E5CK-T
E5CK-T
10
Temperature Ranges
Platinum Resistance Thermometer
Input (switch selectable)
JPt100
Pt100
Range
°
C
–199.9 to 650.0
–199.9 to 650.0
°
F
–199.9 to 999.9
–199.9 to 999.9
Resolution (
°
C/
°
F)
(main setting and alarm)
0
1
Thermocouple
Input (switch
selectable)
(see note)
K1
K2
J1
J2
T
E
L1
L2
U
N
R
S
B
W
PL
II
Range
°
C
–200
to
1,300
0.0 to
500.0
–100
to
850
0.0 to
400.0
–199.9
to
400.0
0 to
600
–100
to
850
0.0 to
400.0
–199.9
to
400.0
–200
to
1,300
0 to
1,700
0 to
1,700
100
to
1,800
0 to
2,300
0 to
1,300
°
F
–300
to
2,300
0.0 to
900.0
–100
to
1,500
0.0 to
750.0
–199.9
to
700.0
0 to
1,100
–100
to
1,500
0.0 to
750.0
–199.9
to
700.0
–300
to
2,300
0 to
3,000
0 to
3,000
300
to
3,200
0 to
4,100
0 to
2,300
Resolution
(
°
C/
°
F)
(main setting
and alarm)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Note:
Setting number is factory-set to 2 (K1).
Current/Voltage
Input (switch selectable)
Current input
Voltage input
4 to 20 mA
0 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
Range
One of following ranges depending on results of scaling
–1999 to 9999
–199.9 to 999.9
–19.99 to 99.99
–1.999 to 9.999
Resolution (
°
C/
°
F)
(main setting and alarm)
17
18
19
20
21
Specifications
Ratings
Item
100- to 240-VAC type
24-VAC/VDC type
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC/VDC, 50/60 Hz
Power consumption
15 VA
6 VA, 3.5 W
Operating voltage range
85% to 110% of rated supply voltage
Sensor input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PL
II
Platinum resistance thermometer: JPt100, Pt100
Current input:
4 to 20 mA, 0 to 20 mA
Voltage input:
1 to 5 V, 0 to 5 V, 1 to 10 V
Input impedance
Current input: 150
Ω
Voltage input: 1 M
Ω
min.
Control output
According to Output Unit (see
Output Unit Ratings and Characteristics)
Auxiliary output
SPST-NO, 3 A at 250 VAC (resistive load)
Control method
ON/OFF or 2-PID control
Setting method
Digital setting using front panel keys
Indication method
7-segment digital display and LEDs
Other functions
Standard
Manual output, heating/cooling control, SP limiter, loop burnout alarm, MV limiter, MV change
rate limiter, input digital filter, input shift, run/reset, protect functions, scaling function