J-18
Solid State Relays
G3NE
Ordering Information
■
List of Models
Note:
When ordering, specify the input voltage.
■
Accessories (Order Separately)
Heat Sinks
The following heat sinks are thin and can be DIN-track mounted.
See
Dimensions
for details.
Specifications
■
Ratings (at an Ambient Temperature of 25
°
C)
Input
Note:
Each model has 5-VDC, 12-VDC, and 24-VDC input versions.
Output
Note: 1.
The load current varies depending on the ambient temperature. Refer to L
oad Current vs. Ambient Temperature
under
Engineering Data
for details.
2.
These values apply when using a dedicated heat sink or a radiation plate of specified size.
Isolation
Zero cross
function
Indicator
Rated output load
Rated input voltage
Model
Phototriac
Yes
No
5 A at 100 to 240 VAC
5, 12, 24 VDC
G3NE-205T-US
G3NE-205T-2-US
10 A at 100 to 240 VAC
G3NE-210T-US
G3NE-210T-2-US
20 A at 100 to 240 VAC
G3NE-220T-US
G3NE-220T-2-US
No
5 A at 100 to 240 VAC
G3NE-205TL-US
G3NE-205TL-2-US
10 A at 100 to 240 VAC
G3NE-210TL-US
G3NE-210TL-2-US
20 A at 100 to 240 VAC
G3NE-220TL-US
G3NE-220TL-2-US
Model
Applicable SSR
Y92B-N50
G3NE-205T(L)(-2)-US/-210T(L)(-2)-US
Y92B-N100
G3NE-220T(L)(-2)-US
Rated voltage
Operating voltage
Voltage level
Input impedance
Must operate
Must release
With zero cross function Without zero cross function
5 VDC
4 to 6 VDC
4 VDC max.
1 VDC min.
250
Ω±
20%
300
Ω±
20%
12 VDC
9.6 to 14.4 VDC
9.6 VDC max.
600
Ω±
20%
800
Ω±
20%
24 VDC
19.2 to 28.8 VDC
19.2 VDC max.
1.6 k
Ω±
20%
Model
Applicable load
Rated load voltage
Load voltage range
Load current
(See note 1.)
Inrush current
With heat sink
Without heat sink
G3NE-205T(L)(-2)-US
100 to 240 VAC
75 to 264 VAC
0.1 to 5 A
0.1 to 5 A
60 A (60 Hz, 1 cycle)
G3NE-210T(L)(-2)-US
0.1 to 10 A
(See note 2.)
0.1 to 5 A
150 A (60 Hz, 1 cycle)
G3NE-220T(L)(-2)-US
0.1 to 20 A
(See note 2.)
0.1 to 5 A
220 A (60 Hz, 1 cycle)