Checking Internal Address Allocations for Variables
The following procedure can be used to check the I/O memory addresses
internally allocated to variables.
1,2,3...
1.
Select
View - Symbols - Global.
2.
Select the instance in the global symbol table, right-click, and select
Func-
tion Block/SFC Memory Address
from the pop-up menu. (Alternately,
select
Memory Allocation - Function Block/SFC Memory - Function
Block/SFC Memory Address
from the PLC Menu.)
3.
The FB Interface Memory Dialog Box will be displayed. Check the I/O
memory addresses internally allocated to variables here.
Address
CP1L-L
D0000 to D9999
Provided
D10000 to D31999
Not Provided
D32000 to D32767
Provided
Example: Instance name displayed in global variable table (automatically registered)
Right-click on the instance name and select
Function Block Instance Address.
Example: Addresses used internally
for the input variables.