21
5
Replacing the Unit
5.1
Replacement of Unit at Fixed Assignment
Safety Key Points
Be sure to turn off the power to the slave before making sets.
1
Check DRT2-
AD04/DA02
range.
■When DIP switch 8 is OFF, set with the Configurator.
Check the range that is being used.
①
Double-click the slave to be set on the normal screen,
Open the Edit Device Parameters screen. (In the Maintenance Mode
screen, right-click-"Parameter"-"Edit")
③
Select the tab for the channel whose range you want to check
■When DIP switch 8 is ON, it is not necessary to check the settings using
the DIP switch.
2
Sets R7D-
SV4/YV2 range.
If DRT2-AD04/DA02 range is set to the DIP switch and all channels are
set to the same range, use the DIP switch to set R7D-SV4/YV2 range.
For details on how to set the DIP switch, refer to "4. Switching."
If DRT2-AD04/DA02 range setting is not the same as the Configurator
setting or all channels, set R7D-SV4/YV2 range using the PC
Configurator software.
For details on how to set the PC Configurator software, refer to "4
Setting by PC configuration software".
3
Sets the node
address.
Set the node address of R7D-SV4/YV2/YS2 to the same node address as
DRT2-AD04/DA02.