Safety Precautions
BUM5002R/BUM3002R
13
Be sure to reset the battery life counter after replacing the battery.
After replacing the battery, select [2. Control] - [Reset B. life counter] from the LCD
menu of the UPS main unit, and reset the battery life counter.
⚫
If the battery life counter is not reset, the battery replacement alarm may be issued before the
expected end of the battery life is reached.
Write the battery replacement date on the provided battery replacement date label
and attach it to the main unit.
Or, select [3. Settings] - [Battery Settings] - [Battery Installation] from the LCD menu
of the UPS main unit, and enter the battery replacement date.
After replacing the battery, execute the self-diagnosis test.
The self-diagnosis test can be performed manually from the LCD menu of the UPS
main unit by selecting [2. Control] - [Start Function Test].
After the self-diagnosis test has been completed, the status automatically returns to
the normal operational status.
Before installing the unit, take note of the serial number of the unit.
The serial number of the product is necessary when making inquiries to the shop of
purchase.
The product serial number is included in the information displayed on the seal on
the back of the product, and on the product serial number seal on the packaging.
This product uses a lead battery (lead accumulator).
⚫
Lead batteries are valuable resources that can be recycled. Please cooperate with
recycling. For recycling the unit, contact the shop of purchase.
Pb