background image

D-12

Inductive Sensors

DC 3-wire Models / DC 4-wire (NO+NC)

Note 1.

The response frequency is an average value. Measurement conditions are as follows: standard target, a distance of twice the standard 
target distance between targets, and a setting distance of half the sensing distance.

2.

When using any model at an ambient temperature between 

40°C and 

25°C and a power voltage between 30 and 32 VDC, use a load 

current of 100 mA max.

3.

For USA and Canada: Use class 2 circuit only.

Size

M18

M30

Type

Shielded

Non-shielded

Shielded

Non-shielded

Non-shielded

Item

E2AX-M18

@

S08-M1-B

@

E2AX-M18

@

S08-M1-C

@

E2AX-S18

@

S08-M1-B

@

E2AX-S18

@

S08-M1-C

@

E2AX-M18

@

N16-M1-B

@

E2AX-M18

@

N16-M1-C

@

E2AX-S18

@

N16-M1-B

@

E2AX-S18

@

N16-M1-C

@

E2AX-M30

@

S15-M1-B

@

E2AX-M30

@

S15-M1-C

@

E2AX-S30

@

S15-M1-B

@

E2AX-S30

@

S15-M1-C

@

E2AX-M30KN20-M1-B

@

E2AX-M30KN20-M1-C

@

E2AX-S30KN20-M1-B

@

E2AX-S30KN20-M1-C

@

E2AX-M30LN30-M1-B

@

E2AX-M30LN30-M1-C

@

E2AX-S30LN30-M1-B

@

E2AX-S30LN30-M1-C

@

Sensing distance

8 mm

±

10%

16 mm

±

10%

15 mm

±

10%

20 mm

±

10%

30 mm

±

10%

Setting distance

0 to 6.4 mm

0 to 12.8 mm

0 to 12 mm

0 to 16 mm

0 to 24 mm

Differential travel

10% max. of sensing distance

Target

Ferrous metal (The sensing distance decreases with non-ferrous metal.)

Standard target 
(mild steel ST37)

24

×

24

×

1 mm

48

×

48

×

1 mm

45

×

45

×

1 mm

60

×

60

×

1 mm

90

×

90

×

1 mm

Response frequency 
(See note 1.)

500 Hz

400 Hz

250 Hz

100 Hz

100 Hz

Power supply voltage 
(operating voltage range)

12 to 24 VDC. Ripple (p-p): 10% max.
(10 to 32 VDC)

Current consumption 
(DC 3-wire)

10 mA max.

Output type

-B models: PNP open collector
-C models: NPN open collector

Control 
output

Load current 
(See note 2.)

200 mA max. (32 VDC max.)

Residual voltage

2 V max. (under load current of 200 mA with cable length of 2 m)

Indicator

Operation indicator (Yellow LED)

Operation mode 
(with sensing object 
approaching)

-B1/-C1 models: NO 
-B2/-C2 models: NC
-B3/ -C3 models: NO+NC
For details, refer to the timing charts.

Protection circuit

Output reverse polarity protection, Power source circuit reverse polarity protection, Surge suppressor, 
Short-circuit protection

Ambient air temperature

Operating: 

40

°

C to 70

°

C, Storage: 

40

°

C to 85

°

C (with no icing or condensation)

Temperature influence 
(See note 2.)

±

10% max. of sensing distance at 23

°

C within temperature range of 

25

°

C to 70

°

C

±

15% max. of sensing distance at 23

°

C within temperature range of 

40

°

C to 70

°

C

Ambient humidity

Operating: 35% to 95%, Storage: 35% to 95%

Voltage influence

±

1% max. of sensing distance in rated voltage range 

±

15%

Insulation resistance

50 M

Ω

 min. (at 500 VDC) between current carry parts and case

Dielectric strength

1,000 VAC at 50/60 Hz for 1 min between current carry parts and case

Vibration resistance

10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y and Z directions

Shock resistance

1,000 m/s

2

, 10 times each in X, Y and Z directions

Standard and listings 
(See note 3.)

IP65
EMC after EN60947-5-2
ATEX after EN50014

EN50281-1-1/2

Connection method

Please see chapter 'Connectivity' for details on M12 connectors.

Weight 
(pak-
kaged)

Connector model

Approx. 70 g

Approx. 200 g

Approx. 200 g

Approx. 260 g

Material

Case

Brass-nickel plated or stainless steel

Sensing surface

PBT

Clamping nut

brass-nickel plated for brass models stainless steel for steel models

Summary of Contents for E2AX -

Page 1: ...08 M1 B3 NPN E2AX M12KN08 M1 C1 E2AX M12KN08 M1 C2 E2AX M12KN08 M1 C3 56 70 PNP E2AX M12LN08 M1 B1 E2AX M12LN08 M1 B2 E2AX M12LN08 M1 B3 NPN E2AX M12LN08 M1 C1 E2AX M12LN08 M1 C2 E2AX M12LN08 M1 C3 M18 Shiel ded 8 0 mm M12 connector Brass 2 39 53 PNP E2AX M18KS08 M1 B1 E2AX M18KS08 M1 B2 E2AX M18KS08 M1 B3 NPN E2AX M18KS08 M1 C1 E2AX M18KS08 M1 C2 E2AX M18KS08 M1 C3 61 75 PNP E2AX M18LS08 M1 B1 E2...

Page 2: ... S Cylindrical metric threaded stainless steel 4 Housing size 08 8 mm 12 12 mm 18 18 mm 30 30 mm 5 Barrel length K Standard length L Long body 6 Shield S Shielded N Non shielded 7 Sensing distance Numeral Sensing distance e g 02 2 mm 16 16 mm 8 Kind of connection M1 M12 connector 4 pin M3 M8 connector 4 pin M5 M8 connector 3 pin 9 Power source and output B DC 3 wire PNP open collector C DC 3 wire ...

