![background image](http://html1.mh-extra.com/html/omron/e2e-x10my1/e2e-x10my1_datasheet_740839008.webp)
8
Cylindrical Inductive Sensor for AC Power Supply
Installation
Connection
Precautions
Mounting
Do not tighten the nut with excessive force. A washer must be used
with the nut.
Note:
The table below shows the tightening torques for part A and
part B nuts. In the previous examples, the nut is on the sensor
head side (part B) and hence the tightening torque for part B
applies. If this nut is in part A, the tightening torque for part A
applies instead.
Influence of Surrounding Metal
When mounting the E2E / E2F within a metal panel, ensure that the
clearances given in the following table are maintained. Failure to
maintain these distances may cause deterioration in the perfor-
mance of the sensor.
Mutual Interference
When installing two or more Sensors face to face or side by side,
ensure that the minimum distances given in the following table are
maintained.
Note: Figures in the parentheses are for E2F used in combination with an E2F
(i.e., E2F-X
5) that is operating at a different frequency.
E2E-X
@
Y
@ / E2F-X@
Y
@
AC 2-wire Models
Blue
Load
Load
Brown
Brown
Blue
Power
supply
Power
supply
Note:
The load can be connected
as shown above.
Model
Part A
Part B
Length
Torque
Torque
M8
Shielded
9 mm
9 N·m
12 N·m
Unshielded
3 mm
M12
30 N·m
M18
70 N·m
M30
180 N·m
Model
l
d
D
m
n
E2E-
X
@
Y
@
AC 2-
wire
Shielded
M8
0 mm
8 mm
0 mm 4.5 mm 12 mm
M12
0 mm 12 mm
0 mm
8 mm 18 mm
M18
0 mm 18 mm
0 mm 20 mm 27 mm
M30
0 mm 30 mm
0 mm 40 mm 45 mm
Un-
shielded
M8
6 mm 24 mm
6 mm
8 mm 24 mm
M12
15 mm 40 mm 15 mm 20 mm 36 mm
M18
22 mm 55 mm 22 mm 40 mm 54 mm
M30
30 mm 90 mm 30 mm 70 mm 90 mm
Shielded Model
Unshielded Model
Part B Part A
Part B Part A
d dia.
E2F-X1R5
@@
M8
0 mm
8 mm
0 mm 4.5 mm 12 mm
E2F-X25
@@
M12
0 mm 12 mm
0 mm
8 mm 18 mm
E2F-X5
@@
M18
0 mm 18 mm
0 mm 20 mm 27 mm
E2F-X10
@@
M30
0 mm 30 mm
0 mm 40 mm 45 mm
Model
Item
M8
M12
M18
M30
E2E-
X
@
Y
@
AC 2-
wire
Shielded A
20
30 (20)
50 (30) 100 (50)
B
15
20 (12)
35 (18)
70 (35)
Un-
shielded
A
80 120 (60) 200 (100) 300 (100)
B
60 100 (50) 110 (60) 200 (100)
E2F-X1R5
@@
A
20
-
-
-
B
!%
-
-
-
E2F-X25
@@
A
-
30 (20)
-
-
B
-
20 (12)
-
-
E2F-X5
@@
A
-
-
50 (30)
-
B
-
-
35 (18)
-
E2F-X10
@@
A
-
-
- 100 (50)
B
-
-
-
70 (35)
Unit: mm
Model
l
d
D
m
n
A