Solid State Relays

 G3NA

13

Noise Terminal Voltage According to 
EN55011

The G3NA-UTU complies with EN55011 standards when a capacitor 
is connected to the load power supply as shown in the following 
circuit diagram.

Connect capacitor C1 to both sides of the input terminals for a 
G3NA with a DC input.

Connect capacitor C2 to both sides of the load power supply 
output.

Connect the varistor to both sides of the G3NA output terminals.

Do not use an input line that is longer than 3 m.

Loss Time

The loss time will increase when the G3NA is used at a low applied 
voltage or current. Be sure that this does not cause any problems. 

Using DC Loads

For a DC or L load, a diode should be connected in parallel the load 
to absorb the counter electromotive force of the load.

Fuses

Connect a quick-break fuse in series with the load as a short-circuit 
protection measure. Use one of the fuses in the following table or 
one with equivalent or better characteristics. 

Recommended Fuses

Reverse Connection 

The output terminal side of the G3NA-D210B is connected to a built-
in diode to protect the SSR from damage that may result from 
reverse connection. The SSR, however, cannot withstand one minute 
or more if the wires are connected in reverse. Therefore, pay the 
utmost attention not to make polarity mistakes on the load side.

G3NA rated 

load current

Fuse model

Manufacturer

Applicable SSR

5 A

60LFF5

Kyosan Electric 
Manufacturing 
Company

G3NA-205B-UTU

8 A

60LFF8

G3NA-210B-UTU

10 A

60LFF10

15 A

60LFF15

G3NA-220B-UTU

20 A

60LFF20
50SHA20

25 A

60PFF25
50SHA25

G3NA-240B-UTU

30 A

60PFF30
50SHA30

G3NA-250B-
UTU

40 A

50SHA40

45 A

50SHA45

50 A

50SHA50

75 A

50SHA75

G3NA-275B-UTU

80 A

50SHA80

G3NA-290B-UTU

100 A

50SHB100

Output

Input

C1

C2

G3NA-UTU 
type

Load

Capacitor C1
0.1 

µ

F

3 m max.

Varistor

 

G3NA-2

@@

: 470 V, 0.6 W

 

G3NA-4

@@

: 910 V, 0.8 W

Capacitor C2

 

G3NA-2

@@

: 1 

µ

F, 250 VAC

 

G3NA-4

@@

: 0.5 

µ

F, 500 VAC

Loss time

SSR

Input

Load

Load power 
supply

Summary of Contents for G3NA

Page 1: ...UL CSA and T V Model Number Structure Model Number Legend 1 Basic Model Name G3NA Solid State Relay 2 Load Power Supply Blank AC output D DC output 3 Rated Load Power Supply Voltage 2 200 VAC or 200...

Page 2: ...VAC See note 5 to 24 VDC G3NA 250B UTU DC5 24 Photocoupler 100 to 120 VAC G3NA 250B UTU AC100 120 200 to 240 VAC G3NA 250B UTU AC200 240 Phototriac 75 A at 24 to 240 VAC See note 2 5 to 24 VDC G3NA 2...

Page 3: ...DC 4 to 32 VDC 15 mA max See note 2 4 VDC max 1 VDC min 100 to 240 VAC 75 to 264 VAC 72 k 20 75 VAC max 20 VAC min Model Applicable load Rated load voltage Load voltage range Load current See note 1 I...

Page 4: ...1 ms max AC input 5 ms max DC input 30 ms max AC input Output ON voltage drop 1 6 V RMS max 1 8 V RMS max 1 6 V RMS max 1 8 V RMS max 1 5 V max Leakage current 5 mA max at 100 VAC 10 mA max at 200 VA...

Page 5: ...NA 450B UTU Load current A Ambient temperature C With standard heat sink Y92B P250 Without heat sink 50 45 40 30 20 12 10 6 4 2 30 20 0 20 40 60 80 100 20 0 20 40 60 80 100 0 60 50 40 30 20 10 6 0 30...

Page 6: ...nrush current A peak G3NA 275B UTU G3NA 475B UTU G3NA 290B UTU G3NA 490B UTU 28 30 26 24 22 20 18 16 14 12 10 8 6 4 2 0 2 000 1 000 500 200 300 100 50 70 30 20 10 Energized time ms Inrush current A pe...

Page 7: ...or M4 holes Load power supply Terminal Arrangement Internal Connections Top View G3NA 275B UTU G3NA 475B UTU G3NA 290B UTU G3NA 490B UTU 16 8 47 5 44 25 8 2 12 4 5 47 6 0 2 1 2 4 3 Mounting Holes Outp...

Page 8: ...the tab with a screwdriver in the direction of the arrow R99 11 for the G3NA 240B UTU G3NA 250B UTU G3NA 450B UTU 4 6 56 21 12 5 16 8 4 5 Use Mounting Bracket R99 11 so that the G3NA 240B 250B 450B U...

Page 9: ...les 77 max 100 max 71 max 100 max 75 max Two 3 2 dia holes Mounting Holes Weight approx 400 g Two M4 holes Two 4 4 dia or M4 holes Y92B N150 Heat Sink for the G3NA 240B UTU 35 47 6 5 6 5 4 5 30 90 0 3...

Page 10: ...0B UTU G3NA 425B UTU G3NA D210B Y92B A150N Low cost Heat Sink for the G3NA 240B UTU The orientation indicated by the external dimensions is not the correct mounting orientation When opening mounting h...

Page 11: ...is caught in screw For GN3A Relays of 40 A or higher use crimp terminals of an appropriate size for the wire diameter for M5 terminals Do not use any wires with damaged sheaths These may cause electr...

Page 12: ...tach a fan to the ventilation outlet or air inlet of the control panel to ventilate the panel This will reduce the ambient temperature of the SSRs and thus increase reliability Generally each 10 C red...

Page 13: ...re Use one of the fuses in the following table or one with equivalent or better characteristics Recommended Fuses Reverse Connection The output terminal side of the G3NA D210B is connected to a built...

Page 14: ...A may malfunction and internal components may be deformed or damaged resulting in failure of the G3NA to operate To prevent the G3NA from abnormal vibration do not install the G3NA in locations or by...

Page 15: ...Solid State Relays G3NA 15...

Page 16: ...uct on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HA...

Reviews: