PTM-300U Quick Set-up Guide

This guide is to provide basic instructions on how to quickly get started 

and configure the

PTM-300U

Series Pulse Timing Module.

To configure the PTM-300U:

1. Hold the 

2

button for 

½

second. (selection flashes)

2. Use the 

6

and

5

buttons to change 

TIMING FUNCTION

,

3. Press the 

button to accept and advance to 

I/O FUNCTION

.

4. Use the 

6

and

5

buttons to change,

5. Press the 

button to accept and advance to 

TIMING VALUE

.

6. Use the 

6

and

5

buttons to change,

7. Press the 

button to accept 

TIMING VALUE 

and exit configuration (resumes normal operation).

(refer to PTM-Series Data Sheet for more detailed information)

TIMING FUNCTION

STRTCH

- Defines a (TIMING VALUE

3

) output pulse length. 

> Typical use: to lengthen or shorten a pulse. [same as INTRVL]

EXTEND

- Adds (TIMING VALUE

3

) to the OFF-edge.

> Typical use: to extend a pulse. [same as DLYOFF]

MOTION

- Retriggerable One-shot function. Time-out (for TIMING VALUE

3

) from last ON-edge.

> Typical uses: Watchdog Timer, Motion Detector, Underspeed detector.  [same as WATCHDOG]

DLY-ON

- Delay-ON (TIMING VALUE

3

). 

> Typical use: Delay-on-make (power applied)

BUFFER

- OUTPUT = INPUT (TIMING VALUE is always 000 mSec)

> Typical uses: Buffer input pulse, (can be used together with I/O FUNCTION to;
Change signal polarity [ 

H

], Debounce input for 8 mSeconds [ 

a

])

I/O FUNCTION

A - Normal Operation; Auto-detects input polarity to match same polarity output.

- Inverts Polarity; Produces compliment NPN or PNP polarity output.

N - Forces output polarity to NPN only.

P - Forces output polarity to PNP only

- Debounces input for approximately 8 milliseconds. Otherwise same as ‘A’ (above).

NOTES:

1.

IMPORTANT NOTE: Input is ignored and output is inhibited during configuration.

2.

If no button is pressed

for 5 seconds, configuration is stored and unit will resume normal operation.

3a. Minimum stored TIMING VALUE is 10 milliseconds.

3b. TIMING VALUE is adjustable in 1 mS increments from 10 to 999 mS and 100 mS from 1 to 60 Seconds.

4. On-the-fly timing adjustments may be made in ‘real-time’ using the 

6

and

5

buttons.

IMPORTANT NOTE: 

Unstored timing changes will be lost if power is lost.

(Unstored TIMING VALUES are denoted with an asterisk ‘*‘.)

5. All LED indicators indicate ‘real-time’ status.

Brentek

E N G I N E E R I N G

QuickGuide

Document No.: PTM-300U-SETUP

 

Sheet 1 OF 2

  Copyright 2007

I/O FUNCTION

TIMING FUNCTION

TIMING VALUE