background image

G-203

F3SL

D

40B

Wiring Example for 1 Sensor and 2 Contactors (with D40B-J2): 
Auto-reset

The configuration in this example is for auto-reset and contactor monitoring.

Wiring Example for 3 Sensors and 2 Contactors (with D40B-J2): 
Auto-reset

The configuration in this example is for auto-reset and contactor monitoring.

Manual Start

If manual start is required, insert start switch S1 between X1 and X2
as shown below. Monitored start is not possible.

Operation Flowchart

M

2

1 A1 +

31

13 23

3

4 A2

X1 X2

32

14 24

KM1

KM2

KM1 KM2

KM1

KM2

Operation Flowchart

Guard door

D40B-J2
Controller

Blue*

Yellow*

Green*

Red*

Fuse

Switch: NO contact

Switch: NC contact

D40B-J2 safety output

KM1, KM2: NC contact

KM1, KM2: NO contact

 Actuator

 Switch

See 

Manual

Start

 on page 9.

Note:

 The circuit in this example is equivalent to a Category 3 circuit.

*This example applies to Standard or Elongated Sensors. The wire colors for the High-temperature Type Sensors are different. Refer to 

Sensor and Controller 

Connection Examples

 on page 10.

M

2

1 A1 +

31

13 23

3

4 A2

X1 X2

32

14 24

KM1 KM2

KM1

KM2

KM1

KM2

Operation Flowchart

Guard door

D40B-J2
Controller

Blue*

Yellow*

Green*

Red*

Fuse

Switch: NO contact

Switch: NC contact

D40B-J2 safety output

KM1, KM2: NC contact

KM1, KM2: NO contact

 Actuator 1

 Switch 1

See 

Manual

Start

 below.

Note 1: 

The circuit in this example is equivalent to a Category 3 circuit.

Note 2: 

If two or more Sensors are connected to one Controller, all of the guard doors must open and close independently. If two or more doors open and close at 
the same time, it is possible that a fault may not be detected.

Note 3: 

Up to six Sensors can be connected to a single Controller.

*This example applies to Standard or Elongated Sensors. The wire colors for the High-temperature Type Sensors are different. Refer to 

Sensor and Controller 

Connection Examples

 on page 10.

Guard door

Guard door

 Actuator 2

 Switch 2

 Actuator 3

 Switch 3

Blue

Yellow

Green

Red

Blue

Yellow

Green

Red

Blue

Yellow

Green

Red

X1 X2

KM1

KM2

Start switch S1

Start switch S1

Switch: NO contact

Switch: NC contact

D40B-J1 safety output

KM1, KM2: NC contact

KM1, KM2: NO contact

F502-EN2-04.book  Seite 203  Dienstag, 26. Juli 2005  5:48 17

Summary of Contents for D40B -

Page 1: ...asy to keep machinery clean Small distortions in the door and me chanical discrepancies can be ab sorbed in the allowable operating range of the magnetic actuator and switch Conforms to Category 3 Mod...

Page 2: ...None 3 m D40B 1B3 10 m D40B 1B10 1 NC 3 m D40B 1D3 10 m D40B 1D10 Elongated Sensor None 3 m D40B 2B3 10 m D40B 2B10 1 NC 3 m D40B 2D3 10 m D40B 2D10 High temperature Type Sensor 1 NC 5 m D40B 3D5C 1...

Page 3: ...r supply voltage 24 VAC DC 24 VAC DC or 110 230 VAC selectable Allowable voltage range Power supply voltage 15 Power consumption 2 0 VA max 4 0 VA max Item Type D40B J1 D40B J2 Rated load Safety conta...

Page 4: ...trol circuit Do not connect a 100 230 VAC power supply to the and terminals Doing so may result in electric shock 3 4 A2 A1 X1 X2 14 32 2 1 13 31 24 23 Control circuit WARNING 16 14 12 10 8 6 4 2 0 6...

Page 5: ...B 1D10 Two 4 2 dia Cable diameter 4 2 dia Switch Actuator 19 19 9 9 4 3 4 3 82 73 64 7 7 5 5 19 19 4 2 4 2 82 9 68 54 4 5 4 5 9 5 10 5 10 Target mark D40B 2B3 D40B 2B10 D40B 2D3 D40B 2D10 Target mark...

Page 6: ...Green D40B J2 Terminal Arrangement M KM1 KM2 KM1 KM2 2 1 A1 13 3 4 A2 X1 X2 14 KM1 KM2 Guard door Fuse D40B J1 Controller Blue Yellow Green Red Operation Flowchart Switch NO contact Switch NC contact...

Page 7: ...n Examples on page 10 M 2 1 A1 31 13 23 3 4 A2 X1 X2 32 14 24 KM1 KM2 KM1 KM2 KM1 KM2 Operation Flowchart Guard door D40B J2 Controller Blue Yellow Green Red Fuse Switch NO contact Switch NC contact D...

Page 8: ...k Auxiliary output D40B 1D Standard models and D40B 2D Elongated models only White Yellow Green Blue Red Actuator Switch 3 2 A1 1 4 A2 X1 21 13 X2 22 14 D40B J1 D40B 3 5C Black Auxiliary output White...

Page 9: ...factory set to 230 VAC Fuse Replacement Method D40B J2 Only Note The D40B J1 has an automatic recovery mechanism and so fuse replacement is not necessary Turn OFF the power to the Controller Open the...

Page 10: ...re to water oil or chemicals Locations subject to dust including iron dust or salts Take appropriate and sufficient countermeasures when using the product in the following locations Locations subject...

Reviews: