3-3-3
Insulation Blocks
As shown in the following diagram, each function block of the E5AR/E5ER-
DRT is electrically insulated.
The following are functionally insulated from each other: 1) each of the inputs,
2) event inputs, voltage outputs, and current outputs, and 3) communications.
The following are insulated from each other with basic insulation: 1) inputs,
event inputs, voltage outputs, current outputs, communications, 2) relay out-
put, and 3) transistor outputs.
If reinforced insulation is required, the input, event input, voltage output, cur-
rent output, and communications terminals must be connected to devices that
have no exposed chargeable parts and whose basic insulation is suitable for
the applicable maximum voltage of connected parts.
To comply with safety standards, always use an EN/IEC-compliant power
supply with reinforced insulation or double insulation for the DeviceNet power
supply.
Power supply
Input 1/potentiometer input
Reinforced insulation
Basic insulation
Functional insulation
Relay output
Transistor output
Input 2
Input 3
Input 4
Event inputs, voltage outputs,
current outputs
Communications
Summary of Contents for E5AR
Page 2: ...E5AR ER Digital Controller DeviceNet Communications User s Manual Produced February 2004...
Page 3: ...iv...
Page 29: ...2 6 Functions Supported Only by the E5AR ER DRT Section 2 2 Operating Procedures...
Page 79: ...6 8 Message Communications Performance Section 6 2 Communications Performance...
Page 91: ...B 6 Mounted Objects Appendix B Appendix B...
Page 95: ...C 4 DeviceNet Connection Hardware Appendix C Appendix C...
Page 97: ...G 2 Glossary...
Page 100: ...Index I 3 W wiring 3 10 precautions 3 9 write mode 4 12...
Page 101: ...I 4 Index...