3-16
DeviceNet Communications Cables Wiring
Section 3-3
P
a
rt
s,
In
st
al
la
-
ti
on
, a
n
d
W
ir
in
g
The colors correspond to the signal lines as follows:
• We recommend the following crimp terminals (for Thin Cables)
Power Lines: Phoenix Contact AI-series Crimp Terminals AI-0.5-6WH
(product code 3200687)
Signal Lines: Phoenix Contact AI-series Crimp Terminals AI-0.25-6BU
(product code 3201291)
The following crimp tool is also available.
Phoenix Contact ZA3 Crimp Tool
3-3-2
Attaching the DeviceNet Communications Unit Connector
Align the DeviceNet Communications Unit connector with the cable connec-
tor, and insert the cable connector fully into the DeviceNet Communications
Unit connector.
Tighten the set screws to a torque between 0.25 and 0.3 N·m to secure the
connector.
E5AR
Color
Signal
Red
Power line, positive voltage (+V)
White
Communications line, high (CAN high)
---
Shield
Blue
Communications line, low (CAN low)
Black
Communications cable, negative voltage (
−
V)
Black (
−
V)
Blue (CAN low)
Shield
White (CAN high)
Red (+V)
Crimp terminal
Line
Insert the line and crimp.
Summary of Contents for E5AR
Page 2: ...E5AR ER Digital Controller DeviceNet Communications User s Manual Produced February 2004...
Page 3: ...iv...
Page 29: ...2 6 Functions Supported Only by the E5AR ER DRT Section 2 2 Operating Procedures...
Page 79: ...6 8 Message Communications Performance Section 6 2 Communications Performance...
Page 91: ...B 6 Mounted Objects Appendix B Appendix B...
Page 95: ...C 4 DeviceNet Connection Hardware Appendix C Appendix C...
Page 97: ...G 2 Glossary...
Page 100: ...Index I 3 W wiring 3 10 precautions 3 9 write mode 4 12...
Page 101: ...I 4 Index...