Level 1 Mode
AT Execute/Cancel
Proportional Band
Available if the Controller is in 2-PID control.
Integral Time
Available if the Controller is in 2-PID control.
Derivative Time
Available if the Controller is in 2-PID control.
For heating/cooling control
For E5
j
K-PRR2
Cooling Coefficient
Used with the Controller is in
heating and cooling control.
Dead Band
Used with the Controller is in
heating and cooling control.
Manual Reset Value
Available when the integral time parameter
of the Controller in standard control is “0.”
Hysteresis (Heat)
Available when the Controller is in
ON/OFF control.
For heating/cooling control
Hysteresis (Cool)
Available when the Controller is in
ON/OFF control
Control Period (Heat)
Available when the Controller has a relay or
voltage output, or is in 2-PID control.
For heating/cooling control
Control Period (Cool)
Available when the Controller has a relay
or voltage output, or is in 2- PID control.
Current value
Heater Current Monitor
Available when the heater
burnout alarm is assigned.
Heater Burnout Detection
Available when the heater
burnout alarm is assigned.
Position-
proportional
dead band
Level 2 Mode
Remote/Local
Used for the
communications function.
LBA Detection Time
Available when the LBA (loop break
alarm) is assigned as an output.
Unavailable to the E5
j
K-PRR2.
MV at Reset
MV at PV Error
MV Upper Limit
Unavailable to the
E5
j
K-PRR2.
MV Lower Limit
Unavailable to the
E5
j
K-PRR2.
MV Change Rate Limit
Input Digital Filter
Alarm 1 Hysteresis
Available only when the alarm
output 1 is assigned.
Alarm 2 Hysteresis
Available only when the alarm
output 2 is assigned.
Alarm 3 Hysteresis
Available only when the alarm
output 3 is assigned.
Input Shift Upper Limit
Available if the input type is a
thermocouple or platinum resistance
thermometer.
Input Shift Lower Limit
Available if the input type is a
thermocouple or platinum resistance
thermometer.
(See
Input Shift)
For E5
j
K-PRR2
Open/Close Hysteresis
Standby Time
Input Shift
When temperature input is selected, scaling is not required. This is
because input is treated as the “temperature” as it is matched to the
input type. However, note that the upper- and lower-limit values of
the sensor can be shifted. For example, if both the upper- and lower-
limit values are shifted by 1.2
°
C, the process value (before shift) is
regarded as 201.2
°
C after shift when input is 200
°
C before shift.
To set the input shift, set shift values in the “input shift upper limit”
and “input shift lower limit” parameters (level 2 mode).
Temperature
Upper limit
Upper-limit compensation value
After
compensation
Before compensation
Lower limit
Lower-limit
compensation value
Input (% of full scale)