background image

E3C-LDA

@

N

4

Amplifier Units

*1.

The following details apply to the input.

*

1-1.

 Input time is 25 ms (ON)/(OFF) only when (in tUnE) input is selected.

*2.

Separately purchase the E3X-CN21 Master Connector (4-conductor) when using this product as a single unit or as a master unit, or the

 E3X-CN22 Slave Connector (2-conductor) when using as a slave unit. Either Connector can be used.

*3.

The tuning will not change the number of units. In standard mode and giga mode, set the threshold value to 400 or more. 

Model

NPN output

E3C-LDA21N

E3C-LDA6N

E3C-LDA7N

PNP output

E3C-LDA51N

E3C-LDA8N

E3C-LDA9N

Connection method 

*

2

Pre-wired

Wire-saving Connector

Applicable Amplifier Unit

E3C-L

@@@

N

Outputs

2 outputs

2 outputs

1 output

External input

 

*

1

1 input

---

1 input

Supply voltage

12 to 24 VDC ±10%, ripple (p-p) 10% max.

Power consumption

Power consumption: 1080 mW max. (when the power supply voltage is 24 V, the current consumption is 45 mA max.)

Control output

Load power supply voltage: 26.4 VDC, open collector output type (depends on the NPN/PNP output format)
Load current: 100 mA max. for 1 to 3 units use, 20 mA max. for 4 or more units joined.
Residual voltage: Load current less than 10 mA: 1 V max., load current 10 to 100 mA: 2 V max.
Off-state current: 0.1 mA max.

Indicators

7-segment displays (Threshold Level display: green, Incident Light Level display: white)
Display direction: Switchable between normal and reversed.
OUT indicator (orange), L/D indicator (orange), ST indicator (blue), DPC indicator (green), 
and OUT selection indicator (orange, only on models with 2 outputs)

Protection circuits

Power supply reverse polarity protection, output short-circuit protection, and output reverse polarity protection

Response 
time

Super-high-speed 
mode (SHS)

Operate or reset: 80 µs

High-speed mode (HS)

Operate or reset: 250 µs

Standard mode (Stnd)

Operate or reset: 1 ms

Giga mode (GIGA)

Operate or reset: 4 ms

Sensitivity adjustment

Smart Tuning (2-point tuning, full auto tuning, power tuning, percentage tuning) or manual adjustment

Maximum connectable Units

16

No. of Units 
for mutual 
interference 
prevention 

*

3

Super High-speed 
Mode (SHS)

0

Note:

The mutual interference prevention function is disabled when the detection mode is set to High Speed mode (SHS).

High-speed Mode (HS)

10

Standard Mode (Stnd)

10

Giga Mode (GIGA)

10

Functions

Dynamic power 
control (DPC)

Provided

Timer

Select from timer disabled, OFF-delay, ON-delay or one-shot timer. 1 to 9,999 ms

Zero reset

Negative values can be displayed. (Threshold value is shifted.)

Resetting settings

Initial reset (factory defaults)

Power tuning

Select from ON or OFF.

Output 1

Select from normal detection mode or area detection mode.

Output 2

Select from normal detection mode, alarm output mode or error output mode.

---

External input

Select from input OFF, tuning, power 
tuning, emission OFF or zero reset.

---

Select from input OFF, tuning, power 
tuning, emission OFF or zero reset.

Hysteresis width

Select from standard setting or user setting.

Ambient temperature range

Operating: Groups of 1 or 2 Amplifier Units: -25 to 55°C, Groups of 3 to 10 Amplifier Units: -25 to 50°C, 

Groups of 11 to 16 Amplifier Units: -25 to 45°C

Storage: -30 to 70°C (with no icing or condensation)

Ambient humidity range

Operating and storage: 35 to 85% (with no condensation) within the surrounding air temperature range shown above

Altitude

2000 m max.

Installation environment

Pollution degree 3 (as per IEC 60947-1)

Insulation resistance

20 M

Ω

 (at 500 VDC)

Dielectric strength

1,000 VAC at 50/60 Hz for 1 min

Vibration resistance (destruction)

10 to 55 Hz with a 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions

Shock resistance (destruction)

500 m/s

for 3 times each in X, Y, and Z directions

Weight (packed state/sensor only)

Approx. 115 g/approx. 75 g

Approx. 60 g/approx. 20 g

Materials

Case

Polycarbonate (PC)

Protective cover

Polycarbonate (PC)

Cable

PVC

Accessories

Instruction manual, compliance sheet

Contact input (relay or switch)

Non-contact input (transistor)

Input time 

*

1-1

NPN

ON: Shorted to 0 V (Sourcing current: 1 mA max.)

ON: 1.5 V max. (Sourcing current: 1 mA max.)

ON: 9 ms min.
OFF: 20 ms min.

OFF: Open or shorted to Vcc

OFF: Vcc - 1.5 V to Vcc (Leakage current: 0.1 mA max.)

