D-106

Inductive Sensors

Effects of Surrounding Metal

Shielded types:

Shielded types allow direct installation on metal plates in an em-
bedded manner without performance change. A minimum dis-
tance of 3sn is required between the active surface and a metallic 
surface in front of the device. (Fig. 1).
For SUS shielded types the following minimum distances are re-
quired to avoid performance change (see Fig.2 and table below):

 

Fig.1: Shielded type (except SUS)

Fig.2: Shielded SUS type

Non-shielded types:

Installation of non-shielded types in metal require the minimum 
distances according to Fig. 3.

Fig.3: Non-shielded type

Item

Examples

Item

AND (serial connection)

The Sensors connected together must satisfy the 
following conditions: 
iL + (N-1) x i = Upper-limit of control output of each 

Sensor

VS - N x VR = Load operating voltage
N =

No. of Sensors

VR =

Residual voltage of each Sensor

VS =

Supply voltage

i = 

Current consumption of the Sensor

iL = 

Load current

If the MY Relay, which operate at 24 VDC, is used as a 
load for example, a maximum of two Proximity Sensors 
can be connected to the load.

OR (parallel connection)

The number of Sensors connected in parallel varies 
with the Proximity Sensor model.

Shielded SUS Types

Free zone

E2EL-2

@

-DS

0,5 mm

3s

n

3s

n

Freezone

d

3s

n

2s

n

3d

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. 

D06E-EN-01

F502-EN2-04.book  Seite 106  Dienstag, 26. Juli 2005  5:48 17

Summary of Contents for E2EL

Page 1: ...L C2F1 DS 2M E2EL C2F2 DS 2M 45 mm Shielded 2 0 mm E2EL C2E1 DSL 2M E2EL C2E2 DSL 2M E2EL C2F1 DSL 2M E2EL C2F2 DSL 2M M8 30 mm Shielded 2 0 mm E2EL X2E1 DS 2M E2EL X2E2 DS 2M E2EL X2F1 DS 2M E2EL X2F2 DS 2M 45 mm Shielded 2 0 mm E2EL X2E1 DSL 2M E2EL X2E2 DSL 2M E2EL X2F1 DSL 2M E2EL X2F2 DSL 2M Diameter Length Mounting Sensing Distance Output NPN NO NPN NC PNP NO PNP NC Ø 6 5 Plug M8 45 mm Shiel...

Page 2: ... load current and with 2 m cable Circuit protection Reverse polarity output short circuit Indicator Operating indicator yellow LED Ambient temperature Operating 25 to 70 C Humidity 35 to 95 RH Influence of temperature 10 max of Sn at 23 C in temperature range of 25 to 70 C Dielectric strength 1 500 VAC 50 60 Hz for 1 min between current carry parts and case Electromagnetic compatibility EMC EN 609...

Page 3: ...Circuit protection Reverse polarity output short circuit Indicator Operating indicator yellow LED Ambient temperature Operating 25 to 70 C Humidity 35 to 95 RH Influence of temperature 10 max of Sn at 23 C in temperature range of 25 to 70 C Dielectric strength 1 500 VAC 50 60 Hz for 1 min between current carry parts and case Electromagnetic compatibility EMC EN 60947 5 2 Vibration resistance Destr...

Page 4: ...curve switch off curve axial distance related to effective operating distance s s r on E2EL E NPN Output E2EL F PNP Output Main circuit Brown 1 Blue 3 Load Black 4 or 2 Blue 3 Load Black 4 or 2 Brown 1 0 V Main circuit 4 7 kW 4 7 kW Sensing object Yellow indicator Control output Yes No ON OFF Lit Not lit NO NC E2EL E NPN Output Sensing object Yellow indicator Control output Yes No ON OFF Lit Not l...

Page 5: ...103 E2EL E2EL Dimensions Cable types E2EL C1 R5 2M E2EL C2 DS 2M E2EL C2M 2M E2EL C1R5 L 2M E2EL C2 DSL 2M E2EL C2M L 2M E2EL X1R5 2M E2EL X2 DS 2M E2EL X2M 2M E2EL X1R5 L 2M E2EL X2 DSL 2M E2EL X2M L 2M ...

Page 6: ... 104 Inductive Sensors Plug types E2EL C1R5 M3 E2EL C2M M3 E2EL C1R5 M3L E2EL C2M M3L E2EL X1R5 M3 E2EL X2M M3 E2EL X1R5 M3L E2EL X2 DM3S E2EL X2M M3L E2EL X1R5 M1 E2EL X2M M1 E2EL X1R5 M1L E2EL X2M M1L ...

Page 7: ... Mounting The Proximity Sensor must not be subjected to excessive shock with a ha mmer when it is installed otherwise the Proximity Sen sor may be damaged or lose the water resistivity Environment Water Resistivity Do not use the Proximity Sensor underwater outdoors or in the rain Operating Environment Be sure to use the Proximity Sensor within operating ambient temperature range and do not use th...

Page 8: ... The Sensors connected together must satisfy the following conditions iL N 1 x i Upper limit of control output of each Sensor VS N x VR Load operating voltage N No of Sensors VR Residual voltage of each Sensor VS Supply voltage i Current consumption of the Sensor iL Load current If the MY Relay which operate at 24 VDC is used as a load for example a maximum of two Proximity Sensors can be connecte...

Reviews: