H3CR-H
H3CR-H
38
Ratings
Rated supply voltage (see note 1)
100 to 120 VAC (50/60 Hz), 200 to 240 VAC (50/60 Hz), 24 VAC/VDC (50/60 Hz), 48 VDC,
100 to 125 VDC
Operating voltage range
85% to 110% of rated supply voltage
No-voltage input (see note 2)
ON-impedance:
1 k
Ω
max.
ON residual voltage: 1 V max.
OFF impedance:
500 k
Ω
min.
Power consumption
100 to 120 VAC:
approx. 0.23 VA (0.22 W) at 120 VAC
200 to 240 VAC:
approx. 0.35 VA (0.3 W) at 240 VAC
24 VAC/DC:
approx. 0.17 VA (0.15 W) at 24 VAC
approx. 0.1 W at 24 VDC
48 VDC:
approx. 0.18 W at 48 VDC
100 to 125 VDC:
approx. 0.5 W at 125 VDC
Control outputs
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos
φ
= 1)
Note:
1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2. For contact input, use contacts which can adequately switch 0.1 mA at 5 V.
Characteristics
Accuracy of operating
time
±
0.2% FS max. (
±
0.2% FS
±
10 ms max. in ranges of 0.6 and 1.2 s)
Setting error
±
5% FS
±
50 ms max.
Operation start voltage
30 % max. of rated voltage
Influence of voltage
±
0.2% FS max. (
±
0.2% FS
±
10 ms max. in ranges of 0.6 and 1.2 s)
Influence of
temperature
±
1% FS max. (
±
1% FS
±
10 ms max. in ranges of 0.6 and 1.2 s)
Insulation resistance
100 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying
metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
Impulse withstand
voltage
3 kV (between power terminals) for 100 to 120 VAC, 200 to 240 VAC, 100 to 125 VDC;
1 kV for 24 VAC/DC, 48 VDC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 120
VAC, 200 to 240 VAC, 100 to 125 VDC;
1.5 kV for 24 VAC/DC, 48 VDC
Noise immunity
±
1.5 kV (between power terminals) and
±
600 V (between input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1
m
s, 1-ns rise);
±
1 kV (between power terminals) for 48 VDC
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction:10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction:10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Shock resistance
Destruction: 980 m/s
2
three times each in six directions
Malfunction: 98 m/s
2
three times each in six directions
Ambient temperature
Operating:–10
°
C to 55
°
C (with no icing)
Storage: –25
°
C to 65
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Life expectancy
Mechanical:10 million operations min. (under no load at 1,200 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,200 operations/h)
EMC
(EMI)
EN61812-1
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
(EMS)
EN61812-1
Immunity ESD:
IEC61000-4-2:
6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
IEC61000-4-3:10 V/m (80 MHz to 1 GHz)
(level 3)
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3:10 V/m (900
±
5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
IEC61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge:
IEC61000-4-5:
1 kV line to line
2 kV line to ground (level 3)
Case color
Light Gray (Munsell 5Y7/1)
Enclosure ratings
IP40 (panel surface)
Weight
Approx. 120 g