Solid State Relays
G3NE
J-19
SSR
■
Characteristics
Engineering Data
Load Current vs. Ambient Temperature
One Cycle Surge Current: Non-repetitive
Note:
Keep the inrush current to half the rated value if it occurs repetitively.
Item
G3NE-2
@@
T(-2)-US
G3NE-2
@@
TL(-2)-US
Operate time
1/2 of load power source cycle + 1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.6 V (RMS) max.
Leakage current
2 mA max. (at 100 VAC)
5 mA max. (at 200 VAC)
Insulation resistance
100 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 1,000 m/s
2
Ambient temperature
Operating: –30
°
C to 80
°
C (with no icing or condensation)
Storage:
–30
°
C to 100
°
C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Certified standards
UL508 File No.E64562/CSA C22.2 (No.0, No.14) File No. LR35535
TÜV R9051064 (VDE0435) (EN60950)
Weight
Approx. 37 g
G3NE-205T(L)(-2)-US
G3NE-210T(L)(-2)-US
G3NE-220T(L)(-2)-US
Ambient temperature (
°
C)
Ambient temperature (
°
C)
Ambient temperature (
°
C)
Load current (A)
Load current (A)
Load current (A)
Without heat sink
Without heat sink
Without heat sink
With standard heat sink (Y92B-N50)
or aluminum plate measuring 100 mm
x 100 mm x t2 mm (W x H x D)
With standard heat sink (Y92B-N100) or
aluminum plate measuring 300 mm x
300 mm x t3 mm (W x H x D)
G3NE-205T(L)(-2)-US
G3NE-210T(L)(-2)-US
G3NE-220T(L)(-2)-US
Inr
ush current (A.
P
eak)
Energized time (ms)
Inr
ush current (A.
P
eak)
Energized time (ms)
Inr
ush current (A.
P
eak)
Energized time (ms)