not insert the wire past the conductor Refer to the following di agrams 2 If the overall diameter of the wire is over ...

Page 38: ...re connection hole 3 Pull out the screwdriver Precautions Always insert the screwdriver straight into the hole never at an angle The clamp spring may be deformed if the screwdriver is not straight Do not move the screwdriver side to side in the clamp hole The clamp spring may be deformed if the screwdriver is moved sideways 6 to 7 mm Fig 1 Exposed Conductor Length A A Wire connection holes Release...

Page 39: ... 4 5 15 50 11 5 10 10 6 2 1 8 1 8 1 3 4 8 35 5 35 5 5 44 3 34 8 16 5 16 12 25 10 15 15 25 25 25 25 10 1 000 10 10 25 1 000 500 25 25 4 5 15 5 1 1 1 1 5 27 16 24 29 2 7 3 0 15 35 0 3 35 0 3 27 0 15 Mounting Track PFP 100N PFP 50N PFP 100N2 M4 x 8 pan head screw see note End Plate PFP M Spacer PFP S see note Note The values shown in parentheses are for the PFP 50N ...

Page 40: ... and secondary windings are mutually isolated and the secondary winding is not grounded Installation If the load current is continuously being supplied to the Timer for a long period of time be sure to provide the mounting clearance as shown in the figure below If used under the conditions other than those specified below except for the H3DS XL the life of internal components may be shortened due ...

Page 41: ...e the Timer wiring and the equipment which generates the input signals as far as possible from the noise sources It is also recom mended to shield the input signal wiring to prevent electronic interfer ence Organic solvents such as paint thinner as well as very acidic or basic solutions can damage the outer casing of the Timer Do not use the Timer in places where it is exposed to dust corrosive ga...

Page 42: ...erest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No L098 E1 05 ...

Reviews: