G3PA-(VD)
G3PA-(VD)
145
ÉÉÉÉÉ
ÉÉÉÉÉ
Close Mounting
At a rated ambient temperature for each.
Note:
Keep a distance of 3 cm or more between the G3PA
(especially the SSR on the upper side) and the duct.
Screw or DIN track mounting is possible.
Mount horizontally to ground.
Panel
Close mounting of up to three G3PA
SSRs is possible.
Load current should be reduced by 10%
for G3PA-210B-VD, -220B-VD, -240B-
VD, and by 20% for other models.
To close mount more than three G3PA,
keep a distance of 10 mm between each
SSR.
DIN track
Panel
For vertical mounting, the load current must
be 30% lower than the rated one (refer to
Engineering Data).
DIN track
G3PA
G3PA
Keep a distance of 80 mm between
the upper SSR and the lower SSR.
Ground
Ground
Horizontal Mounting
Vertical Mounting