2 Installation procedure
2-1 Rackmount installation (EIA/JIS 19-inch rack, server rack)
BUM5002R/BUM3002R
22
2 Installation procedure
2-1 Rackmount installation (EIA/JIS 19-inch rack,
server rack)
The unit is installed in an EIA/JIS 19-inch rack or server rack.
Warning
When installing onto a rack, be sure to use both the provided
support angles and ear brackets to support and fix this product.
⚫
Support each unit individually with support angles.
⚫
When installing onto a rack, be sure to use both the support angles and
ear brackets provided with this product. The ear brackets alone cannot
support this product without the support angles.
⚫
The mass of each unit is about 84 kg for the BUM5002R, and about 45 kg
for the BUM3002R.
When installing onto a rack, install without a battery pack on the
lowermost shelf of the rack, and after installation install the
battery pack.
⚫
You may be injured if the product is dropped.
Be sure to use the mounting screws provided with this product.
⚫
If long screws not provided with this product are used for installation of
the case, there is a risk of internal damage.
⚫
If screws not provided with this product are used, the structural strength
may become insufficient, and it may lead to an accident such as falling of
this unit.
■ Items in the package used when installing in a 19-inch rack
Support angle (L)
1
Support angle (R)
1
Ear bracket
2
Ear bracket mounting flat-head screws (M3)
8
Fixing screws for EIA/JIS rack (M5)
12
Mounting nuts for EIA rack (M5)
12
Fixing flat-head screws for JIS rack (M5)
2