PID
SCR
System Configuration
●
This system controls one loop.
- A type K thermocouple is used for the temperature sensor input.
- The temperature range is 0.0 to 500.0
°
C.
- The output is 4 to 20 mA and heater control is performed using a Thyristor Unit (Power Controller).
- Continuous proportional PID is set.
Note:
The default operation cycle (1 s) is used.
●
The screen for the Loop Controller is displayed by connecting a NS-series PT (Touch Panel).
Thyristor Unit
(Power Controller)
G3PX
Screen for Loop Controller
NS-series PT
(Touch Panel)
NS12
CX-Process Tool
(Support Software)
Cable (2 m) for
Peripheral Bus (Toolbus)
CS1W-CN226
RS-232C Cable
XW2Z-200T (2 m)
CJ-series Loop-control
CPU Unit
CJ1G-CPU45P
Analog Output Unit
CJ1W-DA041
Temperature sensor
Type K thermocouple
4 to 20 mA
Input 1
Output 1
Note:
The Loop
Controller it-
self does not
have analog
I/O. Therefore,
PLC CPU Bus
Units must be
used.
Ty
the
The
Inpu
CJ1
This section provides an explanation of basic CX-Process Tool operation
using the following simple system as an example.
Isolated-type Ther-
mocouple Input Unit
CJ1W-PTS51
Refer to
Creating Function
Block Data
on the
following page.