PNP

ON: Shorted to Vcc (Sinking current: 3 mA max.)

ON: Vcc - 1.5 V to Vcc (Sinking current: 3 mA max.)

OFF: Open or shorted to 0 V

OFF: 1.5 V max. (Leakage current: 0.1 mA max.)

Summary of Contents for E3C-LDA-N Series

Page 1: ...ight from the workpiece Coaxial Optical System Sensing distance of 7 m Sensing distance of 1 m At 1 m Minimum spot diameter of 0 8 mm Optical axis alignment range Approximately r1 to1 5q Spot Line and...

Page 2: ...e for details Use a standard model E39 R12 R13 if the distance from the Sensor is 400 mm or more Use the short distance model E39 R14 if the distance is less than 400 mm Sensing method Appearance Beam...

Page 3: ...mm 2 m 700 mm 400 mm 2 m Standard Mode Stnd 30 to 700 mm 5 m 1 300 mm 700 mm 5 m Giga Mode GIGA 30 to 1000 mm 7 m 1 700 mm 900 mm 7 m Focus 3 0 8 mm max at distances up to 300 mm 33 mm at 150 mm 33 1...

Page 4: ...evention 3 Super High speed Mode SHS 0 Note The mutual interference prevention function is disabled when the detection mode is set to High Speed mode SHS High speed Mode HS 10 Standard Mode Stnd 10 Gi...

Page 5: ...on 220 200 180 160 140 120 100 80 60 40 20 0 FOCUS control turned all the way to right FOCUS control turned to center FOCUS control turned all the way to left 100 300 200 500 400 600 900 700 800 1000...

Page 6: ...ncident light Lit Not lit ON OFF Operate Reset OUT indicator orange Output transistor Load e g relay Between brown and black leads lit L Load OUT indicator orange Display Photoelectric sensor main cir...

Page 7: ...ight Lit Not lit ON OFF Operate Reset OUT indicator orange Output transistor Load e g relay Between blue and black leads lit L 12 to 24 VDC Load Brown Black Orange Blue OUT indicator orange Display Ph...

Page 8: ...ning is in progress Performs tuning and ST Indicator turns ON Threshold Level Green digital display Incident Level White digital display UP DOWN Button Used to fine tune the threshold MODE Button Swit...

Page 9: ...rew with 60 mN m or less to avoid a risk of damage or fire 9 When disposing of the product treat as industrial waste 10 If you notice an abnormal condition such as a strange odor extreme heating of th...

Page 10: ...nges when the angle is adjusted adjust the focus again Shortening the Connection Cable 1 Removing the Connector Using a flat blade screwdriver press the lever in the opening next to the cable and then...

Page 11: ...ified as a class II laser by the FDA and it has already been registered with the CDRH Center for Devices and Radiological Health Ask your OMRON representative for details Laser Labels Technical standa...

Page 12: ...outdoors 17 If you notice any abnormal condition immediately stop using the product turn off the power and consult your dealer without doing any operation such as initialization 18 Sensor heads other...

Page 13: ...e catch the track 2 Push the unit until the hook clicks into place Removing from DIN Track 1 Push the unit in the direction 1 2 Lift the unit in the direction of arrow 2 while performing step 1 Do not...

Page 14: ...8 8 4 3 7 4 75 Emitter 6 Receiver 27 3 1 18 8 20 5 1 27 7 33 33 R4 8 Two 3 2 dia holes Two R2 6 6 5 18 8 0 1 25 25 Two M3 5 1 0 1 Mounting Holes Two R2 6 1 4 1 LD ON indicator Operation indicator Opti...

Page 15: ...2 13 2 4 4 Mounting Holes 18 8 0 1 Two R2 6 6 9 2 1 3 6 1 3 1 34 18 8 21 9 25 25 6 LD ON indicator Operation indicator Optical axis alignment screw FOCUS Adjustment Screw E3C LR11N only 6 6 12 1 3 di...

Page 16: ...f conductor 0 2 mm2 Insulator dia 0 9 mm Standard length 2 m Side B 12 7 114 114 max value with Protective cover open 19 2 170 max value with Protective cover open 16 3 4 4 4 5 3 9 41 5 167 8 167 8 ma...

Page 17: ...ver open 16 3 4 4 4 5 3 9 41 5 167 8 167 8 max value with Protective cover open Two M3 16 Mounting Holes 30 2 32 1 37 33 5 33 5 3 4 4 2 5 2 6 9 3 4 0 25 4 9 2 6 36 7 57 7 83 4 83 4 27 8 30 9 27 1 32 1...

Page 18: ...h 4 conductors Standard cable length 2 m Conductor cross section 0 2 mm2 AWG24 Insulator diameter 1 1 mm 0 Master Connector E3X CN21 7 Cable Cable 4 dia cable with 2 conductors Standard cable length 2...

Page 19: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 20: ...7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron com Kyoto JAPAN OMRON ASIA PA...

Reviews: