Communications Unit
Unit name
CV/CVM1 series
CS-series
Description
Special Units for
communication
[ SYSMAC LINK ]
Coaxial: CV500-SLK21
Optical Fiber Cable:
CV500-SLK11
[ SYSMAC LINK ]
Coaxial: CS1W-SLK21
Optical Fiber: CS1W-SLK11
or
[ Controller Link ]
Wire: CS1W-CLK23
Optical Fiber:
CS1W-CLK13/53
To improve the system performance and maintainability, consider renewaling the system with
Controller Link.
Refer to the following manuals:
Controller Link Units OPERATION MANUAL (Cat. No. W309)
and
SYSMAC Optical Ring Controller Link Units OPERATION MANUAL (Cat. No. W370).
[ SYSNET ]
CV500-SNT31
[ SYSNET ]
None
[ Controller Link ]
Wire: CS1W-CLK23
Optical Fiber:
CS1W-CLK13/53
SYSNET cannot be used with CS-series CPU Units. Consider renewaling the system with Controller
Link.
Refer to the following manuals:
Controller Link Units OPERATION MANUAL (Cat. No. W309)
and
SYSMAC Optical Ring Controller Link Units OPERATION MANUAL (Cat. No. W370).
[ Controller Link ]
Wire: CVM1-CLK21
Optical Fiber Cable:
CVM1-CLK12/52
[ Controller Link ]
Wire: CS1W-CLK23
Optical Fiber:
CS1W-CLK13/53
You have to modify related areas such as status area.
Refer to
Controller Link Units OPERATION MANUAL (Cat. No. W309)
for details.
[ Host Link ]
CV500-LK201
RS232C×1,
RS232C/RS422 ×1
[ Serial Communication Unit ]
CS1W-SCU21-V1(RS232×2),
CS1W-SCU31-V1
(RS422/485×2),
or
[ Seial Communications
Board ]
CS1W-SCB21-V1(RS232×2)
CS1W-SCB41-V1
(RS232×1, RS422/485×1)
You have to change connecting cables and connectors, or modify related areas such as status area.
Refer to
SYSMAC CS/CS Series Serial Communications Board / Serial Communications Unit
OPERATION MANUAL (Cat No. W336
) for details.
[ PC Link ]
CVM1-LK401
[ PC Link ]
C200H-LK401
or
[ Controller Link ]
(Recommended)
Wire: CS1W-CLK23
Optical fiber:
CS1W-CLK13/53
C200H PC Link Uni
efer to the following manuals:
ts can be used. R
SYSMAC C Seriesl
PC Link System Manual (Cat. No. W135)
Consider renewaling the system with Controller Link which has better system performance and
maintainability.
Refer to the following manuals:
Controller Link Units OPERATION MANUAL (W309)
and
SYSMAC Optical Ring Controller Link Units OPERATION MANUAL (W370).
[ DeviceNet ]
CVM1-DRM21(-V1)
[ DeviceNet ]
CS1W-DRM21-V1
or
C200HW-DRM21(-V1)
Both Device Net Units for CS-series and C200H-series can be used.
Consider replacing the system using the CS-series DeviceNet Unit for higher system performance and
maintenance.
You have to modify the I/O allocation areas.
Refer to the following manuals for details:
DeviceNet Unit OPERATION MANUAL (W380)
(for CS/CJ)
DeviceNet Master Units OPERATION MANUAL
(W379) (for C200HW)
[ SYSBUS ]
Wire: C500-RM201.
Optical Fiber Cable:
C500-RM001-(P)(V1)
[ SYSBUS ]
Wire: C200H-RM201
Optical fiber:
C200H-RM001-PV1
or
[ CompoNet ]
CS1W-CRM21
or
[ DeviceNet]
CS1W-DRM21-V1
of
[CompoBus/S]
CS1W-SRM21
C200H SYSBUS Unit can be used with CS-series CPU Units. You have to modify the memory areas.
We recommend you to replace the system with other remote system (CompoNet, DeviceNet or
CompoBus/S) which have better system performance and maintainability.
Refer to
CompoNet Master Units OPERATION MANUAL (W456)
and
CRT1 Series CompoNet Slave
Units and Repeater Units OPERATION MANUAL (W457)
for details of CompoNet.
Refer to
CS/CS Series DeviceNet Units OPERATION MANUAL (W380
) for details of DeviceNet.
Refer to
CompoBus/S OPERATION MANUAL (No. W266)
for details of CompoBus/S.
[SYSMAC BUS/2 ]
Wire:
CV500-RM221 Remote I/O
Master Unit
CV500-RT221 Remote I/O
Slave
Optical Fiber Cable:
CV500-RM211 Remote I/O
Slave
CV500-RT211 Remote I/O
Slave
[SYSMAC BUS/2 ]
None
[ CompoNet ]
CS1W-CRM21
or
[ DeviceNet ]
CS1W-DRM21-V1
or
[ CompoBus/S ]
CS1W-SRM21
SYSMAC BUS/2 Remote I/O cannot be used with CS-series CPU Units. We recommend you to
replace the system with other remote system (CompoNet, DeviceNet or CompoBus/S).
Refer to
CompoNet Master Units OPERATION MANUAL (W456)
and
CRT1 Series CompoNet Slave
Units and Repeater Units OPERATION MANUAL (W457)
for details of CompoNet.
Refer to
CS/CS Series DeviceNet Units OPERATION MANUAL (W380
) for details of DeviceNet.
Refer to
CompoBus/S OPERATION MANUAL (W266)
for details of CompoBus/S.
Support software and Programming devices
Product Name
CV/CVM1 series
CS-series
Description
Support software
CV Support Software
SYSMAC Support Software
CX-Programmer
CX-Programmer Ver.3.0 or
higher
Only CX-Programmer can be used with CS-series CPU Units.
CX-Programmer is included in Omron CX-One FA integrated Tool Package.
Factory intelligent
terminal
FIT10
FIT20
None
Use commercially available personal computers.
PLC-PC connecting
cable
CV500-CIF01
CS1W-CN226/626
(+CS1W-CIF31)
If your PC has no RS232C port, you need to add a USB serial conversion cable.
Programming Console
(Connecting cable)
CV500-PRS21
(CV500-CN[][]4)
C200H-PRO27
(+CS1W-CN[][]4)
or
CQM1-PRO01(+CS1W-CN114
)
A CS1W-CN[][]4 is a connecting cable.
5
Summary of Contents for CV/CVM1
Page 1: ...Replacement Guide CV CVM1 From CV CVM1 to CS1 ...
Page 10: ...MEMO ...
Page 32: ...P076 E1 01 2011 0911 ...