Page 3: ...able length of 2 m Indicator Operation indicator Yellow LED Operation mode with sensing object approaching B1 C1 models NO B2 C2 models NC B3 C3 models NO NC For details refer to the timing charts Protection circuit Output reverse polarity protection Power source circuit reverse polarity protection Surge suppressor Short circuit protection Ambient air temperature Operating 40 C to 70 C Storage 40 ...

Page 4: ...dels PNP open collector C models NPN open collector Control output Load current See note 2 200 mA max 32 VDC max Residual voltage 2 V max under load current of 200 mA with cable length of 2 m Indicator Operation indicator Yellow LED Operation mode with sensing object approaching B1 C1 models NO B2 C2 models NC B3 C3 models NO NC For details refer to the timing charts Protection circuit Output reve...

Page 5: ...dicator Yellow Setting indicator Red NC type Operation indicator Yellow Operation mode D1 models NO D2 models NC Protection circuit Surget suppressor Short circuit protection Ambient temperature Operating 40 C to 70 C Storage 40 C to 85 C with no icing or condensation Temperature influence 10 max of sensing distance at 23 C within temperature range of 25 C to 70 C 15 max of sensing distance at 23 ...

Page 6: ...Load current See note 2 3 to 100 mA Residual voltage 3 V max under load current of 100 mA with cable length of 2 m Indicator see timing chart NO type Operation indicator Yellow Setting indicator Red NC type Operation indicator Yellow Operation mode D1 models NO D2 models NC Protection circuit Surget suppressor Short circuit protection Ambient temperature Operating 40 C to 70 C Storage 40 C to 85 C...

Page 7: ... N16 E2A M12 N08 E2A M30KN20 5 0 4 0 3 0 2 0 1 0 0 d t 1 mm X 5 10 15 20 25 30 35 0 1 0 2 0 3 0 4 0 5 0 7 0 8 0 6 0 10 20 30 40 50 60 d t 1 mm X 0 4 8 12 16 20 10 20 30 40 50 60 70 80 d t 1 mm X Side length of sensing object d mm Brass Iron Sensing distance X mm Stainless steel SUS303 Aluminum Copper Side length of sensing object d mm Brass Iron Sensing distance X mm Copper Stainless steel SUS303 ...

Page 8: ...m Stainless steel SUS303 Copper E2AX M18 N16 E2A S18 N16 Side length of sensing object d mm Sensing distance X mm Iron Copper Brass Aluminum E2AX M30LN30 E2A S30LN30 Side length of sensing object d mm Sensing distance X mm Iron Copper Brass Stainless steel SUS303 Stainless steel SUS303 Aluminum Side length of sensing object d mm Sensing distance X mm 25 20 15 10 5 0 20 40 60 80 100 t 1 mm d X Copp...

Page 9: ...ot used Proximity Sensor main circuits 100 0 Sensing object Rated sensing distance Sensing zone Non sensing zone Proximity Sensor ON OFF ON OFF Yellow indicator Control output 3 1 2 4 Load See note 1 V 0 V M12 Connector Pin Arrangement See note Note Pin 4 of the M12 connector is not used Proximity Sensor main circuits Sensing object 100 0 Rated sensing distance Sensing zone Non sensing zone Proxim...

Page 10: ...12 Connector Pin Arrangement See note 100 0 Sensing object Rated sensing distance Sensing zone Non sensing zone Proximity Sensor ON OFF ON OFF Yellow indicator Control output Load See note 1 V 0 V Note Pin 4 of the M12 connector is not used Proximity Sensor main circuits 3 1 2 4 M12 Connector Pin Arrangement See note Sensing object 100 0 Rated sensing distance Sensing zone Non sensing zone Proximi...

Page 11: ...Proximity Sensor ON OFF ON OFF ON OFF Yellow indicator Red indicator Control output Load Brown Blue V 0 V Load can be connected to V or 0V side 3 1 2 4 M12 Connector Pin Arrangement 100 0 Sensing object Rated sensing distance Sensing zone Non sensing zone Proximity Sensor ON OFF ON OFF Yellow indicator Control output Load Brown Blue V 0 V Load can be connected to V or 0V side 3 1 2 4 M12 Connector...

Page 12: ... Note 1 Operation indicator yellow LED 4 90 Note 2 for NO NC B3 C3 models the total length is 4 mm longer Note 1 Operation indicator yellow LED 4 90 Note 2 for NO NC B3 C3 models the total length is 4 mm longer Note Operation indicator yellow LED 4 90 Note Operation indicator yellow LED 4 90 Note Operation indicator yellow LED 4 90 Two clamping nuts Indicator See note Two clamping nuts Indicator S...

Page 13: ...tal When mounting the E2AX within a metal panel ensure that the clearances given in the following table are maintained Unit mm Note 1 In the case of using the supplied nuts If true flash mounting is necessary apply a free zone of 1 5 mm 2 In the case of using the supplied nuts If true flush mounting is necessary apply a free zone of 4 mm 7 4 56 70 17 M12 1 M12 1 9 2 dia 4 56 70 7 7 17 M12 1 M12 1 ...

Page 14: ...re conditions and other environ mental conditions 5 Check for proper lighting of indicators for models with a set indi cator Never disassemble or repair the Sensor Environment Water Resistivity The Proximity Sensors are tested intensively on water resistance but in order to ensure maximum performance and life expectancy avoid immersion in water and provide protection from rain or snow Operating En...

Reviews: