Proximity Sensors Technical Guide

Note: When AND/OR connections are used with Proximity Sensors, the effects of erroneous pulses or leakage current may prevent use. Verify that there are no 

problems before use.

Extending Cable Length

The cable of a Built-in Amplifier Sensor can be extended to a 
maximum length of 200 m with each of the standard cables 
(excluding some models).
For Separate Amplifier Sensors (E2C-EDA, E2C, E2J, E2CY), refer 
to the specific precautions for individual products.

Bending the Cable

If you need to bend the cable, we recommend a bend radius that is at 
least 3 times the outer diameter of the cable (with the exception of 
coaxial and shielded cables).

Cable Tensile Strength

In general, do not subject the cable to a tension greater than that 
indicated in the following table.

Note: Do not subject a shielded cable or coaxial cable to tension.

Separating High-voltage Lines

Using Metal Conduits
If a power line is to be located near the Proximity Sensor cable, use a 
separate metal conduit to prevent malfunction or damage. (Same for 
DC models.)

Example of Connection with S3D2 Sensor Controller

Using the S3D2 Sensor Controller

Connecting to a Relay Load

Note: DC 2-Wire Sensors have a residual voltage of 3 V. Check the operating 

voltage of the relay before use. 
The residual voltage of the E2E-XD-M1J-T is 5 V.

Model

Type of 

connection

Connection

Description

DC 3-wire

AND (series 
connection)

Keep the number of connected Sensors (N) within the range of the following 
equation.
iL + (N - 1) 

×

 i 

 Upper limit of Proximity Sensor control output

V

S

 - N 

×

 V

R

 Operating load voltage

Note: When an AND circuit is connected, the operation of Proximity Sensor B 

causes power to be supplied to Proximity Sensor A, and thus erroneous 
pulses (approximately 1 ms) may be generated in A when the power is 
turned ON. For this reason, take care when the load has a high 
response speed because malfunction may result.

OR (parallel 
connection)

For Sensors with a current output, a minimum of three OR connections is pos-
sible. Whether or not four or more connections is possible depends on the 
model.

(B)

(A)

Vs

i

+

+

OUT

OUT

-

-

iL

i

Load

Example: A maximum of two 
Sensors can be used when an 
MY (24-VDC) Relay is used for 
the load.

N : Number of Sensors that can be con-

nected

V

R

: Residual output voltage of Sensor

V

S

: Power supply voltage

i : Current consumption of Sensor
iL: Load current

-

OUT

OUT

-

+

+

Vs

Load

Cable diameter

Tensile strength

Less than 4 mm

30 N max.

4 mm min.

50 N max.

DC 2-Wire Sensors

DC 3-Wire Sensors

5

2

4

1

6

3

11

8

10

7

12

9

Brown OUT

Blue 0 V

S3D2

Operation can be reversed with the signal input 
switch on the S3D2.

Blue

Brown

24 VDC

X

5

2

4

1

6

3

11

8

10

7

12

9

Black OUT

Blue 0 V

Brown +12 V

S3D2

Operation can be reversed with the signal input 
switch on the S3D2.

http://www.ia.omron.com/

C-7

(c)Copyright OMRON Corporation 2007   All Rights Reserved. 

Summary of Contents for E2EC -

Page 1: ...e also available The model numbers are E2EC 5 example E2EC CR8D15 DC 3 Wire Models Models with different frequencies are also available The model numbers are E2EC 5 example E2EC CR5D15 Accessories Ord...

Page 2: ...proaching D1 Models NO D2 Models NC Refer to the timing charts under I O Circuit Diagrams on page 5 for details NO Refer to the timing charts under I O Circuit Diagrams on page 5 for details Protectio...

Page 3: ...nce X mm Distance Y mm Sensing Head Y X 4 3 2 1 0 3 1 2 0 1 2 3 4 4 Distance X mm Distance Y mm Sensing Head Y X 6 5 4 3 2 1 0 4 2 0 2 4 Distance Y mm Distance X mm Sensing Head Y X 0 6 0 5 0 4 0 3 0...

Page 4: ...er Brass Distance X mm Side length of sensing object d mm Stainless steel SUS304 Iron X 5 4 3 2 1 0 5 35 30 25 15 20 10 d d t 1 mm Distance X mm Side length of sensing object d mm Brass Copper Stainle...

Page 5: ...tor green Operation indicator red Control output 0 V V Load Brown Blue Prox imity Sensor main circuit Note The load can be connected to either the V or 0 V side 0 100 Sensing object Rated sensing dist...

Page 6: ...Permissible Tightening Range and Torque x The tightening torque applied to the E2EC X4D Threaded Cylindrical Models must be 12 N m max Amplifier Mounting Bracket for DC 2 Wire Models Mounting 1 Insert...

Page 7: ...8 25 5 35 5 18 8 dia 5 4 24 2 1 10 3 6 1 6 dia shielded robotics cable Standard length 400 mm 2 9 dia vinyl insulated round robotics cable with 2 conductors Conductor cross section 0 15 mm2 Insulator...

Page 8: ...round cable with 3 conductors Conductor cross section 0 2 mm2 Insulator diameter 1 2 mm Standard length 2 m 2 The cable can be extended up to 50 m separate metal conduit 3 2 5 dia shielded cable Stan...

Page 9: ...t The load short circuit protection function op erates when the power supply is connected with the correct polarity and the power is within the rated voltage range DC 3 Wire NPN Output Sensors DC 2 Wi...

Page 10: ...stive load Non contact control system Inductive load Relay solenoid etc Steady state current inrush current Operating reset voltage current Lamp load Steady state current inrush current Open close fre...

Page 11: ...or is affected by magnetism or static capacitance from an adjacent Sensor and the output is unstable One means of avoiding interference when mounting Proximity Sensors close together is to alternate S...

Page 12: ...o do not use a Proximity Sensor to turn the power supply ON and OFF for electronic devices that use DC half wave rectification In such a case use a relay to turn the power supply ON and OFF and check...

Page 13: ...sert the front of the Sensor into the special Mounting Bracket included or DIN Track 2 Press the rear of the Sensor into the special Mounting Bracket or DIN Track When mounting the side of the Sensor...

Page 14: ...in series with an AND circuit the limit is three Sensors Be careful of the VS value in the diagram at left OR parallel connection In general it is not possible to use two or more Proximity Sensors in...

Page 15: ...M1J T is 5 V Model Type of connection Connection Description DC 3 wire AND series connection Keep the number of connected Sensors N within the range of the following equation iL N 1 i Upper limit of...

Page 16: ...or hot concentrated sulfuric acid Maintenance and inspection Periodic Inspection To ensure long term stable operation of the Proximity Sensor inspect for the following on a regular basis Conduct these...

Page 17: ...may be suitable for the products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control syst...

Reviews: